《UL SUBJECT 1712-2006 Outline of Investigation for Tests for Ampacity of Insulated Electrical Conductors Installed in the Fire Protective System (Issue 4)《防火系统中安装的绝缘电导线的安培容量试验调查大纲 发.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 1712-2006 Outline of Investigation for Tests for Ampacity of Insulated Electrical Conductors Installed in the Fire Protective System (Issue 4)《防火系统中安装的绝缘电导线的安培容量试验调查大纲 发.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULDecember 12, 20061SUBJECT 1712OUTLINE OF INVESTIGATIONFORTESTS FOR AMPACITY OF INSULATED ELECTRICAL CONDUCTORSINSTALLED IN THE FIRE PROTECTIVE SYSTEMIssue Number: 4DECEMBER 12, 2006Summary of Top
2、icsThis new issue of SU 1712 is being issued through ULs electronicpublishing system to ensure format uniformity between the PDF andHTML versions of the document. No substantive changes have beenincorporated in the document.The UL Foreword is no longer located within the UL Standard. For information
3、concerning the use and application of the requirements contained in thisStandard, the current version of the UL Foreword is located onULStandardsInfoNet at: http:/ 2006 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FRO
4、M ULDECEMBER 12, 2006SUBJECT 17122No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION .4GENERAL1 Scope .52 Glossary .53 Units of Measurement .6TEST METHOD4 Control of Tests .64.1 Test enclosure .64.2 Test e
5、nclosure temperature 64.3 Electrical conductor temperature .64.4 Electrical current .95 Test Samples .105.1 Through-penetration firestops .105.2 Electrical circuit protective systems 105.3 Protection and conditioning of test specimen 10TESTS6 Reference Ampacity Test .117 Ampacity Test .118 Determina
6、tion of Ampacity Reduction 119 Report of Results 12DECEMBER 12, 2006 SUBJECT 1712 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTIONBecause dielectric insulating materials tend to deteriorate at elevated temperatures, the size of an
7、electrical conductor insulated with these materials is typically selected so that the operating temperatureof the conductor is below that at which rapid deterioration of the insulation begins. The operatingtemperature of a specific type of electrical conductor is affected by the current flowing thro
8、ugh theconductor as well as other factors.Ampacity is the maximum current, expressed in amperes, that an electrical conductor can carrycontinuously under conditions of use without exceeding the temperature rating specified for the conductor.The National Electrical Code (NEC) publishes the ampacities
9、 of electrical conductors used for generalwiring.The heat dissipation characteristics of cables can be affected at areas where cables are enclosed in fireprotective systems.Fire protective systems in which insulated electrical conductors are installed include through-penetrationfirestops and electri
10、cal circuit protective systems. A through-penetration firestop is a device or specificconstruction of fill materials designed to resist the penetration of fire through openings made in fireresistive floors or walls to accommodate penetrating items such as insulated electrical wires and cables,cable
11、trays, busways, cablebus, conduits, ducts and pipes. The Standard for Fire Tests ofThrough-Penetration Firestops, UL 1479 (ASTM E814) describes the method used to measure thefire-resistive performance of the devices, materials and assemblies. An electrical circuit protective systemis a specific cons
12、truction of devices, materials or protective coatings, installed around, or applied to,insulated electrical wires and cables, cable trays, busways, cablebus, conduits, junction boxes and otherinsulated electrical conductor raceways. Electrical circuit protective systems are classified with respect t
13、otheir ability to maintain the integrity of the electrical circuits during a standardized exposure to an exteriorfire. The Outline of Investigation for Fire Tests of Electrical Circuit Protective Systems, UL 1724, describesthe method used to measure to the fire resistive performance of the device, m
14、aterials or protectivecoatings.Both the materials and construction features of devices or systems used to protect insulated electricalconductors used in fire protective systems may impede the dissipation of heat from these conductors andcause higher operating temperatures than similar unprotected co
15、nductors carrying the same current. Theeffect of this reduced heat dissipation can be compensated for by reducing the ampacity of theconductors.This Outline of Investigation describes a standard test method for measuring the reduction in ampacity ofinsulated electrical conductors which are enclosed
16、in specific fire protective systems. The ampacityreduction is expressed in terms applicable to a wide variety of materials, cable configurations and ambienttemperatures.Ampacity reduction of insulated electrical conductors used in fire protective systems is defined as thereduction in ampacity necess
17、ary to prevent those conductors from exceeding their rated operatingtemperature applicable to installations covered by the National Electrical Code, NFPA 70. Ampacityreduction is reported as a percent reduction of published rated current.DECEMBER 12, 2006SUBJECT 17124UL COPYRIGHTED MATERIAL NOT AUTH
18、ORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULGENERAL1 Scope1.1 These requirements cover the investigation of ampacity of insulated electrical conductors used inspecific fire protective systems employing various materials and construction types.1.2 This test method is inte
19、nded to determine the ampacity reduction required when insulated electricalconductors are used in specific fire protective systems under normal operating conditions.1.3 The results obtained by use of this test method are intended to develop data that will assist authoritieshaving jurisdiction, and o
20、thers, in determining the acceptability, with reference to their ampacity, ofinsulated electrical conductors installed in specific fire protective systems.2 Glossary2.1 For the purpose of this outline the following definitions apply.2.2 AMPACITY The current, in amperes, that an electrical conductor
21、can carry continuously underconditions of use without exceeding the temperature rating of the conductor.2.3 ELECTRICAL CIRCUIT PROTECTIVE SYSTEM A specific construction of devices, materials orprotective coatings, installed around, or applied to, electrical conductors, raceways, or both, to maintain
22、the integrity of electrical circuits subjected to a standardized exposure to an exterior fire. The Outline ofProposed Investigation for Fire Tests of Electrical Circuit Protective Systems, Subject 1724, describesthe method used to measure the fire resistive performance of the devices, materials or p
23、rotectivecoatings.2.4 ELECTRICAL CONDUCTORS Insulated wires, cables, cablebus, and busbars.2.5 FIRE PROTECTIVE SYSTEM Through-penetration firestops and electrical circuit protectivesystems.2.6 RACEWAY Cable trays and enclosed channels designed to hold wires, cables, cablebus, orbusbars may be of met
24、al or insulating material. A raceway includes rigid metal conduit, rigid nonmetallicconduit, intermediate metal conduit, liquidtight flexible metal conduit, flexible metallic tubing, flexiblemetal conduit, electrical metallic tubing, under-floor raceways, cellular concrete floor raceways, cellularme
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT17122006OUTLINEOFINVESTIGATIONFORTESTSFORAMPACITYOFINSULATEDELECTRICALCONDUCTORSINSTALLEDINTHEFIREPROTECTIVESYSTEMISSUE4

链接地址:http://www.mydoc123.com/p-1069190.html