REG NASA-LLIS-0516-1994 Lessons Learned Working in the Proximity of Energized Electrical Sources.pdf
《REG NASA-LLIS-0516-1994 Lessons Learned Working in the Proximity of Energized Electrical Sources.pdf》由会员分享,可在线阅读,更多相关《REG NASA-LLIS-0516-1994 Lessons Learned Working in the Proximity of Energized Electrical Sources.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、Lessons Learned Entry: 0516Lesson Info:a71 Lesson Number: 0516a71 Lesson Date: 1994-08-02a71 Submitting Organization: LARCa71 Submitted by: Bernard LewisSubject: Working in the Proximity of Energized Electrical Sources Description of Driving Event: On 7-2-91 a LaRC electrical technician was seriousl
2、y injured while preparing to check a 22kV nitrogen filled power cable in an electrical substation. When the technician came in proximity to an energized switchgear electrical terminal, an arc initiated, jumped to the technicians hand, passed into his arm, and exited from various parts of his lower b
3、ody as well as from a key ring hanging from his belt.Langley Handbook (LHB) 1710.6, “Electrical Safety“, defines safe distances for approaching exposed energized circuits. The LaRC investigation determined that the injured technician was less than the LHB 1710.6 mandated 3 feet from the injury causi