1、 AHRI Standard 840 (formerly ARI Standard 840) 1998 Standard for Unit Ventilators AHRI Standard 840 (formerly ARI Standard 840) Price $10.00 (M) $20.00 (NM) Copyright 1998, by Air-Conditioning, Heating and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office
2、 IMPORTANT SAFETY RECOMMENDATIONS It is strongly recommended that the product be designed, constructed, assembled and installed in accordance with nationally recognized safety requirements appropriate for products covered by this standard. AHRI, as a manufacturers trade association, uses its best ef
3、forts to develop standards employing state-of-the-art and accepted industry practices. However, AHRI does not certify or guarantee safety of any products, components or systems designed, tested, rated, installed or operated in accordance with these standards or that any tests conducted under its sta
4、ndards will be non-hazardous or free from risk. Note: This is a new standard. 2 TABLE OF CONTENTS SECTION PAGE Section 1. Purpose 1 Section 2. Scope .1 Section 3. Definitions .1 Section 4. Classifications 3 Section 5. Testing and Rating Requirements 3 Section 6. Minimum Data Requirements for Publish
5、ed Ratings 6 Section 7. Operating Requirements 6 Section 8. Marking and Nameplate Data 6 Section 9. Voluntary Conformance 6 TABLES Table 1. Arrangement of Unit Ventilators .2 Table 2. Air Flow Testing Conditions .4 FIGURES Figure 1. Standard Ventilation Rate Test Set-Up .5 APPENDICES Appendix A. Ref
6、erences Normative 7 Appendix B. References Informative .7 AHRI STANDARD 840-98 1 UNIT VENTILATORS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish, for unit ventilators: definitions; classifications; testing and rating requirements; minimum data requirements for published
7、 ratings; performance requirements; operating requirements; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors, and users. 1.1.2 Review and Amendment. This stand
8、ard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to all factory-made equipment as defined in the following standards which also meet the requirements of 3.4 and are labeled as a unit ventilator. a. Room fan-coil air-conditioners, AHRI S
9、tandard 440 (formerly ARI Standard 440). b. Packaged terminal air-conditioners, AHRI Standard 310/380 (formerly ARI Standard 310/380). c. Unitary air-conditioners and heat pump units, AHRI Standard 210/240 (formerly ARI Standard 210/240). d. Water-source heat pumps, AHRI Standard 320 (formerly ARI S
10、tandard 320). e. Ground water-source heat pumps, AHRI Standard 325 (formerly ARI Standard 325). f. Ground source closed-loop heat pumps, AHRI Standard 330 (formerly ARI Standard 330). 2.2 Exclusions. This standard does not apply to equipment as defined in the following standards: a. Room air-conditi
11、oners, AHAM Standard RAC-1 or ANSI Standard Z234.1. b. Central-station air-handling units, AHRI Standard 430 (formerly ARI Standard 430). Section 3. Definitions 3.1 Definitions. All terms in this document will follow the standard industry definitions established in the current edition of ASHRAE Term
12、inology of Heating, Ventilation, Air Conditioning and Refrigeration, unless otherwise defined in this section. 3.2 Published Rating. A statement of the assigned values of those performance characteristics, under stated rating conditions, by which a unit may be chosen to fit its application. These va
13、lues apply to all units of like nominal size and type (identification) produced by the same manufacturer. As used herein, the term “published rating“ includes the rating of all performance characteristics shown on the unit or published in specifications, advertising or other literature controlled by
14、 the manufacturer, at stated rating conditions. 3.2.1 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.2.2 Application Rating. A rating based on tests performed at application rating conditions (other than Standard Rating Conditions). 3.3 “Shall,“ “Should,“ “ Recom
15、mended“ or “It Is Recommended.“ “Shall,“ “should,“ “recommended“ or “it is recommended“ shall be interpreted as follows: 3.3.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. AHRI STANDARD 840-98 2 I.D. Fa
16、n I.D. Coils O.D. Fan Comp* O.D. Coil I.D. Fan I.D. Coils O.D. Fan Comp* O.D. Coil I.D. Fan I.D. Coil(s) Comp Water/ Refrigerant Coil I.D. Fan I.D. Coil(s) O.D. Fan Comp O.D. Coil I.D. Fan I.D. Coil(s) 3.3.2 Should, Recommended or It Is Recommended. “Should,“ “recommended“ or “it is recommended“ is
17、used to indicate provisions which are not mandatory but which are desirable as good practice. 3.4 Unit Ventilator. A factory-made assembly, equipped with outside air ventilation and return air dampers capable of introducing ventilation air of at least 80% of rated Standard Air Flow, while also havin
18、g the capability to provide any combination of the following functions: humidity control, heating or cooling, and filtering of air. The source of humidity control, heating or cooling supplementary to that from ventilation air, may be remote or an integral part of the unit itself. This equipment is d
19、esigned for free delivery of air into a room, but may be applied with minimal ductwork having a static resistance not exceeding 0.50 in. H2O 125 Pa. This equipment can be either vertical floor standing or horizontally mounted, in or adjacent to the space it serves. This equipment is provided with ai
20、r capacities of 3000 cfm 1416 m3/s or less. Table 1. Arrangement of Unit Ventilators Description Cooling/Heating AHRI Standard Arrangement Self-Contained Unit Ventilator Vapor Compression/Vapor Compression & (backup heat) (electric) (hydronic) (steam) 310/380 Vapor Compression/electric Vapor Compres
21、sion/hydronic Vapor Compression/steam Vapor Compression/none 310/380 Water-Source Self Contained Unit Ventilator Vapor Compression/Vapor Compression & (backup heat) (electric) 320, 325 and 330 Fan-Coil Unit Ventilator Vapor Compression/electric Vapor Compression/hydronic Vapor Compression/steam Vapo
22、r Compression/none 210/240 Vapor Compression/Vapor Compression & (backup heat) (electric) (hydronic) (steam) 210/240 hydronic/electric hydronic/hydronic hydronic/steam hydronic/none 440 * Compressor may be indoors or outdoors. 3.4.1 Self-Contained Unit Ventilators. Any equipment as defined in AHRI S
23、tandard 310/380 (formerly ARI Standard 310/380) with ventilation capabilities as defined in 3.4. 3.4.2 Water-Source Self-Contained Unit Ventilators. Any equipment as defined in AHRI Standards 320, 325, or 330 (formerly ARI Standards 320, 325, or 330) with ventilation capabilities as defined in 3.4.
24、AHRI STANDARD 840-98 3 3.4.3 Fan-Coil Unit Ventilators. Any equipment as defined in AHRI Standards 440 or 210/240 (formerly ARI Standards 440 or 210/240) with ventilation capabilities as defined in 3.4. Section 4. Classifications 4.1 Methods of Classification. Unit ventilators may be classified acco
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI8401998UNITVENTILATORSPDF