NAVY MIL-E-24652-1985 EXTINGUISHER FIRE AQUEOUS FILM FORMING FOAM (AFFF) 2-1 2 GALLON《水薄膜形成泡沫2-1 2加仑灭火器》.pdf
《NAVY MIL-E-24652-1985 EXTINGUISHER FIRE AQUEOUS FILM FORMING FOAM (AFFF) 2-1 2 GALLON《水薄膜形成泡沫2-1 2加仑灭火器》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-E-24652-1985 EXTINGUISHER FIRE AQUEOUS FILM FORMING FOAM (AFFF) 2-1 2 GALLON《水薄膜形成泡沫2-1 2加仑灭火器》.pdf(13页珍藏版)》请在麦多课文档分享上搜索。
1、MIL-E-24652 q2 777770b 0232773 b r- FEDERAL PPP-B-601 - Boxes Wood Cleated Plywood I PPP-B-621 - Box, Wood, Nailed and Lock-Corner. PPP-B-636 - Boxes, Shipping, Fiberboard. PPP-B-640 - Boxes, Fiberboard, Corrugated, Triple-Wall. S-13-SQ MIL-E-=24652(SH) 28 May 1985 MILITARY SPECIFICATION EXTINGUISHE
2、R, FIRE, AQUEOUS FILM FORMING FOAM, (AFFF), 2-1/2 GALLON This specification is approved for use by the Naval Sea Systems Command, Department of the Navy, and is available for use by all Departments and Agencies of the Department of Defense, 1, SCOPE 1.1 Scope. This specification covers the requireme
3、nts for a 2-1/2 galLon fire extinguisher of the stored-pressure type. It is capable of generating a %ow expansion foam using AFFP concentrate and fresh water. 2 APPLICABLE DOCUMENTS 2,l Government documents;. I_ 2.1.1 Specifications and standards. Unless otherwise specified, the fol- lowing specific
4、ations and standards of the issue listed in that issue of the Department of Defense Index of Specifications and Standards (DODISC) specified in the solicitation form a part of this specification to the extent specified here in e SPECIFICATIONS MILITARY MIL-P-116 - Preservation, Methods of. MIL-S-901
5、 - Shock Tests H.I. (High Impact) Shipboard Machinery, Eluipment, and Systems Requirements for. MIL-L-10547 - Liner, Case, and Sheet, Overwrap, Water Vapor- proof or Waterproof, Flexible. MIL-F-24385 - Fire Extinguishing Agent, Aqueous Film Forming Foam (AFFF) Liquid Concentrate for Fresh and Sea Wa
6、ter. Beneficial comments (recommendations, additions, deletions) and any pertinent data which may be of use in improving this document should be-addressed to: Commander, Naval Sea Systems Cumand, SEA 5523, Department of the Navy, Washington, DC 20362-5101 by using the self-addressed Standardization
7、Document Improvement Proposal (DD Form 1426) appearing ab the end of this document. or by letter. FCC 4210 / THIS DOCUMENT CONTAINS /% PAGES Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-E-29652 92 m 7797706 0232779 STANDARDS FEDERAL FED-STD-H2
8、8 - Screw Thread Standards for Federal Services. FED-STD-H28/2 - Unified Thread Form and Thread Series for BGlts, Screws, Nuts, Tapped Holes and General Applica- t ion. M IL IT ARY MIL-STD-105 - Sampling Procedures and Tables for Inspection by MIL-STD-129 - Marking for Shipment and Storage. MIL-STD-
9、167-1 - Mechanical Vibrations of Shipboard Equipment (Type I - Environmental and Type II - Internally Excited) . Attributes. 2.2.2 - Other Government publications. - The following Government publication forms a part of this specification to the extent specified herein. PUBLICATION DEPARTMENT OF TRAN
10、SPORTATION Code of Federal Regulations, Title 49 Part 17 3.306 ( c (Application for copies should be addressed to the Superintendent of Documents, Government Printing Office, Washington, DC 20402.) (Copies of specifications, standards, and publications required by con- tractors in connection with sp
11、ecific acquisition functions should be obtained from the contracting activity or as directed by the contracting officer.) 2.2 Other publications. The following documents form a part of this speci- fication to the extent specified herein. The issues of the documents which are indicated as DoD adopted
12、 shall be the issue listed in the current DoDISS and the supplement thereto, if applicable. UNDERWKITERS LABORATORIES, INC. (UL) Standard Number 8 - Foam Fire Extinguisher. (Application for copies should be addressed to the Underwriters Laboratories, Inc., 207 East Ohio Street, Chicago, IL 60611.) U
