ASHRAE NY-08-055-2008 Supply Fan Control Methods for VAV Systems Using a Fan Airflow Station《使用风机气流站变风量系统进气风扇控制方法》.pdf
《ASHRAE NY-08-055-2008 Supply Fan Control Methods for VAV Systems Using a Fan Airflow Station《使用风机气流站变风量系统进气风扇控制方法》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE NY-08-055-2008 Supply Fan Control Methods for VAV Systems Using a Fan Airflow Station《使用风机气流站变风量系统进气风扇控制方法》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、2008 ASHRAE 451ABSTRACT Two supply fan speed control methods for a variableairflow volume (VAV) system using the fan airflow station(FAS) are introduced in this paper. In the first method, thesupply fan speed is controlled to maintain an optimized systemresistance (S), which is calculated based on t
2、he measured fanhead, and airflow. In the second method, the supply fan speedis controlled to maintain the duct static pressure set point,which is reset based on the airflow ratio measured by the FAS.Both methods can make the terminal box open more comparedwith the conventional supply fan speed contr
3、ol using a fixedduct static pressure set point. These innovative methods can beapplied to systems with either direct digital control (DDC) orpneumatic control terminal boxes. The case studies show thatthe new control methods can significantly save supply fanpower and improve fan efficiency.INTRODUCT
4、IONThe ASHRAE handbook 1999 introduces severalcontrol methods for the supply fan in VAV systems. Flow maybe modulated in a VAV system by using dampers on the outletside of the fan, inlet vanes on the fan, vane-axial fans withcontrollable pitch fan blades, or variable-speed control of thefan motor. T
5、ypically, the inputs to any of these controlleddevices are modulated in order to maintain a duct static pres-sure set point. The pressure sensor must be properly placed tomaintain optimum pressure throughout the supply duct. Expe-rience indicates that performance is satisfactory when thesensor is lo
6、cated at 75% to 100% of the distance from the firstto the most remote terminal ASHRAE Application Hand-book, 1999. The pressure selected provides a minimum staticpressure to all air terminal units during all supply fan designconditions. Multiple static sensors are required when morethan one duct run
7、s from the supply fan. The sensor with thehighest static requirement controls the fan. Because duct run-outs may vary, a control that uses individual set points for eachmeasurement is preferred.In a single-duct VAV system, the duct static pressure setpoint is typically selected by the designer to be
8、 a fixed value.The sensor should be located in the ductwork where the estab-lished set point ensures proper operation of the zone VAVboxes under varying load (supply airflow) conditions. A short-coming of this approach is that static pressure control is basedon the readings of a single sensor that i
9、s assumed to representthe pressure available to all VAV boxes. If the design or appli-cation of the sensor malfunctions, or the sensor is placed in alocation that is not representative, operating problems willresult. Another issue is the static pressure set point, which isnormally set at a very high
10、 value to meet the design conditions.However, the building is operated under off-peak conditionsmost of the time. For a fixed static pressure set point, all of theVAV boxes tend to close as the zone loads and flow require-ments decrease. Therefore, the flow resistance increases withdecreasing loads
11、and consumes a significant amount of fanpower.An alternative approach to supply fan control in a VAVsystem uses flow readings from the direct digital control(DDC) zone terminal boxes to integrate zone VAV require-ments with supply fan operations. Significant fan energysavings are possible if the sta
12、tic pressure set point is reset sothat at least one of the VAV boxes remains open. With thisapproach, the duct system resistance remains similar range.Englander and Norford 1992, Hartman 1993, and Warrenand Norford 1993 proposed several different strategies basedSupply Fan Control Methods for VAV Sy
13、stems Using a Fan Airflow StationGuopeng Liu, PhD Mingsheng Liu, PhD, PEAssociate Member ASHRAE Member ASHRAEGuopeng Liu is a senior project engineer of Building Energy Solutions and Technology, Bes-Tech, Inc., Dallas, TX. Mingsheng Liu is aprofessor in the Department of Architectural Engineering, U
14、niversity of Nebraska Lincoln, Omaha, NE.NY-08-0552008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 114, Part 1. For personal use only. Additional reproduction, distribution, or transmission in either prin
15、t or digital form is not permitted without ASHRAEs prior written permission.452 ASHRAE Transactionson this concept. Englander and Norford used simulations toshow that either static pressure or fan speed can be controlleddirectly using a flow error signal from one or more zones andsimple rules. Their
16、 technique forms the basis of the reset strat-egy given below. At each decision interval (e.g., 5 minutes), the followinglogic can be applied:1. Check the controller outputs for representative VAVboxes and determine time-averaged values over the lastdecision interval.2. If any of the controller outp
17、uts are greater than a thresh-old value (e.g., 98%), then increase the static pressure setpoint by a fixed value (e.g., 5% of the design range) andgo to Step 4. Otherwise, go to Step 3.3. If all of the controller outputs are less than a thresholdvalue (e.g., 90%), then decrease the static pressure s
18、etpoint by a fixed value (e.g., 5% of the design range) andgo to Step 4. Otherwise, do not change the set point.4. Limit the set point between upper and lower limits basedon upper and lower flow limits and the duct design.Unfortunately, this method cannot be used in buildingsthat have a pneumatic te
19、rminal box controller. Box malfunc-tion, communication loss, and other issues make this methoddifficult to implement, even for DDC systems. How should system resistance be maintained relativelyconstant for the pneumatic terminal box controller? Thesystem resistance can be calculated as the ratio of
20、fan head tothe square of the airflow. Accurate measurement of airflow inall ranges is necessary and presents a major challenge incontrolling the system resistance at an optimized value.The most common method is to measure the airflowsusing flow stations in the main supply duct and in the mainreturn
21、duct. For accuracy within 5% to 10%, the airflowmeasurement station requires a straight duct for 6 to 10 ductdiameters upstream and 3 duct diameters downstream NEBB1986. Unfortunately, there are very few systems that havesuch duct runs in the main supply and return ducts. Moreover,the air dynamic he
22、ad varies proportionally to the square of theair velocity. When the velocity is reduced to a lower range, thepressure transducer often cannot provide adequate accuracyfor the dynamic head measurement.To increase the accuracy, it is recommended to measurethe airflow at the location with the highest v
23、elocity Kettler1995. The fan inlet is such a place. Fan inlet technology canmeasure the airflow at the fan inlet mounted in the intake bellof the fan. However, the airflow profile in the fan inlet varieswith the total airflow, which results in high uncertainty anddifficulty of measurement. This meth
24、od cannot provide theaccuracy required for the volumetric tracking. The cost of theturbo meter is another limitation.The thermal anemometer or hot-wire anemometer hasbeen used to determine the air velocity at a point in the flowfield. The measurement range is from 0.005 m/s (0.98 ft/min)to 5 m/s (98
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAENY080552008SUPPLYFANCONTROLMETHODSFORVAVSYSTEMSUSINGAFANAIRFLOWSTATION 使用 风机 气流 风量 系统 风扇 控制 方法

链接地址:http://www.mydoc123.com/p-455578.html