VA 22 13 29-2010 SANITARY SEWERAGE PUMPS.pdf
《VA 22 13 29-2010 SANITARY SEWERAGE PUMPS.pdf》由会员分享,可在线阅读,更多相关《VA 22 13 29-2010 SANITARY SEWERAGE PUMPS.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、11-10 22 13 29 - 1 SECTION 22 13 29 SANITARY SEWERAGE PUMPS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION A. Sanitary /centrifugal sewerage pumps c
2、apable of handling 50 mm (2”) solids. / grinder type sewage pumps utilizing an integral stainless steel cutting device system./ B. Pump capacity. See schedule on Drawing. C. Low voltage starters 1.2 RELATED WORK A. Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING. B. Section 22 05 12, GENERAL MOTO
3、R REQUIREMENTS FOR PLUMBING EQUIPMENT. C. SECTION 22 08 00 COMMISSIONING OF PLUMBING SYSTEMS. Requirements for commissioning, systems readiness checklist, and training. D. Section 26 29 11, LOW-VOLTAGE MOTOR STARTERS. 1.3 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODU
4、CT DATA, AND SAMPLES. B. Manufacturers Literature and Data: 1. Pump: a. Manufacturer and model. b. Operating speed. c. Capacity. d. Characteristic performance curves. 2. Motor: a. Manufacturer, /frame and type/. b. Speed. c. Current Characteristics and W (HP). d. Efficiency. C. Certified copies of a
5、ll the factory and construction site test data sheets and reports. D. Complete operating and maintenance manuals including wiring diagrams, technical data sheets and information for ordering replaceable parts: 1. Include complete list indicating all components of the systems. 2. Include complete dia
6、grams of the internal wiring for each item of equipment. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-10 22 13 29 - 2 3. Diagrams shall have their terminals identified to facilitate installation, operation and maintenance. E. Completed System R
7、eadiness Checklist provided by the Commissioning Agent and completed by the contractor, signed by a qualified technician and dated on the date of completion, in accordance with the requirements of Section 22 08 00 COMMISSIONING OF PLUMBING SYSTEMS. 1.4 APPLICABLE PUBLICATIONS A. The publications lis
8、ted below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. B. National Electrical Manufacturers Association (NEMA): ICS 6-1993 (R2006) . Industrial Control and Systems Enclosures 250-2008 . Enclosures for Electrica
9、l Equipment (1000 Volts Maximum) C. Underwriters Laboratories, Inc. (UL): 508-99 (R2008) . Standards For Industrial Control Equipment PART 2 - PRODUCTS SPEC WRITER NOTE: Make material requirements agree with applicable requirements specified in the referenced Applicable Publications. Update and spec
10、ify only that which applies to the project. Coordinate and assure that the electrical characteristics specified below are clearly shown on the proper drawings. 2.1 SANITARY SEWERAGE PUMP SPEC WRITER NOTE: Coordinate and assure that the electrical characteristics specified below are clearly shown on
11、the proper drawings. A. Duplex or multiplex pumps / Centrifugal / Grinder type designed for 60 degrees C (140 degrees F) maximum water service. Driver shall be electric motor. Support shall be rigid type. Systems to include two or more pumps as required by the Contract Documents. Where hazardous env
12、ironment condition exists, explosion proof pumps shall be installed. 1. Pump housings may be cast iron, bronze, or stainless steel. Cast iron housings for submersible pumps shall be epoxy coated. B. Impeller: / Brass, bronze or cast iron, non-clog, to accommodate 50 mm (2”) solids / 316 SS impeller,
13、 440 SS cutter and cutter plates /. C. Shaft: Stainless steel or other approved corrosion-resisting metal. D. Bearings: As required to hold shaft alignment, anti-friction type for thrust. E. Characteristics: Head capacity characteristics shall not permit overloading at any point of the pump curve. P
14、rovided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-10 22 13 29 - 3 SPEC WRITER NOTE: Use NEMA 4 for drip proof (vertical) or NEMA 6P for completely enclosed (submersible). F. Motor: Maximum 40 degrees C (104 degrees F) ambient temperature rise, drip-p
15、roof, voltage and phase as shown in schedule on Electrical drawings conforming to NEMA 250-Type 4. Size the motor capacity to operate pump without overloading the motor at any point on the pump curve. Refer to Section 22 05 12, GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT. G. Starting Switch: M
16、anually-operated, tumbler type, as specified in Section 26 29 11, LOW-VOLTAGE MOTOR STARTERS. H. Automatic Control and Level Alarm: Provide control panel in a / NEMA 1 enclosure for indoors / NEMA 4X enclosure for outdoors / NEMA 7 enclosure for hazardous environment areas /. The controls shall be s
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2213292010SANITARYSEWERAGEPUMPSPDF