ASTM E119-2008a 837 Standard Test Methods for Fire Tests of Building Construction and Materials.pdf
《ASTM E119-2008a 837 Standard Test Methods for Fire Tests of Building Construction and Materials.pdf》由会员分享,可在线阅读,更多相关《ASTM E119-2008a 837 Standard Test Methods for Fire Tests of Building Construction and Materials.pdf(31页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 119 08aAn American National StandardStandard Test Methods forFire Tests of Building Construction and Materials1This standard is issued under the fixed designation E 119; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision
2、, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.INTRODUCTIONThe performance of wal
3、ls, columns, floors, and other building members under fire exposureconditions is an item of major importance in securing constructions that are safe, and that are not amenace to neighboring structures nor to the public. Recognition of this is registered in the codes ofmany authorities, municipal and
4、 other. It is important to secure balance of the many units in a singlebuilding, and of buildings of like character and use in a community; and also to promote uniformityin requirements of various authorities throughout the country. To do this it is necessary that thefire-resistive properties of mat
5、erials and assemblies be measured and specified according to a commonstandard expressed in terms that are applicable alike to a wide variety of materials, situations, andconditions of exposure.Such a standard is found in the methods that follow. They prescribe a standard exposing fire ofcontrolled e
6、xtent and severity. Performance is defined as the period of resistance to standard exposureelapsing before the first critical point in behavior is observed. Results are reported in units in whichfield exposures can be judged and expressed.The methods may be cited as the “Standard Fire Tests,” and th
7、e performance or exposure shall beexpressed as “2-h,” “6-h,” “12-h,” etc.When a factor of safety exceeding that inherent in the test conditions is desired, a proportionalincrease should be made in the specified time-classification period.1. Scope1.1 The test methods described in this fire-test-respo
8、nsestandard are applicable to assemblies of masonry units and tocomposite assemblies of structural materials for buildings,including bearing and other walls and partitions, columns,girders, beams, slabs, and composite slab and beam assembliesfor floors and roofs. They are also applicable to other as
9、sem-blies and structural units that constitute permanent integralparts of a finished building.1.2 It is the intent that classifications shall register compara-tive performance to specific fire-test conditions during theperiod of exposure and shall not be construed as havingdetermined suitability for
10、 use under other conditions or afterfire exposure.1.3 This standard is used to measure and describe theresponse of materials, products, or assemblies to heat andflame under controlled conditions, but does not by itselfincorporate all factors required for fire hazard or fire riskassessment of the mat
11、erials, products or assemblies underactual fire conditions1.4 These test methods prescribe a standard fire exposurefor comparing the test results of building construction assem-blies. The results of these tests are one factor in assessingpredicted fire performance of building construction and assem-
12、blies. Application of these test results to predict the perfor-mance of actual building construction requires the evaluationof test conditions.1.5 The values stated in inch-pound units are to be regardedas the standard. The values given in parentheses are mathemati-cal conversions to SI units that a
13、re provided for informationonly and are not considered standard.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is the1These test methods are under the jurisdiction of ASTM Committee E05 on FireStandards and are the direct responsibility o
14、f Subcommittee E05.11 on FireResistance.Current edition approved April 1, 2008. Published April 2008. Originallyapproved in 1917. Last previous edition approved in 2008 as E 119 08.These test methods, of which the present standard represents a revision, wereprepared by Sectional Committee on Fire Te
15、sts of Materials and Construction, underthe joint sponsorship of the National Bureau of Standards, the ANSI Fire ProtectionGroup, and ASTM, functioning under the procedure of the American NationalStandards Institute.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken
16、, PA 19428-2959, United States.responsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.7 The text of this standard references notes and footnoteswhich provide explanatory material. The
17、se notes and footnotes(excluding those in tables and figures) shall not be consideredas requirements of the standard.2. Referenced Documents2.1 ASTM Standards:2C 569 Method of Test for Indentation Hardness of Pre-formed Thermal Insulations3D 6513 Practice for Calculating the Superimposed Load onWood
18、-frame Walls for Standard Fire-Resistance TestsE 176 Terminology of Fire StandardsE 814 Test Method for Fire Tests of Through-PenetrationFire StopsE 2226 Practice for Application of Hose Stream3. Terminology3.1 DefinitionsFor definitions of terms found in this testmethod, refer to Terminology E 176.
19、4. Significance and Use4.1 This test method is intended to evaluate the duration forwhich the types of building elements noted in 1.1 contain a fire,retain their structural integrity, or exhibit both propertiesduring a predetermined test exposure.4.2 The test exposes a specimen to a standard fire co
20、ntrolledto achieve specified temperatures throughout a specified timeperiod. When required, the fire exposure is followed by theapplication of a specified standard fire hose stream applied inaccordance with Practice E 2226. The test provides a relativemeasure of the fire-test-response of comparable
21、building ele-ments under these fire exposure conditions. The exposure is notrepresentative of all fire conditions because conditions varywith changes in the amount, nature and distribution of fireloading, ventilation, compartment size and configuration, andheat sink characteristics of the compartmen
22、t. Variation fromthe test conditions or specimen construction, such as size,materials, method of assembly, also affects the fire-test-response. For these reasons, evaluation of the variation isrequired for application to construction in the field.4.3 The test standard provides for the following:4.3.
23、1 For walls, partitions, and floor or roof test specimens:4.3.1.1 Measurement of the transmission of heat.4.3.1.2 Measurement of the transmission of hot gasesthrough the test specimen.4.3.1.3 For load bearing elements, measurement of the loadcarrying ability of the test specimen during the test expo
24、sure.4.3.2 For individual load bearing members such as beamsand columns:4.3.2.1 Measurement of the load carrying ability under thetest exposure with consideration for the end support conditions(that is, restrained or not restrained).4.4 The test standard does not provide the following:4.4.1 Informat
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME1192008A837STANDARDTESTMETHODSFORFIRETESTSOFBUILDINGCONSTRUCTIONANDMATERIALSPDF

链接地址:http://www.mydoc123.com/p-526879.html