1、AMSC N/A 5925 INCH-POUND MIL-DTL-24347B w/ Amendment 2 07 May 2008 SUPERSEDING MIL-DTL-24347B w/ Amendment 1 06 September 2002 DETAIL SPECIFICATION MONITOR, AVAILABLE LOAD, 60 AND 400 HERTZ, A.C., 1 PHASE, ELECTRICAL POWER (NAVAL SHIPBOARD USE) This specification is approved for use by all Departmen
2、ts and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This specification covers an available load monitor (ALM-2) to be used for sensing a load on either a 115 or 440 volt single phase circuit of either 60 or 400 hertz (Hz). ALM-2 is a direct replacement for ALM-1. ALM-1 is not to be pro
3、cured for new constructions or replacement purposes. 2. APPLICABLE DOCUMENTS 2.1 General. The documents listed in this section are specified in sections 3, 4 or 5 of this specification. This section does not include documents cited in other sections of this specification or recommended for additiona
4、l information or as examples. While every effort has been made to ensure the completeness of this list, document users are cautioned that they must meet all specified requirements of documents cited in sections 3, 4 or 5 of this specification, whether or not they are listed. 2.2 Government documents
5、. 2.2.1 Specifications, standards, and handbooks. The following specifications, standards, and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract (see 6 2). DEPARTMENT OF DEF
6、ENSE SPECIFICATIONS MIL-S-901 - Shock Tests, H.I. (High-Impact); Shipboard Machinery, Equipment and Systems, Requirements for. MIL-E-917 - Electric Power Equipment, Basic Requirements. MIL-E-2036 - Enclosures for Electric and Electronic Equipment, Naval Shipboard. MIL-DTL-15024 - Plates, Tags and Ba
7、nds for Identification of Equipment. General Specification for. MIL-P-15024/5 - Plates, Identification. MIL-PRF-19500 - Semiconductor Devices. General Specification for. Comments, suggestions, or questions on this document should be addressed to: Defense Supply Center, Columbus, ATTN: DSCC-VAT, Post
8、 Office Box 3990, Columbus, Ohio 43218-3990 or by email CircuitProtectdla.mil. Since contact information can change, you may want to verify the currency of this address information using the ASSIST Online database at http:/assist.daps.dla.mil. Provided by IHSNot for ResaleNo reproduction or networki
9、ng permitted without license from IHS-,-,-MIL-DTL-24347B w/ Amendment 2 2 DEPARTMENT OF DEFENSE STANDARDS MIL-STD-167-1A - Mechanical Vibrations of Shipboard Equipment (Type I - Environmental and Type II - Internally Excited). MIL-STD-461 - Requirements for the Control of Electromagnetic Interferenc
10、e Characteristics of Subsystems and Equipment. MIL-STD-810 - Environmental Engineering Considerations and Laboratory Tests. MIL-STD-1399-300A - Interface Standard for Shipboard Systems Section 300A Electric Power, Alternating Current (Metric). DEPARTMENT OF DEFENSE HANDBOOKS MIL-HDBK-470 - Designing
11、 and Developing Maintainable Products and Systems, Volume I. MIL-HDBK-781 - Reliability Test Methods, Plans, and Environments for Engineering Development, Qualification, and Production. (Copies of these documents are available online at http:/assist.daps.dla.mil/quicksearch/ or http:/assist.daps.dla
12、.mil or from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia, PA 19111-5094). 2.3 Order of precedence. Unless otherwise noted herein or in the contract , in the event of a conflict between the text of this document and the references cited herein, the text of t
13、his document takes precedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. 3. REQUIREMENTS 3.1 First article. When specified (see 6.2), a sample shall be subjected to first article inspection (see 6.4) in accordance wit
14、h 4.2. 3.2 General requirements. The enclosure and hardware material shall be of corrosion resistance material. The monitor fabricated of static components, shall be in accordance with MIL-E-917, and the requirements of this specification except as otherwise specified in the contract or order. If an
15、y requirement specified herein conflicts with the requirements of MIL-E-917, the requirements of this specification shall govern. 3.2.1 Pure tin. The use of pure tin, as an underplate or final finish, is prohibited both internally and externally. Tin content of the available load monitor components
16、and solder shall not exceed 97 percent, by mass. Tin shall be alloyed with a minimum of 3 percent lead, by mass (see 6.7). 3.2.2 Painting. Parts not fabricated of a corrosion-resisting material or having a corrosion-resistant treatment as specified in MIL-E-917, except for semi-conductors, shall be
17、painted as specified in MIL-E-917. One coat of gray enamel or epoxy shall be applied to the outside of the enclosure. Touching-up will be permitted for marks or scratches due to factory handling. Powder coat which meets the color requirement is permissible. 3.3 Definitions. Definitions shall be as s
18、pecified in MIL-STD-1399-300A. 3.4 Performance. The single phase monitor shall perform the functions specified herein when connected in either a single or three phase main power circuit of either 115 or 440 normal voltage and either a 60 or 400 Hz normal frequency. The monitor shall operate within t
19、he specified limits when the voltage is reduced to 85 percent of normal or raised to 10 percent above normal. The operating frequency range shall be plus or minus 5 percent of normal. A typical monitor external wiring diagram is shown on figure 1. The monitor shall receive its voltage from the load
20、side connections of the disconnect device. Under the above conditions, the monitor shall permit the load disconnect to close and stay latched if a load of 1-1/2 amperes (plus or minus 15 percent) exists. When the load current is reduced below 1-1/2 amperes (plus or minus 15 percent), the monitor sha
21、ll actuate its normally open single contact static device to close and cause the disconnect device to open. Upon receipt of a signal, the contact shall have a delay adjustable from 5 seconds to 30 seconds before it operates. If current goes above 1-1/2 amperes before the set delay time, the monitor
22、shall reset. The delay time shall be set at 15 seconds unless otherwise directed in the contract or order. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-24347B w/ Amendment 2 3 3.4.1 Contact device. The static single contact device in the m
23、onitor is considered normally open when normal voltage and a load current of 1-1/2 amperes (plus or minus 15 percent) or more is available at the monitor. The normally open contact shall have a minimum continuous rating of 10 amperes, and intermittent rating of 15 amperes. 3.4.2 Input power. The mon
24、itor shall meet the performance requirements of 3.4 when powered in accordance with MIL-STD-1399-300A, types II and III. 3.5 Static components. Static components shall be in accordance with MIL-E-917. JAN, JANTX, JANTXV semiconductors in accordance with MIL-PRF-19500 are preferred. It is recommended
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DLAMILDTL24347B22008MONITORAVAILABLELOAD60AND400HERTZAC1PHASEELECTRICALPOWERNAVALSHIPBOARDUSEPDF

链接地址:http://www.mydoc123.com/p-690187.html