NAVY DOD-STD-2145-1983 DISCONNECT SWITCH BOXES CONTACTOR PANELS AND SWITCHBOARDS LOW MAGNETIC FIELD DESIGN OF (METRIC)《低磁场设计接触器板及配电盘分离式电闸盒(公制)》.pdf
《NAVY DOD-STD-2145-1983 DISCONNECT SWITCH BOXES CONTACTOR PANELS AND SWITCHBOARDS LOW MAGNETIC FIELD DESIGN OF (METRIC)《低磁场设计接触器板及配电盘分离式电闸盒(公制)》.pdf》由会员分享,可在线阅读,更多相关《NAVY DOD-STD-2145-1983 DISCONNECT SWITCH BOXES CONTACTOR PANELS AND SWITCHBOARDS LOW MAGNETIC FIELD DESIGN OF (METRIC)《低磁场设计接触器板及配电盘分离式电闸盒(公制)》.pdf(22页珍藏版)》请在麦多课文档分享上搜索。
1、DOD-STD-2145 bL 97997LL 0012614 1 9 1 F IMETRIC 1 DOD-STD-2145(SH) 1 June 1983 MILITARY STAhTDARD DISCONNECT SWITCH BOXES, CONTACTOR PANELS AND SWITCHBOARDS, LOW MAGNETIC FIELD DESIGN OF (METRIC) Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-I . :-
2、 DOD-STD-2145(SH) 1 June 1983 DEPARTMENT OF THE NAVY NAVAZ, SEA SYSTEMS COMMAND Washington, DC 20362 Disconnect Switch Boxes, Contactor Panels and Switchboards, Low Magnetic Field Design of (Metric). DOD-STD-2145(SH) 1; This Military Standard is approved for use by the Naval Sea Systems Command, Dep
3、artment of the Navy, and is available for use by all Departments and Agencies of the Department of Defense. 2. Beneficial comments (recommendations, additions, deletions) and any pertinent data which may be of use in improving this document should be addressed to: Commander, Naval Sea Systems Comman
4、d, SEA 5523, Department of the Navy, Washington, DC 20362 by using the self-addressed Standardization Document Improvement Proposal (DD Form 1426) appearing at the end of this document or by letter. ii : -. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS
5、-,-,-I . ?. . t Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-DOD-STD-2195 61 m 7777711 0012b21 7 W DOD-STD-2145(SH) 1 June 1983 3.1.13 Three-terminal device. A three-terminal device is equipment in wiiich three terminals, one positive and two nega
6、tive, or two positive and one negative, project from the device for connection to a cable run. The device (that is, disconnect switch boxes and contactor panels) may have inultiple sets of three terminals for incoming and outgoing cable runs. 3.1.14 Two-terminal device. A two-kerminal device is equi
7、pment. in which two terminals, one positive and one negative, project from the device to a cable run. 4. G3NEA.L REQUIREMENTS 4.1 Conductor and device arrangement. Conductors for and the devices in the power circuits for disconnect switch boxes, contactor panels, switchboards, power panelS.and motor
8、 controllers shall be physically arranged and intercon- nected in a manner that will result in circuits which produce a minimum stray magnetic field. 4.2 Simplicity of conductor and device arrangement. Arrangement of con- ductors and devices for the power circuits shall be uncomplicated and straight
9、- forward and, at the same time, produce a minimum stray niagnetic field. 4.3 magnetic moment separation. circuits shall be kept as small as possible to minimize the magnetic moments of the current loops. The distance between these current loops shall also be miniinized. required by khe electrical c
10、reepage and clearance distances of the applicable specification for the disconnect switch boxes, contactor panels, switchboards, power panels and motor controllers. Arrangement of power circuit for minimum magnetic moment and minimum The siz,e of current loops, created by the power Conductor and dev
11、ice separation shall be kept to the minimum 4.4 Arrangement of power circuit for minimum net magnetic moment. Current loops created by the power circuits shall be arranged such that the resultant or net magnetic moment will be minimized. 4.4.1 Utilization of parallel compensation in the arrangement
12、of power circuits. Parallel compensation shall be utilized in the arrangement of power circuits in order to assist in achieving a minimum net magnetic moment. Elec- trical resistance of parallel conductors shall be equalized, as required by a particular circuit arrangement, so that maximum parallel
13、compensation is achieved. 4.5 External cable connections to disconnect switch boxes and contactor panels. External cable connections shall be made in accordance with DOD-STD-2133. 4.6 Material. Material used in the construction of disconnect switch- boxes, contactor panels, switchboards, power panel
14、s and motor controllers shall conform to the material requirements of DOD-STD-2143. 3 f“ . Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-DOD-STD-2145 b1 9777731 0032b22 O a DOD-STD-2145(SH) 1 June 1983 5. DETAILED REQUIREMENTS 5.1 Basic conductor a
15、rrangement. The basic arrangement of conductors in disconnect switch boxes, contactor panels, switchboards, power panels and motor controllers shall be a central conductor carrying two units of current in one direction sandwiched between two symme,trically placed conductors each carrying one unit of
16、 current in the opposite direction, as illustratedon figure 2. basic conductor arrangement is compatible with the three-terminal arrangements for magnetic minesweep quad cable runs in accordance with DODiSTD-2133. Consequently, disconnect switch boxes and contactor panels with this basic conductor a
17、rrangement are three-terminal devices. The 52 Conductor bends. Conductor bends can be one of two types: (a) the conductors lie in different planes on each side of the bend or (b) the conductors lie in the same plane on each side of the bend. 5.2.1 Conductors lying in different planes on each side of
18、 the bend. Bending of conductors shall.be accomplished as illustrated on figure 3 when the conductors lie in different planes on each side of the bend. This arrangement will result in zero net magnetic moment of current when the currents in the two outside conductors are equal. 5.2.2 Conductors lyin
19、g in the same plane on each side of the bend. Bending of conductors shall be accomplished as illustrated on figure 4 when the conduc- tors lie in the same plane on each side of the bend. result in zero net magnetic moment of current when the currents in the two outside conductors are equal. This arr
20、angement is difficult to accomplish in practice. Consequently, the preferred power circuit arrangements for dis- connect switch boxes and contactor panels (see 5.4.2) utilizes conductor bends lying in different planes on each side of the bend. This arrangement will -5.3 Devices in power circuits. De
21、vices in power circuits are usually series connected devices, such as ammeter shunts and overload relays. These devices are two-terminal devices and can be connected directly into the circuit or first converted to a three-terminal device and then connected into the circuit. 5.3.1 Direct connection o
22、f devices into the circuit. Direct connection of devices into the circuit shall be accomplished by inserting the device into the circuit of the central conductor on figure 2. The two outer conductors shall be spread symetrically around each side of the device. 5.3.2 Conversion to a three-terminal de
23、vice. If a two-terminal device is placed in a three-terminal box, it shall be connected into the circuit as Illustrated on figure 5. 5.4 Power circuit arrangements. Power circuit arrangements shall be of the folded or crisscross type. not be used. The straight-through type of arrangement shall 5.4.1
24、 Straight-through arrangement. The straight-through arrangement, as illustrated on figure 6 for a disconnect switch box, shall not be used since the creation of a low-stray magnetic field with this design is very dependent upon equal current division between the two outer conductors. 4 .- Provided b
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYDODSTD21451983DISCONNECTSWITCHBOXESCONTACTORPANELSANDSWITCHBOARDSLOWMAGNETICFIELDDESIGNOFMETRIC 磁场

链接地址:http://www.mydoc123.com/p-976746.html