ASCE 29-05-2007 Standard Calculation Methods for Structural Fire Protection (ASCE SEI SFPE 29-05)《防火结构标准计算方法ASCE SEI SFPE 29-05》.pdf
《ASCE 29-05-2007 Standard Calculation Methods for Structural Fire Protection (ASCE SEI SFPE 29-05)《防火结构标准计算方法ASCE SEI SFPE 29-05》.pdf》由会员分享,可在线阅读,更多相关《ASCE 29-05-2007 Standard Calculation Methods for Structural Fire Protection (ASCE SEI SFPE 29-05)《防火结构标准计算方法ASCE SEI SFPE 29-05》.pdf(74页珍藏版)》请在麦多课文档分享上搜索。
1、 ASCE STANDARD ASCEISEIISFPE 29-05 American Society of Civil Engineers Standard Calculation Metho,ds for Structural Fire Protection AE-L, - - Structural Eng/neerlng mnstlfufe *.,Allowing formula: where s = spacing of ribs or undulations t = minimum thickness t, = equivalent thickness calculated in a
2、ccordance with item b, above 2.3.4 Multiple-Wythe Walls For walls consisting of two or more wythes of differ- ent types of concrete, the fire resistance rating shall be determined in accordance with the graphical or numeri- cal solution in Sections 2.3.4.1 and 2.3.4.2, respectively. 2.3.4.1 Graphica
3、l Solutiorz For walls consisting of two wythes of different types of concrete, the fire resistance rating shall be determined from Figure 2- 1. The fire resistance rating shall be the lower of the two ratings determined by assuming that each side of the wall is the fire-exposed side. 2.3.4.2 Nuineri
4、cal Solution For walls consisting of two or more wythes of different types of concrete, or one or more wythes of TABLE 2-1. Fire Resistance of Concrete Walls, Floors, and Roofs Minimum Equivalent Thickness for Fire Resistance Rating (hrs) Concrete Aggregate Type in. mm in. rnm in. mm in. mm in. mm S
5、iliceous 3.5 89 4.3 109 5.0 127 6.2 157 7.0 178 Carbonate 3.2 81 4.0 102 4.6 117 5.7 145 6.6 168 Lightweight 2.5 64 3.1 79 3.6 91 4.4 112 5.1 130 STANDARD CALCULATION Ml3HODS FOR STRUCTURAL FIRE PROTECTION Fire-Exposed Wythe Carbonate Fire-Exposed Wythe Siliceous k 5 0 22 3 A or the fire resistance
6、rating of the floor or roof shall be maintained by other approved methods. 2.4.3 Two-Course Floors and Roofs The fire resistance rating of two-course floors and roofs consisting of a base slab of concrete with a topping (overlay) of concrete with a different type of aggregate is indicated in Figure
7、2-4. If the base slab of concrete is covered with a topping (overlay) of terrazzo or gypsum wallboard, the thickness of terrazzo or gypsum wallboard shall be converted to an equivalent thickness of concrete by multiplying the actual thick- ness by the appropriate factor listed in Table 2-4. This equ
8、ivalent concrete thickness shall be added to the base - - slab thickness and the total thickness used to determine the fire resistance of the slab, including topping, from Table 2- 1. 2.4.4 Insulated Roofs The fire resistance rating of roofs consisting of a base slab of concrete with a topping (over
9、lay) of cellu- lar, perlite, or vermiculite concrete or insulating boards and built-up roof shall be determined from Figure 2-5 (a) or (b). Where a three-ply built-up roof is installed over a lightweight insulating concrete topping, Siliceous Sand-Lightweight Top Course Material or Carbonate or Ligh
10、tweight Gypsum wallboard* 3 2.25 Terrazzo 1 0.75 * Applies only to roofs. 10 minutes shall be permitted to be added to the fire resistance rating calculated from Figure 2-5 (a). 2.5 CONCRETE COVER OVER REINFORCEMENT Minimum concrete cover over positive moment reinforcement for floor and roof slabs a
11、nd beams shall be determined by Sections 2.5.1 through 2.5.3. Concrete cover shall not be less than required by ACI 3 18. For purposes of determining minimum concrete cover, slabs and beams shall be classified as restrained or unrestrained in accordance with Appendix A. 2.5.1 Cover for Slab Reinforc
12、ement The minimum thickness of concrete cover to posi- tive moment non-prestressed and prestressed reinforce- ment (bottom steel) for different types of concrete floor and roof slabs for fire resistance ratings of I to 4 hours shall be not less than the thickness indicated in Table 2-5. For floor or
