ASTM C1710-2015 Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form《管和板形中柔性封闭单元预制绝缘部件安装的标准指南》.pdf
《ASTM C1710-2015 Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form《管和板形中柔性封闭单元预制绝缘部件安装的标准指南》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1710-2015 Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form《管和板形中柔性封闭单元预制绝缘部件安装的标准指南》.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1710 11C1710 15Standard Guide forInstallation of Flexible Closed Cell Preformed Insulation inTube and Sheet Form1This standard is issued under the fixed designation C1710; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revisio
2、n, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This guide covers recommended installation techniques for flexible closed cell pre-formed insulation in
3、 tube or sheet form.This guide is applicable to materials manufactured in accordance with Specification C534 (Elastomeric based insulation) orSpecification C1427 (polyolefin based insulation). The materials covered in this guide encompass a service temperature of -297Fto 300F ( -183C to 150 C) as in
4、dicated in the material specifications referenced above. Many of the recommendations madeare specific to below ambient applications only.1.2 The purpose of this guide is to optimize the thermal performance and longevity of installed closed cell flexible insulationsystems. By following this guide, th
5、e owner, and designer can expect to achieve the energy savings expected and prevention ofcondensation under the specified design conditions. This document is limited to installation procedures and does not encompasssystem design.1.3 The values stated in inch-pound units are to be regarded as standar
6、d. The values given in parentheses are mathematicalconversions to SI units that are provided for information only and are not considered standard.1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this sta
7、ndard to establish appropriate safety and health practices and determine the applicability of regulatorylimitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationC534 Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation
8、 in Sheet and Tubular FormC585 Practice for Inner and Outer Diameters of Thermal Insulation for Nominal Sizes of Pipe and TubingC1427 Specification for Extruded Preformed Flexible Cellular Polyolefin Thermal Insulation in Sheet and Tubular Form2.2 Other Standards:National Commerical, Industrial Insu
9、lation Standards (MICA Manual)3ASHRAE Handbook (Fundamentals Chapter 26)4ASHRAE Handbook (Refrigeration Chapter 33)43. Terminology3.1 DefinitionsC168 shall be considered as applying to the terms in this specification.3.2 Definitions of Terms Specific to This Standard:3.2.1 seamsLongitudinal or horiz
10、ontal cross-sections where insulation meets and must be adhered to itself or other systemcomponents.3.2.2 butt jointsCross-sections where two pieces of tubular or sheet insulation must be adhered to itself or other systemcomponents.1 This guide is under the jurisdiction of ASTM Committee C16 on Ther
11、mal Insulation and is the direct responsibility of Subcommittee C16.40 on Insulation Systems.Current edition approved Sept. 1, 2011Sept. 15, 2015. Published October 2011December 2015. Originally approved in 2009. Last previous edition approved in 20092011as C171009. DOI:10.1520/C171011.11. DOI:10.15
12、20/C171015.2 For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summary page on the ASTM website.3 Available from MICA (Midwest Insulation Contract
13、ors Association) 16712 Elm Circle, Omaha, NE 68130. http:/www.micainsulation.org.4 Available from American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA 30329,http:/www.ashrae.org.This document is not an ASTM standard and is int
14、ended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the curr
15、ent versionof the standard as published by ASTM is to be considered the official document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States13.2.3 vapor (water) stopsLocations / methods to prevent water or water vapor from traveling into
16、 or down a tubular pipesection.from one pipe insulation section to an adjacent insulation and prevent water traveling down the annular space between thepipe insulation and the tubular pipe.3.2.4 sleeving/multi layeringApplying another layer of insulation over the first layer. This process is used wh
17、en the insulationthickness required is greater than that which is commercially available. This technique is also employed when proper installationpractice requires multiple layers and or staggered joint application, even if a single layer thickness is available.4. Summary of Guide4.1 Proper insulati
18、on thickness shall be installed as specified and not compromised. The integrity of the insulation system shallbe maintained throughout the application. Never pull or stretch insulation, always push or over-size insulation.4.2 All seams, butt joints, cutouts and termination points shall be sealed wit
19、h a manufacturers approved adhesive to preventair/moisture intrusion. For below ambient applications, install vapor stops at all insulation terminations or interruptions, such asat supports, valves and flanges by This can be accomplished by several methods; by adhering the insulation directly to the
20、 pipeusing a 2 in. (50 mm) strip of contact adhesive or sealant to maintain closure. Insulationclosure, insulation tape can also be usedfor this purpose by wrapping it around the pipe. A vapor barrier mastic or tape can also be used for this purpose. On straight runs,install vapor stops every 18 ft
21、(5.4 m) to minimize moisture problems if they occur.4.3 Specific product Manufacturers recommended installation practices shall be used in all cases.4.4 Product should be applied to clean, dry surfaces. If the system is operating, additional steps may be needed to insure aproper installation.4.5 Aco
22、ating, jacket, cladding or appropriate protection shall be used where mechanical abuse or damage is expected. Outdoorapplications may require special consideration refer to the manufacturers recommendations.4.6 For satisfactory performance, properly installed protective vapor retarders/barriers and
23、vapor stops must be used on highrelative humidity and below ambient temperature applications to reduce movement of moisture through or around the insulationto the colder interior surface.5. Significance and Use5.1 This guide applies to flexible closed cell insulation tubing and sheet materials manuf
24、actured according to Specification C534and Specification C1427. This standard is intended to provide a basic guide for installing these types of materials.5.2 Confirm application use temperature is consistent with specified use temperature for material as defined in ASTMSpecifications unless otherwi
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC17102015STANDARDGUIDEFORINSTALLATIONOFFLEXIBLECLOSEDCELLPREFORMEDINSULATIONINTUBEANDSHEETFORM 板形中

链接地址:http://www.mydoc123.com/p-465612.html