NAVY MIL-DTL-24640 7 E-2011 CABLE ELECTRIC -20 TO +105 癈 600 VOLTS LIGHTWEIGHT MULTI-CONDUCTOR 22 AWG TYPES 1XMSO AND 1XMSOW《1XMSO及1XMSOW型22 AWG多芯轻量600V -20 ℃~+105 ℃电缆》.pdf
《NAVY MIL-DTL-24640 7 E-2011 CABLE ELECTRIC -20 TO +105 癈 600 VOLTS LIGHTWEIGHT MULTI-CONDUCTOR 22 AWG TYPES 1XMSO AND 1XMSOW《1XMSO及1XMSOW型22 AWG多芯轻量600V -20 ℃~+105 ℃电缆》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-DTL-24640 7 E-2011 CABLE ELECTRIC -20 TO +105 癈 600 VOLTS LIGHTWEIGHT MULTI-CONDUCTOR 22 AWG TYPES 1XMSO AND 1XMSOW《1XMSO及1XMSOW型22 AWG多芯轻量600V -20 ℃~+105 ℃电缆》.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、AMSC N/A FSC 6145 INCH-POUND MIL-DTL-24640/7E 8 November 2011 SUPERSEDING MIL-DTL-24640/7D 22 August 2002 DETAIL SPECIFICATION SHEET CABLE, ELECTRIC, -20 TO +105 C, 600 VOLTS, LIGHTWEIGHT, MULTI-CONDUCTOR, 22 AWG, TYPES 1XMSO AND 1XMSOW This specification is approved for use by all Departments and A
2、gencies of the Department of Defense. The requirements for acquiring the product described herein shall consist of this specification sheet and MIL-DTL-24640. Construction, Non-Watertight (1XMSO) and Watertight (1XMSOW) First - 19-strand, tin-coated copper conductor, 22 AWG. Watertight constructions
3、 shall be constructed with 7 strands. Second - Component wires shall be SAE-AS81044/12, except identification shall be in accordance with the codes and methods of MIL-DTL-24640. Testing shall be in accordance with the component wire ratings and requirements listed on this specification sheet. Confor
4、mance testing shall be in accordance with SAE-AS81044 prior to cabling. Component wire color shall be white, unless specified otherwise. Third - Braided shield of 38 AWG tin-coated copper strands. Braid coverage shall be no less than 90 percent determined in accordance with WC-27500. Fourth - Shield
5、 insulation of two polyester tapes or a polyester tape and extruded jacket. Identification codes applied using Method 2. Fifth - The required number of shielded and jacketed singles shall be cabled together. Cabling sequence shall be consecutive, starting with number 1 from center outward. Fillers m
6、ay be used, as necessary, to form a round cable. Sixth - Optional binder tape. Seventh - Braided shield, tin-coated copper strands. Braid must be constructed to meet surface transfer impedance requirements as listed herein. Eighth - Optional binder tape. Ninth - Cross-linked polyolefin jacket (see t
7、able I for thickness). NOTE: Manufacturers identification tape or thread is required (see 3.7.3). Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-24640/7E 2 TABLE I. Construction details. PIN M24640/7 Type number Number of component wires Jac
8、ket thickness (inch) (min.) Cable diameter (inch) Cable weight (pounds per 1000 feet) (max.) (min.) (max.) -01UO -02UO -03UO -04UO -05UO -06UO 1XMSO-7 1XMSO-16 1XSMO-70 1XMSOW-7 1XMSOW-16 1XSMOW-70 7 16 70 7 16 70 0.038 0.041 0.044 0.038 0.041 0.044 0.344 0.471 0.859 0.360 0.480 0.875 0.370 0.507 0.
9、925 0.385 0.510 0.925 116.0 212.0 735.0 144.0 255.0 900.0 REQUIREMENTS: Qualification required. Construction details: See table I. Component wire: The component wire shall be in accordance with SAE-AS81044 and shall be tested in accordance with the following wire ratings and additional requirements.
10、 Temperature rating 150 C (302 F) (max.) conductor temperature Voltage rating 600 volts (root mean square) at sea level Accelerated aging Non-blocked Oven temperature, 3002 C (5723.6 F) for 6 hours Water-blocked Oven temperature, 2502 C (4823.6 F) for 6 hours Blocking 1502 C (3023.6 F) Flammability
11、30 seconds (max.) 3.0 inch (max.)No flaming of tissue paper Humidity resistance 5000 megohms for 1000 feet (min.) insulation resistance after humidity exposure Dielectric test (100% test) Primary insulation Impulse test - 6.0 kV (peak) or 3 kHz spark test - 1.5kV root mean square Component wire Impu
12、lse test - 8.0 kV (peak) or 3 kHz spark test - 5.5kV root mean square Insulation resistance 5000 megohms for 1000 feet (min.) Life cycle Non-blocked Oven temperature, 2002 C (3923.6 F) for 168 hours Water-blocked Oven temperature, 2002 C (3923.6 F) for 120 hours Physical properties of primary insula
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILDTL246407E2011CABLEELECTRIC20TO105 600 VOLTSLIGHTWEIGHTMULTICONDUCTOR22AWGTYPES1XMSOAND1XMSOW1XMSO

链接地址:http://www.mydoc123.com/p-978630.html