1、AMENDMENT 6 23 October 1975 SUPERSEDING AMENDMENT 5 21 February 1974 MILITARY SPECIFICATION MOTOR-GENERATOR: 100 KW This amendment forms a part of Military Specification MIL-M-28903 (MC), dated 12 December 1968, and is approved for use by all Departments and Agencies of the Department of Defense. PA
2、GE 1 1.1: Delete the second sentence and substitute: “The motor input current is to be 3 phase, 416/208 volt (VI, 60 Hz, 4 wire, and the alternator output is to be 100 kilowatts (kw), 0.8 power factor (pf) lagging, 60 or 400 Hz as specified (see 6.21, 3 phase, 4 wire, 120/208 v, reconnectible to 240
3、/416 v.(I 2.1 : Under “SPECIFICATIONS FEDERAL“, add “FF-B-185 - Bearings, Roller, Cylindrical, And Bearings, Roller, Self-Aligning“, PAGE 2 2.1 : Under VSPECIFICATIONS MILITARY“, add: “MIL-M-8380 MIL-G-81322 -Meter; Alternating Current Frequency, Type B-1 (400 Cycle-Aircraft). -Grease, Aircraft, Gen
4、eral Purpose, Wide Temperature Range. I PAGE 3 2.2: Add the following: A AMERICAN IRON AND STEEL INSTITUTE Steel Products Manual for Stainless and Heat Resisting Steel (Application for copies should be addressed to the American Iron and Steel Institute, 350 Fifth Avenue, New York, N. Y. 11218.)“ FSC
5、 6125 E I . L. Licensed by Information Handling ServicesMIL-M=28903(MC) AMENDMENT 6 PAGE 5 3.2.1: Delete third sentence in entirety. PAGE 11 3.5.1 (f): Delete: “causing zero visibility in bright sunlight“ and substitute “conditions specified in method 711.4 of MIL-STD-705.“ 3.5.3 Delete in entirety
6、and substitute: “3.5.3 Operating speed. The operating speed shall not exceed 1,800 revolutions per minute for 60 Hz output sets and 1,846 revolutions for 400 Hz output sets.“ PAGE 12 3.5.9: At end of paragraph, add “class IIB and those portions of class IIIB applicable to motor-generators.“ 3.5.10.4
7、: Delete and substitute: “3.5.10.4 Transit voltage regulation. Performance of the set under transient conditions (as measured and recorded by a magnetic oscillo- graph) shall be as follows: (a) With the set initially operating at no load, rated voltage, and rated frequency of 60 Hz, the characterist
8、ics of the generator and excitation system shall be such that the minimum rms terminal voltage of the generator does not drop to less than 75 percent of the no load voltage when a balanced 3-phase, 0.4 pf (or less) static load having an impedance of 0.5 per unit based on rated generator kilovolt-amp
9、ere is suddenly applied to the output terminals of the generator. When connect- ed to the specified load, the generator shall recover to a minimum of 0.95 per unit within 300 milliseconds (ms) and shall stabilize at or above this voltage. 1 (b) With the set initially at no load and rated voltage, an
10、d . with rated load at rated pf suddenly applied to the load terminals of the set, the minimum instantaneous rms load voltage shall be not less than 90 percent of the no load voltage and the load voltage shall return to rated value within 200 ms.“ PAGE 13 3.5.10.5: Delete the first sentence and subs
11、titute: “Amplitude modu- lation of the output voltage of the generator when operating with its i u #- Page 2 of 8 pages r Licensed by Information Handling Services MIL-M- 28903W 1 MIL-M-28903 (b) bl = 999770b 0091222 5 AMENDMENT 6 intended voltage regulator shall not exceed 15 percent of the peak vo
12、 1 tag e e 3.5.10.6: Delete percent“ and substitute “10 percent.“ PAGE 14 After 3.7.3, add new paragraph as follows: “3.7.4 Repair parts and tools. The contractor shall furnish a rec- ommended listing of spare parts and tools required (see 6.2). No ship- - ment of sets shall be made unless repair pa
13、rts and maintenance tools are included with the shipment or unless approval for shipment of the sets without such items has been received from the contracting officer.“ %E 15 3.8.8: Delete the first sentence and substitute “An insulated wrench, designed to fit the load and supply terminals, shall be
14、 provided.“ PAGE 17 3.9.1 (h) : Line 3: Delete “between the filters and the cooling fa Line 4: Delete “10 inches“ and substitute “4 inches.“ Sentences 3 and 4: Delete in entirety. At end of paragraph, add “Al1 doors shall be vertically mp: - by use of piano-type hinges, shall have quick disconnect l
15、zt,- be fitted to hold each door open at 300 and 900. A d:. . shall be provided over the doors to prevent entry of rain c ,-ha1 1 snow.“ PAGE 18 After 3.10, add new paragraph as follows: “3.10.1 Forklift openings. Openings shall be provided in the skid base to permit insertion of forklift tynes. Eac
16、h opening shall be not less than 11 inches by 3 inches in size. Openings shall be located so that the center of gravity of the set falls approximately midway between the centers of the forklift openings. of the openings shall be not less than 36 inches nor more than 60 inches. The distance between t
17、he centers Page 3 of 8 pages Licensed by Information Handling Services- MIL-M-28903 (6) 63 W 7997706 0073223 7 - MIL-M-28903(MC) AMENDMENT 6 The openings shall be reinforced and equipped with guides so that the set will not be damaged if it is lifted by a forklift, the tynes of which do not extend c
18、ompletely through the skid base. base may be fabricated or formed from AISI-1010-1020 steel plate.“ Tyne guides in the skid PAGE 20 3.11.9: Delete and substitute: “3.11.9 Bearings. Bearing selection will be compatible with the maximum anticipated rotor loads and operating speeds. Sealed bearings con
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILM2890361975MOTORGENERATOR100KW100 千瓦 电动 发电机 PDF

链接地址:http://www.mydoc123.com/p-980358.html