1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMAY 5, 20171UL 504Outline of Investigation for Mineral-Insulated, Metal-Sheathed CableIssue Number: 1May 5, 2017Summary of TopicsThis first issue of the Outline of Investigation for Mineral-Insul
2、ated,Metal-Sheathed Cable, UL 504.ULs Outlines of Investigation are copyrighted by UL LLC. Neither a printed norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Inves
3、tigation shall remain the sole and exclusive property of ULLLC.COPYRIGHT 2017 UL LLCUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMAY 5, 2017UL 5042No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIB
4、UTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Units of Measurement .43 Undated References 4CONSTRUCTION4 Materials .45 Conductors .56 Insulation 57 Metal Sheath .58 Overall Nonmetallic Covering .68.1 Material .68.2 Properties .78.3 Thicknesses .79 Assembly 8PERFORMANCE10 Continuity
5、 Test of Conductors .811 Dielectric Strength Test .812 Insulation Resistance .813 DC Resistance of Conductors .914 Flexibility Test .915 Test for Durability of Ink Printing 1016 Cable Flame Test (Required for Cables with a Nonmetallic Covering) .1017 Deformation Test (Required for Cables with an Ove
6、rall Nonmetallic Covering of Thermoplastic orXL)1018 Cold-Bend Test (Required for Cables with a Nonmetallic Covering) .1019 Vertical-Tray Flame Test (Optional for Cables with a Nonmetallic Covering) .1120 FT4 Test (Optional for Cables with a Nonmetallic Covering) .1121 Sunlight-Resistance Test (Opti
7、onal for Cables with a Nonmetallic Covering, Required for Cableswith a Nonmetallic Sheath Suitable for Use Outdoors) .1122 Crushing Test (Optional for Cables with a Nonmetallic Covering) .1123 Oil Resistance (Optional for Cables with a Nonmetallic Covering) .1124 Gasoline Resistance (Optional for Ca
8、bles with a Nonmetallic Covering) .12MARKINGS25 Information on the Cable 1226 Information on the Tag, Reel, or Carton .13MAY 5, 2017 UL 504 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 This Outline of Investigation c
9、overs mineral-insulated (Type MI) metal-sheathed cable, which consistsof one or more solid copper conductors insulated with highly compressed magnesium oxide and enclosedin a continuous copper or alloy steel sheath, with or without a nonmetallic jacket.1.2 Cables rated 600 V may be composed of 16 AW
10、G to 500 kcmil single conductor, 16 to 4 AWG twoand three conductor, 16 to 6 AWG four conductor, and 16 to 10 AWG seven conductor constructions.Cables rated 300 V may be composed of two, three, four and seven conductor, sizes 18 to 16 AWG, foruse on signaling circuits.1.3 The copper sheath is suitab
11、le as an equipment grounding conductor. For cable with alloy steel outersheath one of the insulated conductors is to be used for equipment grounding.1.4 The cable shall be installed in accordance with Article 332 of National Electrical Code, NFPA 702 Units of Measurement2.1 The unit of measure shall
12、 be SI. If a value for measurement is followed by a value in other units inparentheses, the second value represents a direct conversion or an alternative value.3 Undated References3.1 Any undated reference to a code or standard appearing in the requirements of this Outline shall beinterpreted as ref
13、erring to the latest edition of that code or standard.3.2 Wherever the designation UL 1581 is used in this cable Outline, reference is to be made to thedesignated part(s) of the Reference Standard for Electrical Wires, Cables, and Flexible Cords, UL 1581.Whenever the designation UL 2556 is used in t
14、his standard, reference is to be made to the designatedparts of the Wire and Cable Test Methods, UL 2556.CONSTRUCTION4 Materials4.1 Only materials that are acceptable for the particular use shall be employed in a cable.4.2 Each material used in a cable shall be compatible with all of the other mater
15、ials used in the cable.MAY 5, 2017UL 5044UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL5 Conductors5.1 Conductors shall be uncoated copper, nickel or nickel clad copper.5.2 Uncoated copper conductors shall comply with the requirements of Sta
16、ndard Specification for Soft orAnnealed Copper Wire, ASTM B3.5.3 Nickel-clad copper conductors shall comply with the requirements of Standard Specification forNickel-Coated Soft or Annealed Copper Wire, ASTM B355.5.4 Nickel conductors shall comply with the requirements of Standard Specification for
17、Nickel Rod andBar, ASTM B1606 Insulation6.1 The insulation shall consist of highly compressed, powdered magnesium oxide.6.2 The minimum insulation thickness between conductors and between conductors and sheath(s) shallbe 0.055 inches.6.3 Compliance with 6.2 shall be determined in accordance with the
18、 method described in 6.3.1 6.3.4.6.3.1 The end of one specimen shall be filed smooth. The end of the specimen shall be fliedperpendicular to the length of the specimen (right-circular cylinder).6.3.2 The mineral insulation shall be carefully removed from the filed end of the specimen to a depth ofat
19、 least 0.01 inches without disturbing the position of the conductors within the cable.6.3.3 A steel gauge shall be inserted between adjacent conductors and between the conductors and thesheath.6.3.4 A steel gauge of 0.054 inches shall pass between adjacent conductors and between the conductorsand th
20、e sheath without disturbing the position of the conductors.7 Metal Sheath7.1 The sheath shall consist of annealed copper or alloyed steel.7.2 The thickness of the sheath shall not be less than the values shown in Table 7.1.MAY 5, 2017 UL 504 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPROD
21、UCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 7.1Thickness of sheathSize of conductor,AWG or kcmilMinimum thickness at any point, milsNumber of conductors12347-1418 19 27 28 28 3116 19 27 28 28 3114 19 27 28 28 3112 19 27 28 28 3110 19 27 28 28 318 20272830366 2303134 4 43436 3 2638382 71 8/
22、022 3034/05250 37 350 39 500 41 7.3 Compliance with the requirements in Table 7.1 shall be determined in accordance with the methodThickness, described in UL 2556.7.4 Joints are permitted in the sheath as long as the thickness requirements and integrity of the mineralinsulation and sheath are mainta
23、ined.8 Overall Nonmetallic Covering8.1 Material8.1.1 An overall nonmetallic covering over the sheath is optional. When applied, the covering shall beeither thermoplastic or thermoset.MAY 5, 2017UL 5046UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION F
24、ROM UL8.2 Properties8.2.1 Specimens prepared from samples of the overall covering taken from the finished cable shall exhibitphysical properties that comply with the requirements in Table 8.1 when tested as indicated in this section.8.2.2 Compliance shall be determined in accordance with the test, P
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT5042017OUTLINEOFINVESTIGATIONFORMINERALINSULATEDMETALSHEATHEDCABLEISSUE1PDF

链接地址:http://www.mydoc123.com/p-1069448.html