1、Designation: E2226 10An American National StandardStandard Practice forApplication of Hose Stream1This standard is issued under the fixed designation E2226; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision.
2、 A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INTRODUCTIONSeveral fire-test-response standards (such as ASTM E119, E814, E2074, and E1966) in order toassess the integrity of building element
3、s after exposure to a specified test fire, require test specimensto be evaluated by exposure to a hose stream. It is important to standardize certain elements of the hosestream to promote uniformity in requirements. To attain this goal, this practice describes a standardapparatus for delivering a so
4、lid stream of water and prescribes a standard method of subjectingbuilding elements to a hose stream after fire exposure.1. Scope*1.1 This practice is applicable to building elements requiredto be subjected to the impact, erosion, and cooling effects of ahose stream as part of a fire-test-response s
5、tandard. Buildingelements include, but are not limited to, wall and partitionassemblies, fire-resistive joint systems, and doors.1.2 This practice shall register performance of the buildingelement under specific hose stream conditions. It shall notimply that, either after exposure or under other con
6、ditions, thestructural capability of the building element is intact or that thebuilding element is suitable for use.1.3 The result derived from this practice is one factor inassessing the integrity of building elements after fire exposure.The practice prescribes a standard hose stream exposure forco
7、mparing performance of building elements after fire expo-sure and evaluates various materials and construction tech-niques under common conditions.1.4 UnitsThe values stated in inch-pound units are to beregarded as standard. The values given in parentheses aremathematical conversions to SI units tha
8、t are provided forinformation only and are not considered standard.1.5 The text of this standard references notes which provideexplanatory material. These notes shall not be considered asrequirements of the standard.1.6 This fire standard cannot be used to provide quantitativemeasures.1.7 This stand
9、ard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 AS
10、TM Standards:2E119 Test Methods for Fire Tests of Building Constructionand MaterialsE176 Terminology of Fire StandardsE631 Terminology of Building ConstructionsE814 Test Method for Fire Tests of Penetration FirestopSystemsE1966 Test Method for Fire-Resistive Joint SystemsE2074 Test Method for Fire T
11、ests of Door Assemblies,Including Positive Pressure Testing of Side-Hinged andPivoted Swinging Door Assemblies32.2 UL Standard:UL 385 Standard for Safety Play Pipes for Water SupplyTesting in Fire-Protection Service43. Terminology3.1 DefinitionsFor definitions of terms used in this prac-tice, refer
12、to Terminologies E176 and E631.3.2 Definitions of Terms Specific to This Standard:3.2.1 building element, na component or assembly ofmaterials using products manufactured as independent units1This practice is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibil
13、ity of Subcommittee E05.11 on FireResistance.Current edition approved April 15, 2010. Published May 2010. Originallyapproved in 2002. Last previous edition approved in 2008 as E222608. DOI:10.1520/E2226-10.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer
14、Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Withdrawn. The last approved version of this historical standard is referencedon www.astm.org.4Available from Underwriters Laboratories (UL), Corporate Pr
15、ogress, 333Pfingsten Rd., Northbrook, IL 60062.1*A Summary of Changes section appears at the end of this standard.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.capable of being joined with or placed within other compo-nents or assem
16、blies to create a structure.3.2.2 exposed area, nthe total surface area of the testassembly that is subjected to the fire-resistance test including,when required, the supporting construction.3.2.3 fully developed stream, na coherent, forceful pro-jection of water similar in shape and intensity to th
17、e streambeing applied to the exposed side of the test assembly from thenozzle.3.2.4 supporting construction, nconstruction required forthe testing of some building elements into which the testspecimen is assembled, for example, the wall into which a dooris fitted.3.2.5 test assembly, nthe building e
18、lement or elementsbeing tested and, if applicable, the supporting construction.4. Significance and Use4.1 This practice is intended to standardize the apparatusused and the method or pattern of application of a standardhose stream to building elements as one part of the assessmentand fire resistance
19、 rating of building elements.4.1.1 This practice specifies the water pressure and durationof exposure or application of the hose stream to the testassembly.4.2 This practice is intended to be used only after a testassembly has completed a prescribed standard fire-resistancetest.4.3 The practice expo
20、ses a test assembly to a standard hosestream under controlled laboratory conditions.4.3.1 Pass/fail criteria are defined in the appropriate fire testmethod.4.3.2 This exposure is not intended to replicate typical firefighting operations or all applied or impact loads a systemcould be subjected to in
21、 field use and conditions.4.4 Any variation from tested conditions has the potential ofsubstantially changing the performance characteristics deter-mined by this practice.5. Apparatus5.1 The apparatus used to apply the hose stream is shown inFig. 1 and shall be capable of delivering a solid stream o
22、f waterat the pressure specified in the fire-resistance test method.5.1.1 The water stream shall be delivered through a 2-12 in.(64 mm) hose discharging through a National Standard Play-pipe of corresponding size equipped with a 1-18 in. (29 mm)discharge tip of standard taper, smooth-bore pattern wi
23、thout ashoulder at the orifice. Refer to UL 385.5.1.2 The water pressure at the base of the nozzle shall bemeasured by providing a 12 in. (305 mm) length of a straightrun 2-12 in. (64 mm) pipe between the hose and the playpipe.Eight inches downstream from one end, the pipe shall have an18 in. (3.2 m
24、m) diameter pressure tap drilled through the pipesidewall with a pipe coupling welded or brazed concentricallyover the hole. The pressure tap shall be flush with andFIG. 1 Hose Stream ApparatusE2226 102perpendicular (6 5) to the inner wall of the pipe. Burrs orother irregularities shall be removed o
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME22262010STANDARDPRACTICEFORAPPLICATIONOFHOSESTREAM 软管 使用 标准 实施 规程 PDF

链接地址:http://www.mydoc123.com/p-530610.html