ASTM C1081-1998(2014) Standard Specification for Asbestos-Cement Corrugated Fill For Use in Cooling Towers《冷却塔用石棉水泥波纹状填料的标准规格》.pdf
《ASTM C1081-1998(2014) Standard Specification for Asbestos-Cement Corrugated Fill For Use in Cooling Towers《冷却塔用石棉水泥波纹状填料的标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1081-1998(2014) Standard Specification for Asbestos-Cement Corrugated Fill For Use in Cooling Towers《冷却塔用石棉水泥波纹状填料的标准规格》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1081 98 (Reapproved 2014)Standard Specification forAsbestos-Cement Corrugated Fill For Use in CoolingTowers1This standard is issued under the fixed designation C1081; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, th
2、e year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers splash bar and corrugatedsheet type asbestos-cement products used as cooling tower
3、 fill.1.2 Drift eliminators or demisters, louvers, partitioning andcasing panels are covered in Specifications C1080. Asbestos-cement pipes are covered in Specification C296 and Specifi-cations C428. Asbestos-cement flat sheet fill (heat exchangesurfaces) are specified in Specification C1082.1.3 The
4、 values stated in the SI system are to be regarded asthe standard. The inch-pound units in parentheses are forinformation only.1.4 WarningBreathing of asbestos dust is hazardous.Asbestos and asbestos products present demonstrated healthrisks for users and for those with whom they come into contact.I
5、n addition to other precautions, when working with asbestos-cement products, minimize the dust that results. For informa-tion on the safe use of chrysoltile asbestos, refer to “Safe Useof Chrysotile Asbestos: A Manual on Preventive and ControlMeasures.”21.5 The following precautionary caveat pertain
6、s only to theTest Method portion, Section 8, of this Specification: Thisstandard does not purport to address all of the safety concerns,if any, associated with its use. It is the responsibility of the userof this standard to establish appropriate safety and healthpractices and determine the applicab
7、ility of regulatory limita-tions prior to use. See 1.4 for a specific safety hazard.2. Referenced Documents2.1 ASTM Standards:3C150 Specification for Portland CementC296 Specification for Asbestos-Cement Pressure PipeC428 Specification forAsbestos-Cement Nonpressure SewerPipeC458 Test Method for Org
8、anic Fiber Content of Asbestos-Cement ProductsC459 Test Methods for Asbestos-Cement Flat ProductsC500 Test Methods for Asbestos-Cement PipeC1080 Specification for Asbestos-Cement Products OtherThan Fill For Cooling TowersC1082 Specification for Asbestos-Cement Flat Sheet forCooling Tower FillC1096 T
9、est Method for Determination of Wood Fiber inAsbestos CementD2946 Terminology for Asbestos and AsbestosCementProducts2.2 DIN Standard:DIN 274 Asbestzement-Weilplatten43. Terminology3.1 DefinitionsThe definitions included in TerminologyD2946 are applicable to this specification.3.2 Definitions of Ter
10、ms Specific to This Standard:3.2.1 autoclaved productProducts that have been treatedin a saturated steam atmosphere at between 689 and 1517 kPa(100 and 220 psi) for at least 8 h, and that contain portlandcement Type I (Specification C150) together with fine silica inthe ratio of 3:2 that can react t
11、o form calcium silicate reactionproducts.3.2.2 pressed productsProducts that are pressed singly orin stacks interlayered with templates, at a minimum pressure of12 MPa (1740 psi).3.2.3 pitchThe wave length in corrugated products.4. Classification4.1 Splash Bar Classification:4.1.1 Type ISplash bars
12、consist of corrugated autoclavedpressed asbestos-cement sheets for the most demanding appli-cations that meet the requirements set forth in Table 1.1This specification is under the jurisdiction of ASTM Committee C17 onFiber-Reinforced Cement Products and is the direct responsibility of SubcommitteeC
13、17.03 on Asbestos - Cement Sheet Products and Accessories.Current edition approved Dec. 1, 2014. Published December 2014. Originallyapproved in 1987. Last previous edition approved in 2008 as C1081 98 (2008).DOI: 10.1520/C1081-98R14.2Available from The Asbestos Institute, http:/ referenced ASTM stan
14、dards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.4Available from Deutsches Institut fr Normunge, Beuth Verlaq GmbH,Auslieferung, Post F
15、ach1107, D-1000 Berlin 30, Germany.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States14.1.2 Type IISplash bars consist of corrugated pressedasbestos-cement sheets for intermediate service that meetrequirements presented in Table 1.4.1.3
16、Type IIISplash bars are intended for less demandingservice that meet the requirements stated in Table 1.4.2 Corrugated Fill:4.2.1 Type ANon-autoclaved, compressed, corrugatedsheet, with a nominal thickness of 5 mm (316 in.):Pitch 107 mm (4.2 in.)Average minimum bending moment 556 Nm/m(125 ftlbf/ft)I
17、ndividual specimen minimum bending moment 471 Nm/m(106 ftlbf/ft)Minimum density 1.6 g/cm3(100 lb/ft3)Maximum water absorption 25 %NOTE 1Calculate bending moment in accordance with DIN 274.5. Ordering Information5.1 Splash Bars:5.1.1 State the type, dimensions, and quantity required.5.1.2 State what
18、type of certification, if any, is required.5.2 Corrugated Fill:5.2.1 State that Type A is required.5.2.2 State length, width, and quantity of panels required.5.2.3 State what type of certification, if any, is required.6. Materials and Manufacture6.1 Splash BarsManufacturing and composition require-m
19、ents are given in Table 1.6.2 Corrugated FillManufacturing requirements are givenin 4.2.1.7. Performance Requirements7.1 Splash BarsPerformance requirements are stated inTable 1.7.2 Corrugated FillPerformance requirements are statedin 4.2.1.8. Test Methods8.1 Apparent Density:8.1.1 ScopeThis test me
20、thod covers the determination ofthe mass per unit volume of asbestos-cement products.8.1.2 Significance and Use:8.1.2.1 The apparent density gives an indication of relativeproduct robustness and durability. It is used to evaluate therequirements for dedicated support structures.8.1.3 Hazards:Warning
21、see 1.4.8.1.4 ProcedureCalculate the apparent density by divid-ing the mass of a specimen dried to constant mass at 110 6 5Cby the volume of the specimen.8.1.5 Precision and Bias:8.1.5.1 PrecisionNo statement is made on the precision ofthis test method since conformance to specific criteria is theon
22、ly measure of success specified.8.1.5.2 BiasBias cannot be established on these porousheterogeneous products of variable composition, for lack of areferee test method.8.2 Water AbsorptionIn accordance with Test MethodsC459.8.3 Flexural Strength and Modulus of RuptureIn ac-cordance with Test Methods
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC108119982014STANDARDSPECIFICATIONFORASBESTOSCEMENTCORRUGATEDFILLFORUSEINCOOLINGTOWERS 冷却塔 石棉 水泥

链接地址:http://www.mydoc123.com/p-463290.html