Boiler Safety.ppt
《Boiler Safety.ppt》由会员分享,可在线阅读,更多相关《Boiler Safety.ppt(16页珍藏版)》请在麦多课文档分享上搜索。
1、,Boiler Safety,Safety Appurtenances In Boiler,Pressure gauge & Test connectionSafety Valves (Drum & Super-heater)Blow down valveDrum Level Water Gauge GlassesStop Valve in Steam lineStop & Check Valves in Feed Line,Necessity of Safety valve,It prevents the boiler pressure from going above a safe pre
2、-determined pressure, by opening, to allow the excess steam to escape into the atmosphere when the set point is reached. This guards against a possible explosion from excessive pressure.Each Boiler must have one S.V, the minimum size being a inch valve for miniature boilers & a inch valve for others
3、. A Boiler with more than 500 Sq.ft of heating surface & an electric boiler with a power input of over 500 KW should have two or more Safety valves.,Capacity of Safety valve,In any case , SV capacity must be such as to discharge all the steam the boiler can generate without allowing pressure to rise
4、 more than 6 % above the highest pressure at which any valve is set & in no case more than 6 % above the maximum allowable working pressure.All the Safety valves used on Steam boilers must be of Direct Spring Loaded type.,Definition of Safety Relief valve,It is an automatic pressure-relieving device
5、 actuated by the pressure upstream of the valve & which opens by pop action, with further increase in lift of the valve, when pressure increases over popping pressure.It thus combines the feature of pop action & further lift with pressure increase.,Terminology of Safety Relief valves,Blow down :It i
6、s the difference between the opening & closing pressure of the Safety valve.Ex- A safety valve that pops at 200psi & seatsat 195 psi has a blow down of 5 psi.Code rule for determining SV relieving capacity :SV capacity on a boiler must be such that the SV or valves willdischarge all the steam that c
7、an be generated by the boiler (this is assumed to be the max. firing rate) without allowing the pressure to rise more than 6 % above the highest pressure at which any valve is set & in no case more than 6 % above the max allowable pressure.,ASME markings required on High Pressure Safety Valves:,Name
8、 or identifying trade mark of manufacturerManufacturers design or type numberSize in inches, Seat Diameter in inches( i.e the pipe size of valve inlet )Pressure in lbs/ sq.ft or Kg / sq.cm (Steam pressure at which it is to blow)Blow down in Kgs or lbs ( BD is the difference between the opening & clo
9、sing pressure )Capacity in lbs / hr or kg / hrCapacity lift in inches. It is the distance the valve disc rises under the action of steam when the valve is blowing under a pressure of 3 % above the set pressure.,Number of Safety Valves requirement,Each Boiler requires at least one SV, but if the heat
10、ing surface exceeds 500 Sq.ft, the boiler must have two or more Safety relief valves.When not more than two valves of different sizes are mounted singly on the boiler, the smaller valve must not be les than 50 % in relieving capacity of the larger valve.Every super-heater attached to a boiler with n
11、o intervening valves between the super-heater & boiler requires one or more safety valves on the super-heater outlet header.With no intervening stop valves between the super-heater & boiler, the capacity of the safety valves on the super-heater may be included in the total required for the boiler, p
12、rovided the safety valve capacity in the boiler is at least 75 % of the aggregate SV capacity required for the Boiler. Ex- If a boilers steaming capacity is 100 tons, a minimum of two valves are required on Boiler with a total relieving capacity of 75 % of (100 Tons) I.e 75 tons. The super-heater wo
13、uld then require a SV with a capacity of (100 75) tonsi.e 25 Tons.,Important Points,Heating Surface :That side of the boiler surface exposed to the products of combustion, exclusive of super-heating surface.The areas to be considered for this purpose are tubes, fire-boxes, shells, tube sheets & the
14、projected area of the headers.Sequence of Safety valves Blowing:The super-heater safety valves should always be set at a lower pressure than the drum safety valve ,so as to ensure steam flow through the super-heater at all times. If the drum safety valve blows first, the super-heater could be starve
15、d of cooling steam, leading to possible super-heater tube overheating & rupture.,Important Points,Re-heater Safety valves :The capacity of re-heater safety valves can not be included in the total safety valve capacity required for the boiler & super-heater.The relieving capacity of re-heater safety
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
2000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BOILERSAFETYPPT