UL SUBJECT 710C-2006 OUTLINE OF INVESTIGATION FOR ULTRAVIOLET RADIATION SYSTEMS FOR USE IN THE VENTILATION CONTROL OF COMMERCIAL COOKING OPERATIONS (Issue 3)《商用烹饪作业的通风控制用紫外线辐射系统调查大.pdf
《UL SUBJECT 710C-2006 OUTLINE OF INVESTIGATION FOR ULTRAVIOLET RADIATION SYSTEMS FOR USE IN THE VENTILATION CONTROL OF COMMERCIAL COOKING OPERATIONS (Issue 3)《商用烹饪作业的通风控制用紫外线辐射系统调查大.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 710C-2006 OUTLINE OF INVESTIGATION FOR ULTRAVIOLET RADIATION SYSTEMS FOR USE IN THE VENTILATION CONTROL OF COMMERCIAL COOKING OPERATIONS (Issue 3)《商用烹饪作业的通风控制用紫外线辐射系统调查大.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULSeptember 22, 20061SUBJECT 710COUTLINE OF INVESTIGATIONFORULTRAVIOLET RADIATION SYSTEMS FOR USE IN THE VENTILATIONCONTROL OF COMMERCIAL COOKING OPERATIONSIssue Number: 3September 22, 2006Summary
2、of TopicsThis Third Issue of the Outline of Investigation for Ultraviolet RadiationSystems for Use in the Ventilation Control of Commercial CookingOperations, Subject 710C, is issued to make the following importantupdates in requirements: a) Title (the Second Issue was titled Outline ofInvestigation
3、 for Ultraviolet Lamps Used for Reduction of Grease LadenVapors from Cooking Equipment) and Scope changed to better align withNFPA 96; b) Glossary is expanded for clarity; c) 7.2 allows other materialthan metal and to evaluate the suitability of the barrier by test; d) 7.3allows filters and other UV
4、 attenuation barriers to be evaluated by test; e)7.4 requires UV attenuation barriers also serving as filters to comply withUL 1046 or UL 710 as appropriate for the filter; f) 7.5 requires thatattenuation barriers with adjustable features to be adjusted to the worstcase position for test; g) 7.12 al
5、lows for cleaning of the interlock, h) 7.13requires a pressure interlock to de-energize the UV lamp when the portsare plugged; i) 7.19 requires a ballast to comply with UL 935 or UL 1029; j)7.21 and 17.8 require UV lamps to be marked; k) 7.22 requires the hoodexhaust to be marked for lamp replacemen
6、t; l) 8.1 added requirements forUV protection for electrical insulation; m) 9.1 changes the requirementsfor Water Wash Hoods to test with water wash nozzles; n) 10.1 addsrequirements for protection of electrical components from condensation;o) 11.1 and 11.2 adds requirement for gaskets and seals to
7、comply withUL 710 test; p) in Section 14, replace former UL 1598 water spray test withactual water wash hood nozzle tests; q) Section 16, clarifies a one-minuteactivation allowance for interlock systems; r) 17.1 adds adhesive labelrequirement to comply with UL 969; s) 17.2 adds that printed labelssh
8、ould not be exposed to the UV source; t) 17.5 revised to allowan equivalent statement; u) 17.6 adds required marking for filterattenuation barriers; v) 17.7 adds required markings for multi-piece filterattenuation barriers; w) 17.9 requires the hood to be marked for UV lampreplacement; x) 18.4 adds
9、lamp replacement information to theinstructions; y) 18.5 gasket replacement information added to theinstructions; and z) 18.6 requires information on the water wash systemmaintenance and nozzles.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL
10、The UL Foreword is no longer located within the UL Standard. For informationconcerning the use and application of the requirements contained in thisStandard, the current version of the UL Foreword is located onULStandardsInfoNet at: http:/ 2006 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL N
11、OT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 General 43 Components 44 Undated References 55 Units of Measurement .56 Glossary .5CONSTRUCTION7 Assembly 78 Electrical Insulation 99 Water Wash Hoods 1010 Moisture Condensation 1011 Mater
12、ials .10PERFORMANCE12 Ultraviolet (UV) Irradiance Test .1013 Temperature Tests 1114 Water Wash Spray Test .1114.1 General .1115 Endurance Test for Interlock Devices .1216 Test for Pressure Interlock Devices .12MARKINGS17 General 13INSTRUCTIONS18 Installation Instructions 14APPENDIX AStandards for Co
13、mponents .A1SEPTEMBER 22, 2006 SUBJECT 710C 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover ultraviolet (UV) radiation lamp systems used for the reduction of greaseladen vapors from commercial c
14、ooking equipment when installed within Listed Exhaust Hoods forCommercial Cooking Equipment.1.1 effective March 22, 20091.2 These requirements are not intended to address the effectiveness of the UV radiation to reducegrease-laden vapors from cooking operations.1.2 effective March 22, 20091.3 This O
15、utline applies to UV lamp assemblies for use in locations that are intended for installation onbranch circuits of 600 V nominal or less between conductors in accordance with the National ElectricalCode (NEC), ANSI/NFPA 70.1.3 effective March 22, 20092 General2.1 Exhaust hoods provided with UV lamp a
16、ssemblies shall comply with all requirements of the Standardfor Exhaust Hoods for Commercial Cooking Equipment, UL 710, unless otherwise specified in this Outline.2.1 effective March 22, 20093 Components3.1 Except as indicated in 3.2, a component of a product covered by this Outline shall comply wit
17、h therequirements for that component. See Appendix A for a list of standards covering components generallyused in the products covered by this Outline.3.1 effective March 22, 20093.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristics not n
18、eeded in the application of the component in theproduct covered by this Outline; orb) Is superseded by a requirement in this Outline.3.2 effective March 22, 20093.3 A component shall be used in accordance with its rating for the intended conditions of use.3.3 effective March 22, 20093.4 Specific com
19、ponents are accepted as being incomplete in construction features, or restricted inperformance capabilities. Such components are intended for use only under limited conditions, such astemperatures not exceeding specified limits, and shall be used only under those specific conditions forwhich they ha
20、ve been investigated.3.4 effective March 22, 2009SEPTEMBER 22, 2006SUBJECT 710C4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4 Undated References4.1 Any undated reference to a code or standard appearing in the requirements of this Outline s
21、hall beinterpreted as referring to the latest edition of that code or standard.4.1 effective March 22, 20095 Units of Measurement5.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.5.1 effective March 22, 20095.2 Unless indicated
22、 otherwise, all voltage and current values mentioned in this Outline areroot-mean-square (rms).5.2 effective March 22, 20096 Glossary6.1 For the purpose of this Outline, the following definitions apply.6.1 effective March 22, 20096.2 BALLAST A current limiting device required to start and operate fl
23、uorescent and cold cathodelamps.6.2 effective March 22, 20096.3 BALLAST, REMOTE A ballast that is not mounted in the UV luminaire assembly.6.3 effective March 22, 20096.4 ENCLOSURE That part of the product that:a) Renders inaccessible all or any parts of the equipment that may otherwise present a ri
24、sk ofelectric shock and/orb) Retards propagation of flame initiated by electrical disturbances occurring within.6.4 effective March 22, 20096.5 FIXTURE Referenced as a luminaire in this Outline.6.5 effective March 22, 20096.6 GASKET A resilient elastomeric material used between two rigid surfaces.6.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便