DIN EN 16840-2017 Inland navigation vessels - Electrical shore connection three-phase current 400 V 50 Hz at least 250 A German version EN 16840 2017《内河航行用船舶 电气岸电连接 三相电流400 V 50 Hz.pdf
《DIN EN 16840-2017 Inland navigation vessels - Electrical shore connection three-phase current 400 V 50 Hz at least 250 A German version EN 16840 2017《内河航行用船舶 电气岸电连接 三相电流400 V 50 Hz.pdf》由会员分享,可在线阅读,更多相关《DIN EN 16840-2017 Inland navigation vessels - Electrical shore connection three-phase current 400 V 50 Hz at least 250 A German version EN 16840 2017《内河航行用船舶 电气岸电连接 三相电流400 V 50 Hz.pdf(23页珍藏版)》请在麦多课文档分享上搜索。
1、May 2017 English price group 12No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 29.120.30; 47.020.60; 47.060; 93.140
2、!%eD electrical installation for supplying electrical energy to inland navigation vessels in ports and at landing stages 3.3 DIN EN 16840:2017-05 EN 16840:2017 (E) 7 charging station the shore-based section of the electrical shore connection, with one or more connection unit(s) 3.4 on-shore connecti
3、on unit a unit for connecting to the on-board electrical power network 3.5 transfer station spatially separated section of an on-shore unit with single conductor sockets for the on-shore connection cables Note 1 to entry: See 4.1, Figure 1 b. 3.6 on-shore connection monitoring system consisting of s
4、everal components, which releases the supply of on-shore power after inserting and locking single plug-type connectors. 3.7 on-shore connection line single-core flexible line provided with plugs and on-board couplings 3.8 rectifier unit on-board devices which transfer electrical energy 3.9 landing s
5、tage a shore location for landing vehicles 4 Requirements 4.1 Components The electrical shore connection consists of the following components, see Figure 1: Charging station according to Annex A; Transfer station according to Annex A (optional); Five on-board connecting cables according to Annex B;
6、On-board rectifier unit according to Annex B. Additional cable bridges and movable cable drums or containers (optional). DIN EN 16840:2017-05 EN 16840:2017 (E) 8 a) Charging station, schematic representation o b) Charging station with transfer station, schematic representation Key 1 Charging station
7、 2 Operating instructions 3 a Shore connection unit with socket outlets 3 b Shore connection unit with connection cables 4 Shore connections with plugs and on-board couplings 5 On-board rectifier unit with on-board plugs 6 Inland navigation vessel 7 Floating landing stage 8 Transfer station with soc
8、ket outlets Figure 1 Schematic representation of an electrical shore connection DIN EN 16840:2017-05 EN 16840:2017 (E) 9 4.2 Electrical characteristics The electrical shore connection shall be rated for 400 V, 50 Hz and at least 250 A current. If higher currents are required, all components of the e
9、lectrical shore connection shall be rated for these values. 4.3 Basic safety requirements 4.3.1 General In order to abandon the landing stage in an emergency, it shall be possible for trained ship crew to disconnect the connection including all the necessary switching operations at any time, without
10、 help from shore-based personnel. 4.3.2 Plug-in connectors Sockets, plugs, on-board plugs and on-board couplings shall be enclosed plug-in connectors with disengaging interlocking mechanisms as per EN 61984. The plug-in connections shall comply with the required rated current and be constructed in s
11、uch a manner that plug-in connections for different rated currents cannot be connected to one another. An appropriate plug system shall ensure that a connection can only be established in the sequence PE, N, L1, L2, L3. Disconnecting a connection should only be possible in the sequence L3, L2, L1, N
12、, PE. After establishing all individual connections, a mechanical locking mechanism shall ensure that the connection cannot be interrupted. 4.3.3 On-shore Connection Monitoring 4.3.3.1 On Shore Technical measures shall be taken to ensure that the current can only be switched on when all five on-shor
13、e connection cables are plugged in and locked both on board and on shore. Likewise, the electric on-shore connection shall be automatically switched off whenever one of the mechanical locks (on board or on shore) is opened. 4.3.3.2 On Board Technical measures shall be taken to ensure that the on-boa
14、rd power supply system can only be switched on when all five on-shore connecting cables are plugged in and locked on board. Likewise, the on-board power system shall be disconnected from the on-board rectifier as soon as the on-board lock is opened. 4.4 Other requirements It is recommended that envi
15、ronmentally-friendly materials only should be used, which have the lowest impact on the environment both in terms of production as well as disposal/recycling. DIN EN 16840:2017-05 EN 16840:2017 (E) 10 Annex A (normative) Shore-based section A.1 General A.1.1 Components The charging station consists
16、of the following components, see Figure A.1: Connection protection equipment; Overvoltage protection (optional); One or more shore connection unit(s). A shore connection unit consists of: A three-phase meter (optional); Overcurrent protection device, such as a circuit breaker with undervoltage trigg
17、ering according to EN 60947-2; On-shore connection monitoring; Five single-core socket outlets. The protection device Item 1) provides protection from short-circuits and shall comply with EN 60898-1. DIN EN 16840:2017-05 EN 16840:2017 (E) 11 Key 1 Cable protective device 2 Overvoltage protection (op
18、tional) 3 Three-phase meter (optional) 4 Overcurrent protection e.g. circuit breaker with undervoltage triggering 5 On-shore connection monitoring 6 Single-core socket outlets Figure A.1 Circuit diagram Example of a charging station with two connection units A.1.2 Designs The following designs are d
19、ifferentiated: Design A: Charging station with integrated single-core socket outlets; Design B: Charging station with spatially disconnected transfer station with integrated single-core socket outlets. A.1.3 General requirements The charging station shall be a protected design according to EN 15869-
20、2, e.g. its control elements and socket outlets are located behind a door or flap. When a socket is inserted, the door or flap shall also close in such a way that the connecting cables can be drawn out without being damaged. The charging station shall be designed so that it is as close as possible t
21、o the edge of the quay/floating landing stage. A.1.4 On-shore Connection Monitoring On-shore connection monitoring shall comply with the requirements set forth according to 4.3.3.1 NOTE On-board plug-in connections can be monitored using a loop current with an on-board reactance coil between N and L
22、3. DIN EN 16840:2017-05 EN 16840:2017 (E) 12 A.1.5 Lighting The charging station shall be equipped with lighting capable of adequately illuminating the controls, the plug-in connections and the three-phase meter. A.1.6 Transfer station If it is expected that the charging station will be designed at
23、a distance exceeding 10 m from the edge of the mooring quay/floating landing stage, a transfer station shall be provided at a distance of less than 10 m from the edge of the quay/floating landing stage. A transfer station shall have five single-core socket outlets and be lit. The trunk lines between
24、 the charging station and transfer station shall be flexible and shall be protected according to the local conditions. The trunk lines shall be protected from crushing, squeezing and/or bending and laid above the highest expected water level. The transfer station shall comply with the same requireme
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DINEN168402017INLANDNAVIGATIONVESSELSELECTRICALSHORECONNECTIONTHREEPHASECURRENT400V50HZATLEAST250AGERMANVERSIONEN168402017

链接地址:http://www.mydoc123.com/p-673237.html