13、NIFORM CLASSIFICATION COMMITTEE AGENT Uniform Freight Classification Ratings, Rules, and Regulations. (Application for copies should be addressed to the Uniform Classification Committee Agent, Tariff Publication Officer, Room 1106, 222 South Riverside Plaza, Chicago, IL 60606.) 2 Provided by IHSNot
14、for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-E-2LIh52 LI2 m 77777Oh 0232775 T m a . c a NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) Pamphlet 11 - Standard for Low Expansion Foam and Combined Agent Sys tems . (Application for copies should be addressed to the Nat
15、ional Fire Protection Association, Battery March Park, Quincy, MA 02269.) (Industry association specifications and standards are generally available for reference from libraries. They are also distributed among technical groups and using Federal agencies. ) 2.3 Order of precedence. - In the event of
16、 a conflict between the text of this specification and the references cited herein, the text of this specifica- tion shall take precedence. 3. REQUIREMENTS 3.1 First article. When specified (see 6.2.1), a sample shall be sub- jected to first article inspection (see 4.2 and 6.3). 3.2 Materials. 3.2.1
17、 Finish. The shell shall be finished with a red enamel protective coating for identification and enhanced corrosion resistance. 3.2.2 Threads. Threads shall be in accordance with FEU-STD-H28 and FED-STD-H28/2. 3.2.3 Recovered materi-. Unless otherwise specified herein, all equip- ment, materials, an
18、d articles incorporated in the products covered by this speci- fication shall be new and shall be fabricated using materials produced from recovered materials to the maximum extent practicable without jeopardizing the intended use. The term “recovered materials“ means materials which have been colle
19、cted or recovered from solid waste and reprocessed to become a source of raw materials, as opposed to virgin raw materials. None of the above shall be interpreted to mean that the use of used or rebuilt products is allowed under this specification unless otherwise specifically specified. 3.3 Fire ex
20、tinguishing agent. The fire extinguishing agent tested for listing by Underwriters Laboratories shall be a solution of liquid AFFF con- centrate and fresh water. The fire extinguisher shall be compatible with the use of AFFF in accordance with MIL-F-24385. 3.4 Weight. The weight of the empty charged
21、 extinguisher, excluding the mounting bracket, shall not exceed 10 pounds. 3.5 Overall dimensions-. The extinguisher and bracket shall be as small as possible consistent with good design and performance. height shall be not greater than 25 inches. The extinguisher 3 Provided by IHSNot for ResaleNo r
22、eproduction or networking permitted without license from IHS-,-,- MIL-E-24652 42 W 777970b 023277b L i 3.6 Design and construction, 3.6.1 Extinguisher. The extinguisher shall be a stored-pressure type - with a rated capacity of 2.5 gallons of AFFF solution and a service pressure of 100 pounds per sq
23、uare inch (lb/in2), rechargeable without the use of special tools or special equipment. tools are defined as those not listed in the Federal Supply catalog, copies of which may be consulted in the office of the Defense Contract Administration Service.) end of the discharge hose. The extinguisher sha
24、ll be listed by Underwriters Laboratories Inc., (UL) in accordance with UL Standard No. 8, and shall have a minimum fire extinguishing rating of 3-A:20-B. The extinguisher shall be easily (Special The flow shall be controlled by a shut off valve at the extinguisher 3.6.2 Extinguisher components. The
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILE246521985EXTINGUISHERFIREAQUEOUSFILMFORMINGFOAMAFFF212GALLON 薄膜 形成 泡沫 212 加仑 灭火器 PDF

链接地址:http://www.mydoc123.com/p-979028.html