NAVISTAR CEMS BT-39-2009 Determination Of Nonabsorbable Gas In Air Conditioner Refrigerant.pdf
《NAVISTAR CEMS BT-39-2009 Determination Of Nonabsorbable Gas In Air Conditioner Refrigerant.pdf》由会员分享,可在线阅读,更多相关《NAVISTAR CEMS BT-39-2009 Determination Of Nonabsorbable Gas In Air Conditioner Refrigerant.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、 This document is restricted and may not be sent outside Navistar, Inc. or reproduced without permission from Corporate Technical Standards. Suppliers are required to assume all patent liability. 2009 by Navistar, Inc. AUGUST 2009 Page 1 of 6 NAVISTAR, INC. CEMS (CORPORATE ENGINEERING MATERIAL SPECI
2、FICATION) NUMBER: CEMS BT-39 TITLE: Determination Of Nonabsorbable Gas In Air Conditioner Refrigerant CURRENT ISSUE DATE: August 2009 WRITTEN/REVIEWED BY: Materials Engineering APPROVED BY: Materials Engineering SUPERSEDES ISSUE OF: October 2001 PRINTED COPIES OF THIS DOCUMENT MUST BE VERIFIED FOR C
3、URRENT REVISION This specification may involve hazardous materials, equipment, and procedures. This specification does not purport to address all of the safety issues associated with its use. The user is responsible to consult appropriate safety and health practices and to determine the applicabilit
4、y of regulatory limits prior to use. Change Notice: Replaced “International Truck and Engine Corporation” with “Navistar, Inc.” per corporate directive. 1.0 SCOPE This is a method for determining the volume percentage of nonabsorbable gas in air conditioner refrigerant. (This method adapted from “De
5、termination of Nonabsorbable Gas in Fluorocarbon Products”, DuPont Test Method B-38.) 2.0 APPARATUS 2.1 Special absorption vessel, No. LG-11119, available from Labglass, Inc., Northwest Boulevard, Vineland, NJ 08360. (See Figure 1, page 4.) 2.2 250 milliliter leveling bulb. 2.3 Glass tee. 2.4 Pinch
6、clamp. 3.0 MATERIAL 3.1 Distilled water. 3.2 Tygon tubing. 3.3 Reagent grade perchloroethylene (tetrachloroethylene). 3.4 “Siliclad” (silicone concentrate) obtainable from the Scientific Glass Apparatus Company, Inc., 737 Broad Street, Bloomfield, NJ 07003. CAUTION: Perchloroethylene is toxic and Si
7、liclad is both toxic and flammable. These materials must be used in adequate ventilation. 4.0 PROCEDURE 4.1 Prepare the special absorption vessel as follows: 4.1.1 wash the vessel in soap and water, and rinse in clear distilled water; 4.1.2 prepare a solution of one part by volume “Siliclad” to 100
8、parts by volume distilled water; 4.1.3 swirl the “Siliclad” solution inside the absorption vessel, completely coating the inner surfaces, allow to stand for at least 5 minutes, and then discard the excess solution; 4.1.4 rinse the vessel with clear distilled water and dry at 212 + 3F (100 + 1C) for
9、at least ten minutes: 4.1.5 the absorption vessel must be re-treated in the foregoing manner when water begins to form droplets instead of a thin film on the vessel walls. NUMBER: CEMS BT-39 TITLE: Determination Of Nonabsorbable Gas In Air Conditioner Refrigerant CURRENT ISSUE DATE: August 2009 This
10、 document is restricted and may not be sent outside Navistar, Inc. or reproduced without permission from Corporate Technical Standards. Suppliers are required to assume all patent liability. 2009 by Navistar, Inc. AUGUST 2009 Page 2 of 6 4.2 After cooling the vessel, attach it to the leveling bulb w
11、ith tubing. Add 20 to 25 milliliters of distilled water to the bulb and allow it to flow into the vessel. Fill the bulb and vessel with enough perchloroethylene previously saturated with both air and water to force the water in the vessel into the stopcock stem. Make certain that the water level rea
12、ches the top of the stopcock stem. Saturated perchloroethylene may be made by bubbling undried air through it. 4.3 Add sufficient water to the leveling bulb to form a water seal in the bulb, also. See Figure 2, page 5. 4.4 Attach the absorption vessel-leveling bulb combination and the glass tee-pinc
13、h clamp combination to the sampling source with Tygon tubing as shown in Figure 2, page 5. 4.5 Close the stopcock on the absorption vessel, open the pinch clamp and purge the lines to remove residual air. Purging must be done with the sample container inverted; also, purging must be conducted at a r
14、ate slow enough to prevent the introduction of liquid refrigerant into the connecting tube. 4.6 Close the pinch clamp and then close the valve on the sample source. Return the sample container to the upright position. Open the stopcock on the absorption vessel, and then open and adjust the valve on
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVISTARCEMSBT392009DETERMINATIONOFNONABSORBABLEGASINAIRCONDITIONERREFRIGERANTPDF

链接地址:http://www.mydoc123.com/p-962038.html