《UL SUBJECT 1699A-2010 OUTLINE OF INVESTIGATION FOR OUTLET BRANCH CIRCUIT ARC-FAULT CIRCUIT-INTERRUPTERS (Issue 2)《出口线路电弧故障断路器的调查大纲 (议题2)》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 1699A-2010 OUTLINE OF INVESTIGATION FOR OUTLET BRANCH CIRCUIT ARC-FAULT CIRCUIT-INTERRUPTERS (Issue 2)《出口线路电弧故障断路器的调查大纲 (议题2)》.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMarch 17, 20101SUBJECT 1699AOUTLINE OF INVESTIGATIONFOROUTLET BRANCH CIRCUIT ARC-FAULT CIRCUIT-INTERRUPTERSIssue Number 2MARCH 17, 2010COPYRIGHT 2010 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED
2、MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMARCH 17, 2010SUBJECT 1699A2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Glossary .43 Components 4
3、4 Units of Measurement .55 Undated References 5CONSTRUCTION6 General 57 Spacings .58 Terminals 59 Housings .610 Grounding 6PERFORMANCE11 General .612 Impact Test .713 Leakage Current Measurement 714 Arc Fault Detection Tests .714.1 Carbonized path arc ignition test 714.2 Carbonized path arc clearing
4、 time test .715 Unwanted Tripping Tests .815.1 Loading condition II normal operation arcing 816 Operation Inhibition Tests .816.1 General 816.2 EMI filter .817 Short Circuit Current Test .8RATINGS18 General .9MARKINGS19 General .920 Installation Instructions/Owners Manual 9MARCH 17, 2010 SUBJECT 169
5、9A 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover arc-fault circuit-interrupters (AFCIs) of the outlet branch circuit typeintended for use in dwelling units. These devices are intended to mitig
6、ate the effects of arcing faults thatmay pose a risk of fire ignition under certain conditions if the arcing persists.1.2 These devices have a maximum rating of 20 A and are intended for use in 120-V ac, 60-HZ circuits.1.3 These requirements are intended to be used with the Standard for Arc-Fault Ci
7、rcuit-Interrupters, UL1699, as these requirements modify the requirements described in that standard.1.4 Unless otherwise specified, when the term arc-fault circuit-interrupter or AFCI is used in thisOutline, it refers to an arc-fault circuit-interrupter of the outlet branch circuit type, also known
8、 as an outletbranch circuit arc-fault circuit-interrupter (OBC AFCI).2 Glossary2.1 For the purposes of this Outline of Investigation, the following definition applies.2.2 OUTLET BRANCH CIRCUIT ARC-FAULT CIRCUIT-INTERRUPTER A device intended to beinstalled as the first outlet in a branch circuit. It
9、is intended to provide protection to downstream branchcircuit wiring, cord sets, and power-supply cords against the unwanted effects of arcing. This devicealso provides protection to upstream branch circuit wiring. It is intended to be provided with or withoutreceptacle outlets.3 Components3.1 Excep
10、t as indicated in 3.2, a component of a product covered by this Outline of Investigation shallcomply with the requirements for that component.3.2 A component need not comply with a specific requirement that:a) Involves a feature or characteristic not needed in the application of the component in the
11、product covered by this Outline of Investigation, orb) Is superceded by a requirement in this Outline of Investigation.3.3 A component shall be used in accordance with its recognized rating established for the intendedconditions of use.3.4 Specific components are recognized as being incomplete in co
12、nstruction features or restricted inperformance capabilities. Such components are intended for use only under limited conditions, such ascertain temperatures not exceeding specified limits, and shall be used only under those specific conditionsfor which they have been recognized.MARCH 17, 2010SUBJEC
13、T 1699A4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4 Units of Measurement4.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.5 Undated References5.1 Any undated refere
14、nce to a code or standard appearing in the requirements of this Outline ofInvestigation shall be interpreted as referring to the latest edition of that code or standard.CONSTRUCTION6 General6.1 In addition to the construction requirements in Sections 6-15 of the Standard for Arc-FaultCircuit-Interru
15、pters, UL 1699, an outlet branch circuit arc-fault circuit-interrupter shall comply with Sections20-23 of UL 1699.6.2 An outlet branch circuit AFCI shall also comply with the construction requirements for receptacles,including the enclosure requirements, in the Standard for Attachment Plugs and Rece
16、ptacles, UL 498.7 Spacings7.1 For Clearance B (controlled overvoltage) requirements in the Standard for Insulation CoordinationIncluding Clearances and Creepage Distances for Electrical Equipment, UL 840, the applicableovervoltage category for line-voltage circuits is Category III for outlet branch
17、circuit AFCIs. Anyovervoltage protection device needed to achieve these categories shall be provided as an integral part ofthe arc-fault circuit-interrupter.8 Terminals8.1 An outlet branch circuit AFCI shall comply with the terminal requirements in Terminals, Section 17 ofthe Standard for Arc-Fault
18、Circuit-Interrupters, UL 1699, except that the minimum wire binding screw sizeis No. 8 (4.2 mm).MARCH 17, 2010 SUBJECT 1699A 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL9 Housings9.1 An outlet branch circuit AFCI shall comply with the mat
19、erials requirements in Sections 8.1 8.7 ofthe Standard for Attachment Plugs and Receptacles, UL 498.10 Grounding10.1 An outlet branch circuit AFCI shall comply with the grounding requirements in Grounding, Section19, of the Standard for Arc-Fault Circuit-Interrupters, UL 1699.PERFORMANCE11 General11
20、.1 An outlet branch circuit arc-fault circuit-interrupter shall comply with the performance requirementsfor arc-fault circuit-interrupters in the Standard for Arc-Fault Circuit-Interrupters, UL 1699, as detailed inTable 34.1 of UL 1699 and Table 11.1 of this Outline of Investigation.Table 11.1Arc fa
21、ult detection tests tableTests in the Standard for Arc-Fault Circuit-Interrupters, UL 1699Outlet branch circuitAFCI40.2 Carbonized path arc ignition testNM-B insulation cut X40.3 Carbonized path arc interruption testSPT-2 insulation cut XNM-B insulation cut X40.4 Carbonized path arc clearing time te
22、stSPT-2 insulation cut XNM-B insulation cut X40.5 Point contact arc testSPT-2 insulation cut XNM-B insulation cut X41 Unwanted tripping tests41.2 Load condition I inrush X41.3 Load condition II normal operation arcingconditionsac Xconditionsde XLoad condition in 15.1.1 of this Outline of Investigati
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT1699A2010OUTLINEOFINVESTIGATIONFOROUTLETBRANCHCIRCUITARCFAULTCIRCUITINTERRUPTERSISSUE2 出口 线路

链接地址:http://www.mydoc123.com/p-1069188.html