ASHRAE OR-05-14-1-2005 An Experimental Study of the Effects of Inlet Plenum Walls on Axial Fan Performance《轴流风机性能对进气室墙壁的影响的实验研究RP-1010》.pdf
《ASHRAE OR-05-14-1-2005 An Experimental Study of the Effects of Inlet Plenum Walls on Axial Fan Performance《轴流风机性能对进气室墙壁的影响的实验研究RP-1010》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-05-14-1-2005 An Experimental Study of the Effects of Inlet Plenum Walls on Axial Fan Performance《轴流风机性能对进气室墙壁的影响的实验研究RP-1010》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、OR-05-14-1 (RP-1 O1 O) Test Fan ID # 36x 14 An Experimental Study of the Effects of Inlet Plenum Walls on Axial Fan Performance Blade Rotational Blade Data No of Hub Diameter Frequency Number Tip Angle O Vanes in. (mm) DHT Hz 10 1,9, 16,24 8 14.0 (356) 0.39 297 William B. Swim, PhD ABSTRACT This exp
2、erimental study determined the degradation in performance of large axial fans caused by close inlet walls. Three fans with hub to tip ratios of 0.39, 0.49, and O. 74 were each tested at four blade angles and over the jlow rate range of wide open to near shutof The closest walls, 0.5D front clearance
3、 and OD side clearance, caused only modest loss in flow rate, up to 3%, and less than a 5% loss of eficiency in the 0.49 H/Tfan. The other two fans had only minor decreases injlow rate and in eficiency for the closest walls. No signij- cant losses were foundfor any of the test fans when tested with
4、clearances larger than the minimum. INTRODUCTION ASHRAE has a strong and continuing interest in helping develop an understanding of the potential degradation of the noise and performance of fans when installed in realistic, non- ideal, air-handling systems. This degradation of performance, termed sy
5、stem efect, has been used by the technical commu- niy in system design with only limited success. And the noise penalty of non-ideal installations has been mostly guided by personal experience of the designer. This study was initiated by ASHRAE as Research Project 1010, ?Inlet Installation Effects,
6、Air and Sound, on Vaneaxial Fans,? to contribute to the understanding of inlet system effects on axial fans. Noise and performance measurements were made on three 36 in. (914 mm) diameter, variable pitch axial fans with nominal hub diameters of 14, 17, and 26 in. (360,430, and 660 mm). Each of the t
7、hree fans was tested at four blade angles, providing ?12? test fans. These test fans are described in Table 1. Table 1. Test Fans Used on RP I010 Project Type: Joy Series 1000 Axivane Fans Model Numbers: 36-1 4-1 780,36- 17- 1780,36-26- 1780 Fan Nominal Diameter, D: 36 in. (914 mm) Manufacturer: New
8、 Philadelphia Fan Company Fan Motors:1780 RPM (29.7 Hz) Impeller Tip Diameter, DT: 35.9 in. (912 mm) 36x 17 1 12 3,10, 18,25 I 9 1 17.5 (444) I 0.49 1 356 36x26 I 16 15,22,30,37 I 13 I 26.5 (673) I 0.74 I 475 William B. Swim is professor emeritus of Mechanical Engineering at Tennessee Technological
9、University, Cookeville, Tenn. 02005 ASHRAE. 993 Test Wall Positions Test Wall ID Numbers r Movable Tes! Wall Nozzle Chamber Figure 1 Test fan nomenclature and test setup geometry Figure 2 Isometric view of 61,700 ft (1 740 my reverberation room setup for ASHRAE RP-IO10 fan tests. The 12 fans were te
10、sted using 10 test-wall positions designed to simulate the effect of installing fans in close prox- imity to the walls of an inlet plenum. Figure 1 describes the L- shaped test wall as well as the locations and the identification numbers of the 10 test-wall positions. The 120 tests of this project c
11、overed the fan flow rate range from free delivery to near shutoff with data collected at 9 to 11 test points or deter- minations for each test. The test fan sizes, as shown in Table 1, are identified as 36 x 14, 36 x 17, and 36 x 26. The wall positions are identified as WP1 through WP10, as shown in
12、 Figure 1. TEST METHODS The noise measurements were made in a large reverber- ation room with the free inlet of the fan fitted with an inlet bell and inlet screen. The exhaust of the test fan was ducted to an adjacent nozzle chamber where flow rate and static pressure rise were measured. An auxiliar
13、y fan on the exhaust of the nozzle chamber was used to control the back-pressure on the test fan. The test components, test fan, test wall, and micro- phone traversing unit, are illustrated in the isometric drawing of Figure 2. The performance measurements were made 994 ASHRAE Transactions: Symposia
14、 following Figure 12 of AMCA Standard 210-99 (ASHRAE Standard 51-1999). The noise measurements were made in accordance with AMCA Standard 300-96. The L-shaped test wall was used to simulate plenum walls close to the front and the side of the fan inlet. The test wall, constructed of 2 x 4 stud framin
15、g covered with heavy, 6 mil (O. 15 mm) Visquene sheeting, measured 123 in. (3 124 mm or 3.4D) along the fan axis, 159 in. (4039 mm or 4.4D) across the front of the fan, and 144 in. (3658 mm or 4D) in height. The photograph in Figure 3 shows the 36 x 26 fan mounted for testing while Figure 4 shows th
16、e test wall installed at the fan inlet. The fan and three test wall positions are shown, as located in the reverberation room, in Figure 5. The test wall was moved in increments from a “free” inlet condition, at 5D in front and 5D to the side of the fan inlet (WPl), to the worst case, where the wall
17、 was closest to the fan inlet, %D in front and OD to the side (WP2). The performance and noise were measured for each test-wall position, first at free inlet condition, identified as wall position 1 (WPl), then at position 2 (WP2), the worst case. The eight other wall posi- tions, WP3 through WP10,
18、followed in order. The test-wall positions, listed in Figure 1 , provided three sets of three front-clearance positions (not counting WP 1). Following the free inlet test, the side wall was moved to zero clearance and tests were conducted at three front wall clear- ances-OSD, D, and 1 SD. The side w
19、all clearance was then set to 0.5D, and tests run at D, 1.5D, and 2D front clearance. Figure3 Photograph of the 36 x 26 fan mounted for testing. Figure 4 Photograph of a fan and test wall setup for test. 30 ft, O in. (9140mr9) d Air Measuring Chamber (for Exhoust Hode Fons) Not Used For RPlOlO Il 8
20、in. (200nri) Air 14-osuring Charber (Fut Supply Mud? Turi Ceiling H?ight 18 ft. 6 in. (5640mm) 71 ft. O in. (21600mm) w Microphone Swing Path 12 ft. O in. (3660mm) u 10 fi. (3050mm) High Figure 5 Plan view of reverberation room and adjacent nozzle chamber: ASHRAE Transactions: Symposia 995 Figure 6
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR051412005ANEXPERIMENTALSTUDYOFTHEEFFECTSOFINLETPLENUMWALLSONAXIALFANPERFORMANCE 轴流 风机 性能 进气室

链接地址:http://www.mydoc123.com/p-455608.html