1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJANUARY 26, 20151UL 509Outline of Investigation for Bus Drop CableIssue Number: 2January 26, 2015Summary of TopicsThis outline is being revised to make grounding conductors optional.COPYRIGHT 201
2、5 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJANUARY 26, 2015UL 5092No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODU
3、CTION1 Scope .4CONSTRUCTION2 Assembly 43 Circuit and Grounding Conductors 44 Overall Jacket 5MARKINGS5 On the Cable .56 On the Tag, Reel, or Carton 6TEST PROGRAM7 Details .6JANUARY 26, 2015 UL 509 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM
4、 ULINTRODUCTION1 Scope1.1 This Outline covers bus drop cable for use as described in Section 368.56 (B) and other applicableparts of the National Electrical Code (NEC), NFPA 70.CONSTRUCTION2 Assembly2.1 The cable shall consist of 3 or 4 insulated circuit conductors of the same type and size cabledto
5、gether with an optional grounding conductor, plus fillers as necessary to make the finished cable roundand firm, and an overall jacket of material rated for the dry temperature rating of the insulated conductors.All conductors shall be stranded. The cable shall not contain both thermoplastic and the
6、rmoset materials.3 Circuit and Grounding Conductors3.1 The circuit conductors and any optional grounding conductor that is insulated shall be unmarked TypeTW, THW, THW-2, THHN, THWN, THWN-2 as described in the Standard for Thermoplastic-InsulatedWires and Cables, UL 83 or Type XHHW, XHHW-2, RHW, RHW
7、-2, or RHH wires as described in theStandard for Thermoset-Insulated Wires and Cables, UL 44. All conductors shall be stranded and in sizes14 4/0 AWG if of copper and in sizes 12 4/0 AWG if of aluminum or copper-clad aluminum.3.2 The optional grounding conductor shall be bare or fully insulated and
8、of the same type as the circuitconductors and shall not be located in the center of the cable core. A bare grounding conductor shall bein one or more sections that are cabled with the circuit conductors. The grounding conductor shall not besmaller in size than indicated in Table 3.1. The individual
9、members of a sectioned grounding conductorshall not be smaller than 18 AWG.Table 3.1Minimum size of optional grounding conductorSize of circuit conductors, AWG Minimum size of grounding conductor, AWGCopper circuit conductors and grounding conductor14 1412 12106 1042 81 4/0 6Aluminum or copper-clad
10、aluminum circuit conductors and grounding conductor12 12104 83 1/0 62/0 4/0 4JANUARY 26, 2015UL 5094UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4 Overall Jacket4.1 The average and point thicknesses of the overall jacket shall not be less t
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT5092015ULOUTLINEFORINVESTIGATIONBUSDROPCABLEISSUE2 总线 分支 电缆 UL 调查 大纲 议题 PDF

链接地址:http://www.mydoc123.com/p-1069452.html