IEEE 634-2004 en Standard Cable-Penetration Fire Stop Qualification Test《电缆防火鉴定试验》.pdf
《IEEE 634-2004 en Standard Cable-Penetration Fire Stop Qualification Test《电缆防火鉴定试验》.pdf》由会员分享,可在线阅读,更多相关《IEEE 634-2004 en Standard Cable-Penetration Fire Stop Qualification Test《电缆防火鉴定试验》.pdf(28页珍藏版)》请在麦多课文档分享上搜索。
1、IEEE Std 634-2004(Revision ofIEEE Std 634-1978)634TMIEEE Standard Cable-PenetrationFire Stop Qualification Test3 Park Avenue, New York, NY10016-5997, USAIEEE Power Engineering SocietySponsored by theInsulated Conductors Committee11 May 2005Print: SH95297PDF: SS95297Recognized as anAmerican National
2、Standard (ANSI)The Institute of Electrical and Electronics Engineers, Inc.3 Park Avenue, New York, NY 10016-5997, USACopyright 2005 by the Institute of Electrical and Electronics Engineers, Inc.All rights reserved. Published 11 May 2005. Printed in the United States of America.IEEE is a registered t
3、rademark in the U.S. Patent (978) 750-8400. Permission to photocopy portions of any individual standard for educationalclassroom use can also be obtained through the Copyright Clearance Center.Note: Attention is called to the possibility that implementation of this standard may require use of subjec
4、t mat-ter covered by patent rights. By publication of this standard, no position is taken with respect to the existence orvalidity of any patent rights in connection therewith. The IEEE shall not be responsible for identifying patentsfor which a license may be required by an IEEE standard or for con
5、ducting inquiries into the legal validity orscope of those patents that are brought to its attention.iiiCopyright 2005 IEEE. All rights reserved.IntroductionConfining a fire to the area of origin is desirable for a number of reasons, including protecting a structurespersonnel and/or occupants, preve
6、nting excessive damage to a structures equipment and/or contents, andminimizing the consequential loss as a result of the fire. Fire resistant barriers (e.g., wall, floor, and ceilingpartitions) generally provide the primary means of fire containment. However, the effectiveness of a fireresistant ba
7、rrier may be compromised by the quantity, type, and size of openings or penetrations through thebarrier. In the construction of all types of buildings, openings exist through barriers to allow the passage ofmechanical and electrical equipment. Such openings must be closed or sealed in order for the
8、fire resistancerating of the barrier to be maintained. The fire resistance rating of a barrier is generally determined bytesting in accordance with other industry standards (e.g., ASTM E119a, NFPA 251). The fire resistancerating of cable-penetration fire stops is intended to be determined using this
9、 standard. IEEE Std 634 was initially developed to provide qualification test procedures for type testing cable-penetration fire stops when mounted in fire rated barriers. Originally approved by the IEEE Standards Boardon December 15, 1977, IEEE Std 634 remained unchanged until it was withdrawn in A
10、pril of 1990.Subsequently, a Cable-Penetration Fire Stop Qualification working group was formed to revive the standard.The principle changes from the previous version of this standard include general test methodology,acceptance criteria, and rating classification. The updated standard incorporates m
11、odernized fire testingprotocols, such as furnace pressure requirements, variable temperature acceptance criteria based on actualcable properties, and separate rating classifications for cable-penetration fire stops which limit flamepropagation alone or in addition to limiting unexposed side temperat
12、ure rise (e.g., F-ratings and T-ratings). This standard is intended to provide a controlled method by which cable-penetration fire stops can be testedto determine their fire resistance capability. However, this standard does not address the followingconditions related to cable-penetration fire stops
13、. Pressure seals: Some cable-penetration fire stops may also be required to function as a pressure seal to main-tain an existing differential pressure between areas separated by the barrier in which it is installed. This stan-dard does not address the ability of a cable-penetration fire stop to serv
14、e as a pressure resistant seal, eventhough a correlation could be made to a minor pressure rating based on the specific furnace pressure condi-tion under which this test is performed. Ampacity derating due to cable-penetration fire stops: It is recognized that the thermal insulating character-istics
15、 of a cable-penetration fire stop may have an effect on the ampacity of the cables passing through thepenetration. Design of the cable-penetration fire stop should address this effect. However, ampacity consid-erations are not part of this qualification test and, consequently, are not within the sco
16、pe of this standard.Electrical penetration assemblies in containment structures: Electrical penetration assemblies in containmentstructures are not covered in this standard. For guidance in this area, refer to IEEE Std 31TM.Seismic, radiation, aging, and loss-of-coolant accident (LOCA): Although it
17、is recognized that seismic, radi-ation, aging, and LOCA conditions may be required to be considered and evaluated for nuclear powerplants, these effects are not within the scope of this standard. For guidance in these areas, refer to ANSI/IEEE Std 344TMand IEEE Std 323TM.aInformation on references c
18、an be found in Clause 2.This introduction is not part of IEEE Std 634-2004, IEEE Standard Cable-Penetration Fire Stop Qualification Test.ivCopyright 2005 IEEE. All rights reserved.Test limitations and cautions: This test is performed with a specific standard fire. This fire may or may notbe as sever
19、e as fires actually experienced and hence may not predict the performance of the cable penetra-tion fire stop in actual service. It is the judgment of those experienced in the field that relative performanceis accurately portrayed, and the relative values may be used as a basis for engineering judgm
20、ent in a particu-lar design situation. Notice to usersErrataErrata, if any, for this and all other standards can be accessed at the following URL: http:/standards.ieee.org/reading/ieee/updates/errata/index.html. Users are encouraged to check this URL forerrata periodically.InterpretationsCurrent int
21、erpretations can be accessed at the following URL: http:/standards.ieee.org/reading/ieee/interp/index.html.PatentsAttention is called to the possibility that implementation of this standard may require use of subject mattercovered by patent rights. By publication of this standard, no position is tak
22、en with respect to the existence orvalidity of any patent rights in connection therewith. The IEEE shall not be responsible for identifyingpatents or patent applications for which a license may be required to implement an IEEE standard or forconducting inquiries into the legal validity or scope of t
23、hose patents that are brought to its attention.vCopyright 2005 IEEE. All rights reserved.ParticipantsThe following is a list of participants in the Cable-Penetration Fire Stop Qualification Working Group. John White, ChairScott Groesbeck, Vice ChairThe following members of the individual balloting c
24、ommittee voted on this standard. Balloters may havevoted for approval, disapproval, or abstention. When the IEEE-SA Standards Board approved this standard on 15 November 2004, it had the followingmembership:Don Wright, ChairSteve M. Mills, Vice ChairJudith Gorman, Secretary*Member EmeritusAlso inclu
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- IEEE6342004ENSTANDARDCABLEPENETRATIONFIRESTOPQUALIFICATIONTEST 电缆 防火 鉴定 试验 PDF

链接地址:http://www.mydoc123.com/p-1248799.html