CLC TR 50480-2011 Determination of cross-sectional area of conductors and selection of protective devices.pdf
《CLC TR 50480-2011 Determination of cross-sectional area of conductors and selection of protective devices.pdf》由会员分享,可在线阅读,更多相关《CLC TR 50480-2011 Determination of cross-sectional area of conductors and selection of protective devices.pdf(48页珍藏版)》请在麦多课文档分享上搜索。
1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationPD CLC/TR 50480:2011Determination of cross-sectional of protective devicesarea of conductors and selection National forewordThis Published Document is the UK implementation of CL
2、C/TR 50 :2012.The requirements for electrical installations are given in BS 7671:2008. This Technical Report sets out a uniform approach to the calculations required for the determination of cross-sectional area of conductors and the selection of the appropriate protective devices to meet the requir
3、ements of BS 7671. The main body of the technical report was developed by CENELEC TC 64. National Annex NA provides details of additional and alternative calculation methods that are used in the UK.The UK participation in its preparation was entrusted to Technical Committee JPEL/64, Electrical insta
4、llations of buildings Joint committee.A list of organizations represented on this committee can be obtained on request to its secretary. The British Standards Institution 2012. Published by BSI Standards Limited 2012.ISBN 978 0 580 64478 8ICS 29.050Compliance with a British Standard cannot confer im
5、munity from legal obligations.This was published under the authority of the Standards Policy and Strategy Committee on 31 December 2012.Amendments/corrigenda issued since publicationDate Text affectedBRITISH STANDARDPD CLC/TR 50480:2011This publication does not purport to include all the necessary p
6、rovisions of a contract. Users are responsible for its correct application.Published Document 480TECHNICAL REPORT CLC/TR 50480 RAPPORT TECHNIQUE TECHNISCHER BERICHT February 2011 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisch
7、es Komitee fr Elektrotechnische Normung Management Centre: Avenue Marnix 17, B - 1000 Brussels 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. CLC/TR 50480:2011 E ICS 29.050 Supersedes R064-003:1998English version Determination
8、of cross-sectional area of conductors and selection of protective devices Dtermination des sections des conducteurs et choix des dispositifs de protection Festlegung von Leiterquerschnitten und Auswahl von Schutzeinrichtungen This Technical Report was approved by CENELEC on 2011-01-02. CENELEC membe
9、rs are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia
10、, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. - 2 - Foreword This Technical Report was prepared by CENELEC Technical Committee 64, Electrical installations and protection against electric shock. The text of the draft was circulated for voting in accordance with the Internal Regulati
11、ons, Part 2, Subclause 11.4.3.3 (simple majority) and was approved by CENELEC as CLC/TR 50480 on 2011-01-13. This Technical Report supersedes R064-003:1998. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and CENELEC shall not
12、 be held responsible for identifying any or all such patent rights. _ PD CLC/TR 50480:2011 CLC/TR 50480:2011 (E)- 3 - Contents Foreword . - 2 - Introduction - 5 -1 Scope . - 6 -2 Reference documents - 7 -3 Symbols . - 8 -4 Parameters - 13 -4.1 General - 13 -4.2 Conductor resistances . - 15 -4.3 Cond
13、uctor reactances - 15 -5 Characteristics of installations . - 16 -6 Characteristics of the supply source . - 19 -6.1 Voltage . - 19 -6.2 Supply by HV/LV transformers - 19 -6.3 Supply by generators . - 20 -6.4 Contribution of asynchronous motors - 20 -6.5 LV supply . - 21 -6.6 Capacitors - 21 -7 Char
14、acteristics of protective devices. - 21 -7.1 Circuit-breakers . - 21 -7.2 Fuses . - 22 -8 Protection against overload currents. - 22 -8.1 Current-carrying capacity . - 22 -8.2 Coordination between conductors and overload protective devices - 22 -9 Determination of breaking capacity of protective dev
15、ices - 24 -9.1 General . - 24 -9.2 Three line maximum short-circuit current - 24 -9.3 Line-to-line maximum short-circuit current - 25 -9.4 Line-to-neutral maximum short-circuit current . - 26 -10 Ability to withstand electro-dynamic stresses for busbar trunking systems - 27 -11 Fault protection (pro
16、tection against indirect contact) - 28 -11.1 Disconnecting time - 28 -11.2 Calculation of earth fault current Ief- 28 -12 Verification of thermal stress in conductors . - 29 -12.1 Thermal stress . - 29 -12.2 Minimum short-circuit current - 30 -12.3 Calculation of the minimum short-circuit current .
17、- 31 -13 Voltage drop . - 32 -Annex A Conductor resistances . - 34 -Bibliography . - 44 - National Annex NA (informative)UK National Practice. - -35PD CLC/TR 50480:2011 CLC/TR 50480:2011 (E)- 4 - Figures Figure 1 Examples of installation configurations and impedances used in this document . - 13 -Fi
18、gure 2 Examples of installation configurations and impedances used in this clause - 25 -Tables Table 1 Resistivity at 20 C in accordance with IEC 60909, in mmm / m - 13 -Table 2 Resistivity at various temperatures - 14 -Table 3 Reactance per metre of conductors of cables ( x ) - 14 -Table 4 Selectio
19、n of resistivity and reactance for insulated conductors and cables. - 16 -Table 5 Selection of resistance and reactance for busbar trunking systems . - 17 -Table 6 Elements to take into account when calculating maximum and minimum short circuit currents and earth fault currents. - 18 -Table 7 Voltag
20、e factor c - 19 -Table 8 Values of kM. - 21 -Table 9 Peak factor (n) . - 27 -Table 10 Maximum disconnecting time for TN and TT systems and for IT systems in case of a second fault - 28 -Table 11 Values of the factor k . - 30 -Table A.1 Conductor AC resistances at 20 C, m / m . - 3 -5PD CLC/TR 50480:
21、2011 CLC/TR 50480:2011 (E)- 5 - Introduction The harmonised rules for the erection of electrical low voltage installations, HD 384/HD 60364, require selection, dimensioning and calculation for the components of an electrical installation. In complex installations long and detailed calculations may b
22、e needed. The rules of HD 384/HD 60364 give the basic principles without the details necessary for an accurate application. Computers with appropriate software enable the applicable rules for the determination of conductor cross-section area and selection of protective devices to be applied readily.
23、 It is important that the results of such software programs are in accordance with the harmonised rules. Therefore this Technical Report defines the different reference parameters necessary for the calculation of the cross-sectional area of the conductors and for the selection of the protective devi
24、ces. It also gives the reference methods for calculation according to the different safety rules defined in the Harmonisation Documents of the series HD 384/HD 60364. PD CLC/TR 50480:2011 CLC/TR 50480:2011 (E)- 6 - 1 Scope This Technical Report applies to low-voltage installations with a nominal sys
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- CLCTR504802011DETERMINATIONOFCROSSSECTIONALAREAOFCONDUCTORSANDSELECTIONOFPROTECTIVEDEVICESPDF

链接地址:http://www.mydoc123.com/p-629507.html