《ASTM D7619-2012a 2500 Standard Test Method for Sizing and Counting Particles in Light and Middle Distillate Fuels by Automatic Particle Counter《通过自动颗粒计数器在轻质和中间馏出燃料颗粒的粒度测量和计数方法的标准试验.pdf》由会员分享,可在线阅读,更多相关《ASTM D7619-2012a 2500 Standard Test Method for Sizing and Counting Particles in Light and Middle Distillate Fuels by Automatic Particle Counter《通过自动颗粒计数器在轻质和中间馏出燃料颗粒的粒度测量和计数方法的标准试验.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D7619 12aStandard Test Method forSizing and Counting Particles in Light and Middle DistillateFuels, by Automatic Particle Counter1, 2This standard is issued under the fixed designation D7619; the number immediately following the designation indicates the year oforiginal adoption or, in
2、the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This test method uses a specific automatic particlecounter2(APC) to count and measu
3、re the size of dispersed dirtparticles, water droplets and other particles, in light and middledistillate fuel, and bio fuels such as biodiesel and biodieselblends, in the overall range from 4 m(c) to 100 m(c) and inthe size bands 4 m(c), 6 m(c), and 14 m(c).NOTE 1ASTM specification fuels falling wi
4、thin the scope of this testmethod include Specifications: D975 grades 1D and 2D, D1655, D3699,D4814 (see 14.1.1.1), D6751, D6985, D7467 and distillate grades of D396and D2880.NOTE 2For the purposes of this test method, water droplets arecounted as particles, and agglomerated particles are detected a
5、nd countedas a single larger particle. Dirt includes biological particles. Although theprojected area of a particle is measured, this is expressed as the diameterof a sphere for the purposes of this test method.NOTE 3The notation (c), used with particle sizes, is used to denotethat the apparatus has
6、 been calibrated in accordance with ISO 11171.Strictly this only applies to particles up to 50 m.NOTE 4This test method may be used for particle sizes bands up to100 m(c), however the precision has only been determined for the sizebands 4 m(c), 6 m(c), and 14 m(c). All measurements are per mL.1.2 Th
7、e values stated in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-pria
8、te safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:3D396 Specification for Fuel OilsD975 Specification for Diesel Fuel OilsD1655 Specification for Aviation Turbine FuelsD2880 Specification for Gas Turbine F
9、uel OilsD3699 Specification for KerosineD4057 Practice for Manual Sampling of Petroleum andPetroleum ProductsD4177 Practice for Automatic Sampling of Petroleum andPetroleum ProductsD4814 Specification for Automotive Spark-Ignition EngineFuelD5854 Practice for Mixing and Handling of Liquid Samplesof
10、Petroleum and Petroleum ProductsD6300 Practice for Determination of Precision and BiasData for Use in Test Methods for Petroleum Products andLubricantsD6751 Specification for Biodiesel Fuel Blend Stock (B100)for Middle Distillate FuelsD6985 Specification for Middle Distillate Fuel OilMilitary Marine
11、 Applications4D7467 Specification for Diesel Fuel Oil, Biodiesel Blend(B6 to B20)2.2 ASTM Adjuncts:5ADJ6300 D2PP Determination of Precision and Bias datafor Use in Test Methods for Petroleum Products2.3 ISO Standards:6ISO 11171 Hydraulic Fluid PowerCalibration of Auto-matic Particle Counters for Liq
12、uidsISO 4406 Hydraulic Fluid PowerFluidsMethod forCoding Level of Contamination by Solid Particles1This test method is under the jurisdiction of ASTM Committee D02 onPetroleum Products and Lubricants and is the direct responsibility of SubcommitteeD02.14 on Stability and Cleanliness of Liquid Fuels.
13、Current edition approved June 1, 2012. Published October 2012. Originallyapproved in 2010. Last previous edition approved in 2012 as D761912. DOI:10.1520/D7619-12A.2The sole source of the apparatus known to the committee at this time isSETA-AvCount, available from Stanhope-Seta, London Street, Chert
14、sey, SurreyKT16 8AP UK. If you are aware of alternative suppliers, please provide thisinformation to ASTM International Headquarters. Your comments will receivecareful consideration of a meeting of the responsible technical committee,1whichyou may attend.3For referenced ASTM standards, visit the AST
15、M website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.4Withdrawn. The last approved version of this historical standard is referencedon www.astm.org.5Out of pri
16、nt.6Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.1*A Summary of Changes section appears at the end of this standard.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, Uni
17、ted States.ISO 12103-A1 Specification for Ultra Fine Test Dust(UFTD)ISO 12103-A3 Specification for Medium Test Dust (MTD)3. Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 particles, nsolid particles and dispersed water drop-lets which are detected and counted by this test method
18、.3.1.2 particle count, nthe sum of the number of solidparticles and dispersed water droplets.3.1.3 particle size, m(c), nthe projected area equivalentdiameter of spherical particles passing through the detectingcell in accordance with ISO 11171.3.1.4 particle size cumulative count, nthe total number
19、 ofparticles per mL, in size bands, 4 m(c), 6 m(c), and 14m(c),3.1.4.1 DiscussionAutomatic particle counters may alsocount the total number of particles per mL, in size bands, inaddition to those in 3.1.4,upto100 m.3.1.5 ISO Codes, na standard method for coding the levelof contamination by particles
20、.3.1.5.1 DiscussionResults are expressed by ISO Codes asspecified by ISO 4406. These codes are written in the form ofx/y/z, where x, y and z are ISO Codes equivalent to thecumulative counts, per mL, for particle size bands 4 m(c),6 m(c), and 14 m(c) respectively. An example of this isgiven in Append
21、ix X1.NOTE 5All particle counts are per mL.3.1.6 coincidence error limit, nthe highest concentrationof ISO ultrafine test dust (ISO 12103-A1 or ISO UFTD) thatcan be counted with an automatic particle counter with lessthan 5 % error resulting from the presence of more than oneparticle in the sensor/l
22、aser optical path at a time.3.1.7 test specimen, nan aliquot of the test sample. (SeeSection 10.)4. Summary of Test Method24.1 The optical measurement cell comprises a light sourceand an optical sensor. The principle of operation is themeasurement of laser light obscuration. Particles/droplets en-tr
23、ained within the test specimen cast shadows on the opticalsensor causing a reduction of the output voltage of the sensor.The voltage drop is a function of the particle/droplet size. Eachdetected particle is counted, sized and recorded. Upon comple-tion of the test the software calculates and display
24、s the numberof obscuration events for each of the predetermined size bands.4.2 The test specimen is mixed in its container to suspendthe particles. Upon initiation of a test, the automatic particlecounter (APC) draws the test specimen directly from a testspecimen container (see Fig. A1.1). The test
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD76192012A2500STANDARDTESTMETHODFORSIZINGANDCOUNTINGPARTICLESINLIGHTANDMIDDLEDISTILLATEFUELSBYAUTOMATICPARTICLECOUNTER

链接地址:http://www.mydoc123.com/p-525966.html