1、01-11 22 14 36 - 1 SECTION 22 14 36 PACKAGED, SUBMERSIBLE, DRAINAGE PUMP UNITS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION A. Packaged submersibl
2、e drainage pump units. See schedule on Drawings for pump capacity and head. 1.2 RELATED WORK A. Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING. B. Section 22 05 12, GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT. C. SECTION 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS. Requirements for commiss
3、ioning, systems readiness checklist, and training. D. Section 26 29 11, LOW-VOLTAGE MOTOR STARTERS. 1.3 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Manufacturers Literature and Data: 1. Pump: a. Manufacturer and model. b. Operating speed. c.
4、 Capacity. d. Characteristic performance curves. 2. Motor: a. Manufacturer, frame and type. b. Speed. c. Current Characteristics and W (HP). d. Efficiency. C. Certified copies of all the factory and construction site test data sheets and reports. D. Complete operating and maintenance manuals includi
5、ng wiring diagrams, technical data sheets and information for ordering replaceable parts: 1. Include complete list indicating all components of the systems. 2. Include complete diagrams of the internal wiring for each item of equipment. 3. Diagrams shall have their terminals identified to facilitate
6、 installation, operation and maintenance. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-01-11 22 14 36 - 2 E. Completed System Readiness Checklist provided by the Commissioning Agent and completed by the contractor, signed by a qualified technician
7、 and dated on the date of completion, in accordance with the requirements of Section 22 08 00 COMMISSIONING OF PLUMBING SYSTEMS. 1.4 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the
8、 basic designation only. B. National Electrical Manufacturers Association (NEMA): ICS6-93 (R2006).Industrial Control and Systems Enclosures 250-2008Enclosures for Electrical Equipment (1000 Volts Maximum) C. Underwriters Laboratories, Inc. (UL): 508-99 (R2008)Standards For Industrial Control Equipme
9、nt PART 2 - PRODUCTS SPEC WRITER NOTE: Make material requirements agree with applicable requirements specified in the referenced Applicable Publications. Update and specify only that which applies to the project. Coordinate and assure that the electrical characteristics specified below are clearly s
10、hown on the proper drawings. 2.1 SUBMERSIBLE DRAINAGE PUMP A. Centrifugal, submersible, designed for / 60 / 82 / degrees C (/ 140 / 180 / degrees F) maximum water temperature. Driver shall be electric motor with rigid type support. Provide perforated, nonferrous suction strainer: Systems may include
11、 one, two, or more pumps with alternator as required by Contract Documents: 1. Pump housings may be cast iron, bronze, or stainless steel. Cast iron housings for submersible pumps shall be epoxy coated. B. Impeller: Brass or bronze. C. Shaft: Bronze, stainless steel or other approved corrosion-resis
12、ting metal. D. Bearings: As required to hold shaft alignment, anti-friction type for thrust permanently lubricated. SPEC WRITER NOTE: Use NEMA 4 for dripproof (vertical) or NEMA 6P for completely enclosed (submersible). E. Motor: Maximum 40 degrees C ambient temperature rise, completely enclosed, vo
13、ltage and phase as shown in schedule on Electrical drawings conforming to NEMA 250- -Type 6P. Size the motor capacity to operate the pump without overloading the motor at any point on the pump curve Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-01-
14、11 22 14 36 - 3 Refer to Section 22 05 12, GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT. F. Starting Switch: Manually-operated, tumbler type, as specified in Section 26 29 11, LOW-VOLTAGE MOTOR STARTERS. G. Automatic Control and Level Alarm: Furnish a control panel in a / Nema 1 enclosure for i
15、ndoors / Nema 4X enclosure for outdoors / . The controls shall be suitable for operation with the electrical characteristics listed on the Electrical drawings. The control panel shall have a level control system with switches to start and stop pumps automatically, and to activate a high water alarm.
16、 The level control system will include sensors in the sump that detect the level of the liquid. The sensors may be float type switches, ultrasonic level sensors, transducers, or other appropriate equipment. The high water alarm shall have a red beacon light at the control panel and a buzzer, horn, o
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2214362011PACKAGEDSUBMERSIBLEDRAINAGEPUMPUNITSPDF

链接地址:http://www.mydoc123.com/p-1074881.html