13、 roof slabs consisting of two or more courses of different types of concrete, the cover requirements shall be based on the type of concrete used for the base slab, provided the base slab is not less than 1 in. (25 mm) thick. Table 2-5 shall apply to one-way or two-way cast-in-place or precast solid
14、or hollow-core slabs with flat undersurfaces. 2.5.2 Cover for Non-Prestressed Reinforcement in Beams The minimum thickness of concrete cover to positive moment non-prestressed reinforcement (bot- tom steel) for restrained and unrestrained beams of different widths for fire resistance ratings of 1 to
15、 4 hours for all types of concrete shall not be less than the thickness indicated in Table 2-6. Values in Table 2-6 for restrained beams apply to beams spaced more than 4 ft (1,2 19 mm) on center. For restrained beams and joists spaced 4 ft (1,2 19 mm) or less on center, 314 in. (19 mm) cover is ade
16、quate for fire resistance ratings of 4 hours or less regardless of the width of the beam. Cover for intermediate beam widths shall be determined by direct interpolation. ASCWSEIISFPE 29-05 SAND-LIGHTWEIGHT CONCRETE . . ., . . Carbonate Base Siliceous Base 25 51 76 102 127 mm 25 51 76 102 inches 0 12
17、3 4 THICKNESS OF NORMAL WEIGHT CONCRETE BASE SLAB NORMAL WEIGHT CONCRETE SAND-LIGHTWEIGHT CONCRETE Carbonate Overlay Siliceous Overlay mm mm 25 51 76 102 127 25 51 76 102 127 5 127 5 127 inches inches THICKNESS OF SAND-LIGHTWEIGHT CONCRETE BASE SLAB FIGURE 2-4. Fire Resistance of Two-Course Concrete
18、 Floors and Roofs (Source: Abrams, M. S., and Gustaferro, A. H. (1968). “Fire endurance of two-course floors and roofs.“ Portland Cement Association Research and Development Bulletin RD048. Used with permission.) 2.5.2.1 Calculating Cover cover of the individual bars. For corner bars (i.e., bars The
19、 concrete cover for an individual bar is the equal distance from the bottom and side), the mini- minimum thickness of concrete between the surface of mum cover used in the calculation shall be one-half the bar and the fire-exposed surface of the beam. For the actual value. The actual cover for an in
20、dividual bar beams in which several bars are used, the cover, for the shall not be less than one-half the value shown in Table purposes of Table 2-6, is the average of the minimum 2-6 or 314 in. (19 mm), whichever is greater. STANDARD CALCULATION METHODS FOR STRUCTURAL FlRE PROTECTION Carbonate Base
21、 (25) (5 1) (76) (102) . : : - CELLULAR CONCRETE . : : . .: ,.: .: “ :;., CONCRETE ,: ;. ,: ,j: . . , .:, Siliceous Base (25) (5 1) (76) (102) Sand-Lightweight Base (25) (5 1) (76) (102) THICKNESS OF CONCRETE BASE SLAB IN INCHES (mm) -: . . PERLITE CONCRETE :-. ; . . . : . . CONCRETE : : . .:,. . :j
22、 . . . . e, U Carbonate Base Siliceous Base Sand-Lightweight Base (25) (5 1 ) (76) ( 102) 02) 3 a 2 0 “ (51) 2 (51) 2 (5 1) rn2 8iZ 1 I= P) 24 (25) 1 (25) 1 (25) .i! 0 22 b 0 1234 0 1234 0 1234 THICKNESS OF CONCRETE BASE SLAB IN INCHES (mm) : VERMICULITE CONCRETE .: . . . . .: . . .;. : : ; ; . : .
23、. Carbonate Base Siliceous Base Sand-Lightweight Base (25) (51) (76) (102) (102) (25) (51) (76) (102) (102) (25) (51) (76) (102) (102) (51) 2 (5 1) (25) 1 (25) 1 (25) 0 1234 0 1234 0 1234 THICKNESS OF CONCRETE BASE SLAB IN INCHES (mm) FIGURE 2-5. (a) Fire Resistance of Concrete Roofs with Overlays o
24、f Insulating Concrete (Source: Abrams, M. S., and Gustaferro, A. H. (1970). “Fire resistance of lightweight insulating concretes.“ Portland Cement Association Research and Development Bulletin RD004. Used with permission.) 2.5.3 Cover for Prestressed Reinforcement types of concrete for fire resistan
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASCE29052007STANDARDCALCULATIONMETHODSFORSTRUCTURALFIREPROTECTIONASCESEISFPE2905 防火 结构 标准 计算方法 ASCESEISFPE2905PDF

链接地址:http://www.mydoc123.com/p-453896.html