1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAUGUST 22, 20181UL 1366Outline of Investigation for Insulated Bus PipeIssue Number: 1August 22, 2018Summary of TopicsThis First Issue of the Outline of Investigation for Insulated Bus Pipe, UL136
2、6, covers:a) Insulated Bus Pipe (IBP) having ac voltage ratings up to 46 kV;b) Equipment intended for use only in ordinary locations inaccordance with ANSI/NFPA 70, the National Electrical Code(locations other than those identified as “Hazardous” or“Classified Locations”); andc) IBP for installation
3、 above ground for indoor use and outdooruse, in areas which are accessible to qualified persons only.ULs Outlines of Investigation are copyrighted by UL LLC. Neither a printed norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all
4、copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of ULLLC.COPYRIGHT 2018 UL LLCUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAUGUST 22, 2018UL 13662No Text on This PageU
5、L COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .52 Components 53 Units of Measurement .54 Undated References 55 Glossary .66 Service Conditions 86.1 Normal service conditions .86.2 Special service conditions .8CONST
6、RUCTION7 General 98 Grounding and Bonding 99 Enclosures and Connecting Sleeves .1010 Connections 1111 Mounting Structure 1112 Clearance and Creepage Distances .11PERFORMANCE13 General 1213.5 Measurement of IBP and connector sleeve temperatures during testing .1313.6 Connections of conductors for con
7、tinuous current tests .1313.7 Test setup configuration .1314 Test Sequence for IBP Systems 1415 Dielectric Voltage-Withstand at Rated Frequency with Partial Discharge Measurement 1516 Power Factor and Capacitance .1617 Full Wave Lightning Impulse Withstand Voltage 1618 Chopped Wave Lightning Impulse
8、 Withstand Voltage .1719 Continuous Current-Test .1720 Cyclic Aging Test .1821 Peak Withstand and Short-Time Withstand Tests .1921.1 Peak withstand current test 1921.2 Short-time withstand current test .2122 Vertical-Tray Flame Test .2223 Limited Smoke Test .2324 Sunlight Resistance .2325 Durability
9、 of Ink Printing .2326 Rain Tests .2426.2 Driven rain test .2426.3 Extended rain test 2427 Rod Entry Test .25PRODUCTION TESTS28 Production Line Tests .2628.1 General .2628.2 Power factor and capacitance test 26AUGUST 22, 2018 UL 1366 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION O
10、RDISTRIBUTION WITHOUT PERMISSION FROM UL28.3 Visual inspection and dimensions 2628.4 Continuity of conductor .2728.5 Ground layer continuity test 2728.6 Covering integrity test .27RATING29 General 28MARKING30 General 28INSTRUCTIONS31 General 30AUGUST 22, 2018UL 13664UL COPYRIGHTED MATERIAL NOT AUTHO
11、RIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover Insulated Bus Pipe (IBP) having ac voltage ratings up to 46 kV.1.2 These requirements cover equipment intended for use only in ordinary locations in accordance withANSI/NFPA 70, th
12、e National Electrical Code (locations other than those identified as “Hazardous” or“Classified Locations”).1.3 These requirements cover IBP for installation above ground for indoor use and outdoor use, in areaswhich are accessible to qualified persons only.2 Components2.1 A component of a product co
13、vered by this Outline shall comply with the requirements for thatcomponent and shall be used in accordance with its recognized rating and other limitations of use.2.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristic not required in the ap
14、plication of the component in theproduct covered by this Outline, orb) Is superseded by a requirement in this Outline.3 Units of Measurement3.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.4 Undated References4.1 Any undated r
15、eference to a code or standard appearing in the requirements of this Outline shall beinterpreted as referring to the latest edition of that code or standard.AUGUST 22, 2018 UL 1366 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL5 Glossary5.1
16、 The following terms and definitions apply as related to this Outline.5.1.1 AMBIENT AIR TEMPERATURE The temperature of the surrounding air that comes in contact withequipment.5.1.2 INSULATED BUS PIPE (IBP) A bus system that consists of a solid or hollow conductor withinsulation wound from untreated
17、paper and subsequently impregnated with a curable resin.5.1.3 CAPACITIVE GRADING A method by which desired voltage grading is obtained by anarrangement of conducting or semiconducting layers incorporated into the insulating material.5.1.4 CLEARANCE The distance between two conductive parts along a s
18、tring stretched the shortestway between these conductive parts.5.1.5 CONNECTION BOX An enclosure intended to surround the point where the IBP system isconnected to other electrical equipment, such as switchgear, to provide protection against unintentionalcontact with live parts, and to provide some
19、degree of protection against environmental contaminantswhen closely coupled with the connected equipment.5.1.6 COVERING A surrounding cover or housing used to protect the contained conductor and preventaccidental contact with live parts.5.1.7 CREEPAGE DISTANCE The shortest distance along the surface
20、 of an insulating materialbetween two conductive parts.5.1.8 FIELD WIRING TERMINAL A portion of the IBP intended for connection to cable(s) at theinstallation site.5.1.9 INDOOR USE An installation of IBP where the entire IBP system is exposed only to indooratmospheric conditions.5.1.10 MONTHLY NORMA
21、L MAXIMUM TEMPERATURE A temperature computed by averaging themaximum temperature for each day of the month, and averaging this number over 30 years.Note: The monthly normal maximum temperature for many locations in the United States can be obtained from National Centers forEnvironment Information. S
22、ee IEEE C37.24, Guide for Evaluation the Effect of Solar Radiation on Outdoor Metal-EnclosedSwitchgear for more information.5.1.11 OUTDOOR USE An installation of IBP where any portion of the system is exposed to outdooratmospheric conditions.5.1.12 SUPPORT COMPONENTS The basic subassemblies of the I
23、BP system that add strength,rigidity and support to the IBP system.AUGUST 22, 2018UL 13666UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL5.1.13 TAP BOX An enclosure intended to surround a point in the IBP system where three or moresections of
24、 IBP are joined together, to provide protection against unintentional contact with live parts, andto provide some degree of protection against environmental contaminants.5.1.14 TEMPERATURE RISE The difference between the measured temperature and the ambient airtemperature.5.1.15 TERMINATION A device
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT13662018ULOUTLINEFORINVESTIGATIONINSULATEDBUSPIPEISSUE1PDF

链接地址:http://www.mydoc123.com/p-1069164.html