ASHRAE HVAC APPLICATIONS IP CH 33-2015 KITCHEN VENTILATION.pdf
《ASHRAE HVAC APPLICATIONS IP CH 33-2015 KITCHEN VENTILATION.pdf》由会员分享,可在线阅读,更多相关《ASHRAE HVAC APPLICATIONS IP CH 33-2015 KITCHEN VENTILATION.pdf(40页珍藏版)》请在麦多课文档分享上搜索。
1、33.1CHAPTER 33 KITCHEN VENTILATIONCOMMERCIAL KITCHEN VENTILATION 33.1Commissioning. 33.1Ventilation Design 33.2System Integration and Design 33.2Energy Considerations. 33.4Commercial Exhaust Hoods. 33.7Cooking Effluent Generation and Control . 33.16Replacement (Makeup) Air Systems. 33.20HVAC System
2、Design . 33.26Exhaust Systems . 33.27Exhaust Fans 33.28Fire Safety 33.29System Commissioning and Air Balancing 33.32Operations and Maintenance. 33.34RESIDENTIAL KITCHEN VENTILATION 33.35Exhaust Systems . 33.35RESEARCH 33.37HIS chapter focuses primarily on commercial kitchen ventila-Ttion (CKV) syste
3、ms in restaurants and institutional food servicefacilities, and incorporates the research and experience (including allsteps of the design process) amassed by TC 5.10 over the past twodecades. Although a brief section on residential kitchen ventilationhas been retained, only minor updates have been
4、incorporated overthe history of this chapter. Given ongoing debate on residentialrange hood performance, TC 5.10 anticipates sponsoring research toprovide a basis for enhanced design of residential kitchen ventilation(RKV) systems.1. COMMERCIAL KITCHEN VENTILATIONKitchen ventilation is a complex web
5、 of interconnected HVAC sys-tems. The main components typically include (1) cooling to addressheat from cooking appliances, (2) replacement air to provide properpressurization during cooking operations, and (3) exhaust to removeheat and effluent generated by cooking appliances. System designincludes
6、 aspects of air conditioning, fire safety, ventilation, buildingpressurization, refrigeration, air distribution, and food serviceequipment. Kitchens are in many buildings, including restaurantsand retail malls (see Chapter 2), hotels (Chapter 6), hospitals(Chapter 8), single- and multifamily dwellin
7、gs (Chapter 1), educa-tional facilities (Chapter 7), and correctional facilities. Each buildingtype has special requirements for its kitchens, but many basic needsare common to all. This chapter provides an understanding of thedifferent components of kitchen ventilation systems and where theycan be
8、applied. Additionally, background information is included toprovide an understanding of the history and rationale behind thesedesign decisions.Kitchen ventilation has at least two purposes: (1) to provide acomfortable environment in the kitchen and (2) to ensure the safetyof personnel working in the
9、 kitchen and of other building occupants.Comfort criteria often depend on the local climate, because somekitchens are not air conditioned. Kitchen ventilation ensures safetyby providing a means to remove the heat, smoke, and grease (cook-ing effluent) produced during normal cooking operations.HVAC s
10、ystem designers are most frequently involved in commer-cial kitchen applications, in which cooking effluent contains largeamounts of grease or water vapor. Residential kitchens typically usea totally different type of hood. The amount of grease produced inresidential applications is significantly le
11、ss than in commercial appli-cations, so the health and fire hazard is much lower.The centerpiece of almost any kitchen ventilation system is anexhaust hood(s), used primarily to remove cooking effluent fromkitchens. Effluent includes gaseous, liquid, and solid contaminantsproduced by the cooking pro
12、cess, and may also include products offuel and even food combustion. These contaminants must beremoved for both comfort and safety; effluent can be potentially life-threatening and, under certain conditions, flammable. Finally, notethat the arrangement of food service equipment and its coordinationw
13、ith the hood(s) can greatly affect the energy used by these systems,which in turn affects kitchen operating costs. Quite often, the hoodselection and appliance layout is determined by a kitchen facilitydesigner. To minimize energy use and ensure a properly designedkitchen ventilation system, the HVA
14、C engineer should reach out tothe kitchen designer and share the practices and ideas presented inthis chapter.SustainabilityKitchens are some of the most intensive users of energy for a givenfloor area when compared to other commercial or institutional occu-pancies. In addition to energy used during
15、 cooking, the kitchen ven-tilation system must address the large amount of heat emitted orconvected into the kitchen from the cooking equipment, and supplyand condition the replacement air needed to support the cookingeffluent exhaust system as well as ensure acceptable indoor environ-mental quality
16、 (IEQ). An additional factor to be considered is thecooking effluent, and any treatments that may be required before itis discharged into the atmosphere.Given these factors, it is imperative that the kitchen ventilationsystem be designed with careful consideration of both first costs andoperating co
17、sts. Maintenance costs should also be considered,including scheduled equipment replacement (such as air filters), anycorresponding labor, and any production down time as a result of themaintenance.To ensure all of these criteria are accounted for in the kitchen ven-tilation design, the integrated bu
18、ilding design approach described inChapter 58 is recommended.1.1 COMMISSIONINGBecause CKV systems are very complex operational environ-ments, it is strongly recommended that ASHRAE Standard 202 andthe recommendations in Chapter 43 for commissioning be followedfor any commercial kitchen ventilation p
19、roject. Sections of thischapter contain the technical information necessary to address allfour phases of commissioning. Addressing the following topics isrecommended when developing and executing any commissioningplan:1. Owners project requirements (OPR)a. System manual outlinei. System selection: s
20、pecific kitchen ventilation use re-quirements (by owner or design team)The preparation of this chapter is assigned to TC 5.10, Kitchen Ventilation.33.2 2015 ASHRAE HandbookHVAC Applicationsii. Type of facility (e.g., commissary, quick service, full service, institutional)iii. Cooking appliances sele
21、ction based on menu, type of cooking, and special/unusual considerations iv. Other considerations1. System cost2. Kitchen space comfort targets3. Energy use and sustainability targets4. Replacement air requirements5. Cooking exhausta. Duct routing and egressb. Effluent control requirementsc. Air dis
22、charge and outlet restrictions6. Other mechanical servicesa. HVAC equipment locationb. Utility services7. Future expansion8. Ongoing maintenance requirements2. Design phasea. Systems manual outline (i.e., design intent): the engineers response to the OPRb. Hood selection based on appliance line up (
23、very critical because it affects exhaust rate)c. Replacement air method, and kitchen air movementd. Accounting for kitchen equipment heat gainse. System control strategies, including demand-controlled kitchen ventilation (DCKV) systemsf. Exhaust effluent control measuresg. Energy saving measuresh. E
24、xhaust system requirementsi. Fire safetyj. Codes and standardsi. NFPA Standard 96ii. ASHRAE Standard 154iii. IMC (ICC 2012)iv. UL Standard 710v. UL Standard 7623. Construction phasea. Submittal review and coordination with all disciplinesb. Installation and execution with end use in mindc. Exhaust d
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEHVACAPPLICATIONSIPCH332015KITCHENVENTILATIONPDF

链接地址:http://www.mydoc123.com/p-454924.html