ASTM E2750-2011 Standard Guide for Extension of Data For Penetrations Seals《渗透密封层数据的扩展标准指南》.pdf
《ASTM E2750-2011 Standard Guide for Extension of Data For Penetrations Seals《渗透密封层数据的扩展标准指南》.pdf》由会员分享,可在线阅读,更多相关《ASTM E2750-2011 Standard Guide for Extension of Data For Penetrations Seals《渗透密封层数据的扩展标准指南》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2750 11An American National StandardStandard Guide forExtension of Data For Penetrations Seals1This standard is issued under the fixed designation E2750; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of las
2、t revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This guide covers the extension of results obtained fromfire tests performed in accordance with Test Method E814 toapplic
3、ations that have not been tested. Test Method E814evaluates the duration for which test specimens will contain afire, retain their integrity, or both during a predetermined firetest exposure. Firestops are intended for use in fire-resistivewalls and floors that are evaluated in conformance with Test
4、Method E119.NOTE 1Data obtained from firestops tested in accordance with TestMethods E119 with positive pressure can also be used.1.2 This guide is based on principles involving the exten-sion of test data using simple considerations. The acceptance ofthese principles and their application is based
5、substantially onan analogous worst-case proposition.1.3 These principles are only applicable to temperatureconditions represented by the standard time-temperature curvedescribed in Test Method E814, for systems falling within thescope of Test Method E814. This test method is a fire-test-response sta
6、ndard.1.4 The types of building constructions which are part ofthis guide are as follows: floors, walls, partitions, floor/ceilingand roof/ceiling assemblies.1.5 This guide applies to:1.5.1 a single penetrating item, or1.5.2 multiple penetrating items.1.6 This guide does not apply to joints systems
7、tested toE119, E1966 and E2307.1.7 Penetrating items can be one of the following: metallicpipe, non-metallic pipe, metallic tubing, non-metallic tubing,metallic conduit, non-metallic conduit, flexible metal conduit,cables, cable trays, bus ducts, insulated pipes, insulated tubing,insulated conduit,
8、insulated and non-insulated ducts, and struc-tural members.Metallic pipe, tubing or conduit 6.7Insulated pipe, tubing or conduit 6.8Non-metallic pipe, tubing or conduit 6.9 and 6.10Flexible metal conduit 6.11.1.4 and 6.11.1.5Cables 6.11Cable tray 6.12Bus duct 6.13Non-insulated duct 6.14Insulated duc
9、t 6.14.2Non-structural or service support member 6.15Mixed penetrations 6.161.8 Assemblies can be one of the following; concrete floorsor walls, masonry walls, gypsum walls, wood floor/ceilingassemblies, concrete floor/ceiling assemblies, chase wall infloor/ceiling assemblies and fire-rated insulate
10、d walls.Concrete floors or walls 6.1Masonry walls 6.1Gypsum board wall assemblies 6.2Wood floor/ceiling assemblies 6.3Floor/ceiling assembly with concrete floor 6.4Chase wall intersecting a floor/ceiling assembly 6.5Fire-resistance insulated walls 6.61.9 The extension of data using numerical calcula
11、tionsbased on empirical data or theoretical models is not covered inthis guide.1.10 This guide does not cover the substitution of oneproprietary material for another proprietary material, or mate-rials for which fire-test data are not presently available.1.11 This guide is used to predict or provide
12、 a quantitativemeasure of the fire hazard from a specified set of fire conditionsinvolving specific materials, products, or assemblies. Thisassessment does not necessarily predict the hazard of actualfires which involve conditions other than those assumed in theanalysis.1.12 This guide is used to me
13、asure and describe the re-sponse of materials, products, or assemblies to heat and flameunder controlled conditions, but does not by itself incorporateall factors required for fire hazard or fire risk assessment of thematerials, products or assemblies under actual fire conditions.1.13 The values sta
14、ted in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard.1This standard guide is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibility of Subcommittee E05.11 on FireResistance.Current edition approved May 1, 20
15、11. Published June 2011. DOI: 10.1520/E2750-11.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.1.14 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the
16、user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationE119 Test Methods for Fire Tests of Building Constructionand M
17、aterialsE176 Terminology of Fire StandardsE631 Terminology of Building ConstructionsE814 Test Method for Fire Tests of Penetration FirestopSystemsE1966 Test Method for Fire-Resistive Joint SystemsE2032 Guide for Extension of Data From Fire ResistanceTests Conducted in Accordance with ASTM E 119E2307
18、 Test Method for Determining Fire Resistance ofPerimeter Fire Barriers Using Intermediate-Scale, Multi-story Test Apparatus2.2 Other Standards:ACI 216 Fire Resistance of Concrete33. Terminology3.1 Definitions:3.1.1 For definitions used in this guide, refer to Terminolo-gies in E176, C168 and E631.3.
19、1.2 For definitions of terms specific to this standard, referto E814 and E2032.4. Significance and Use4.1 The methods and procedures set forth in this guide relateto the extension of the fire test results to firestop systems thathave not been tested.4.2 Users of this guide must have knowledge and un
20、der-standing of the provisions of Test Method E119 and TestMethod E814 including those pertaining to conditions ofacceptance.4.3 In order to apply some of the principles described in thisguide, reference to the original fire test report will be necessary.4.4 In Test Method E814, the specimens are su
21、bjected tospecific laboratory fire test exposure conditions. Differencesbetween the tested assembly and the as-built assembly impactthe fire-test-response characteristics. Substitution of differenttest conditions also impacts the fire-test-response characteris-tics.4.5 The extension of data is valid
22、 only for the fire testexposure described in Test Method E814.4.6 This guide shall not be used to extrapolate the fireresistance rating to a higher value.4.7 Limitations:4.7.1 The extension of fire resistance data is to be used onlyfor changes to the tested specimen that fall within normal andreason
23、able limits of accepted construction practices.4.7.2 Conclusions derived from using this guide are validonly if the identified change is the only change in theconstruction or properties of the components.4.7.3 Evaluation of changes to the fire-resistive assembly inwhich the firestop is installed is
24、governed by the Extension ofData principles in Guide E2032.4.8 The statements in this guide are based on a singlechange to a system.NOTE 2It is possible that multiple changes have a different cumula-tive effect than that of individual changes evaluated separately. Theprinciples contained herein may
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME27502011STANDARDGUIDEFOREXTENSIONOFDATAFORPENETRATIONSSEALS 渗透 密封 数据 扩展 标准 指南 PDF

链接地址:http://www.mydoc123.com/p-531819.html