1、Designation: F 478 92 (Reapproved 2007)Standard Specification forIn-Service Care of Insulating Line Hose and Covers1This standard is issued under the fixed designation F 478; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year
2、 of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the in-service care, inspection,testing, and use voltage of insulating line hose and co
3、vers forprotection from electrical shock.1.2 The following safety hazards caveat applies only to thetest method portion, Section 7, of this specification: Thisstandard does not purport to address all of the safety problems,if any, associated with its use. It is the responsibility of the userof this
4、standard to establish appropriate safety and healthpractices and determine the applicability of regulatory limita-tions prior to use. Specific precautionary statements are givenin Note 1.2. Referenced Documents2.1 ASTM Standards:2D 1049 Specification for Rubber Insulating CoversD 1050 Specification
5、for Rubber Insulating Line HoseD 2865 Practice for Calibration of Standards and Equip-ment for Electrical Insulating Materials Testing2.2 ANSI Standards:C 84.1 Voltage Ratings for Electric Power Systems andEquipment (60 Hz)32.3 IEEE Standard:IEEE Standard 4, Techniques for High Voltage Testing43. Te
6、rminology3.1 breakdownthe electrical discharge or arc occurringbetween the electrodes and through the equipment being tested.3.2 bulk storage the storage of hose or covers togetherwith one or more layers piled neatly, but without the benefit ofspacers, supports, or special protective containers.3.3
7、coveran electrically insulated enclosure designed tobe installed temporarily on various types of irregularly shapedelectrical equipment to protect personnel and equipment work-ing in the close proximity.3.4 designated personan individual who is qualified byexperience or training to perform an assign
8、ed task.3.5 distortedphysically changed from the natural andoriginal shape, caused by stress of any type.3.6 electrical testing facilitya location with qualified per-sonnel, testing equipment, and procedures for the inspectionand electrical testing of electrical insulating protective equip-ment.3.7
9、electrodethe energized or grounded conductor portionof electrical test equipment which is placed near or in contactwith the material or equipment being tested.3.8 flashoverthe electrical discharge or arc occurringbetween electrodes and over or around, but not through, theequipment being tested.3.9 h
10、osean electrical insulating tube with a longitudinalslit designed to be installed temporarily on energized electricalwires.3.10 ozonea very active form of oxygen that may beproduced by corona, arcing, or ultraviolet rays.3.11 ozone cutting and checkingcracks produced byozone in a material under mech
11、anical stress.3.12 retestthe tests given after the initial acceptance test,usually performed at regular periodic intervals or as requiredbecause of physical inspection.3.13 voltage, maximum usethe a-c voltage (rms) classifi-cation of the protective equipment that designates the maxi-mum nominal desi
12、gn voltage of the energized system that maybe safely worked. The nominal design voltage is equal tophase-to-phase voltage on multiphase circuits.3.13.1 If there is no multiphase exposure in a system area,and the voltage exposure is limited to phase (polarity on d-csystems) to ground potential, the p
13、hase (polarity on d-csystems) to ground potential shall be considered to be thenominal design voltage.1This specification is under the jurisdiction of ASTM Committee F18 onElectrical Protective Equipment for Workers and is the direct responsibility ofSubcommittee F18.25 on Insulating Cover-Up Equipm
14、ent.Current edition approved June 1, 2007. Published July 2007. Originally approvedin 1976. Last previous edition approved in 1999 as F 478 92(1999).2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStanda
15、rds volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.4Available from Institute of Electrical and Electronics Engineers, Inc., 445 HoesLane
16、, Piscataway, NJ 08854-4150.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.13.2 If electrical equipment and devices are insulated, orisolated, or both, such that the multiphase exposure on agrounded wye circuit is removed, then th
17、e nominal designvoltage may be considered as the phase-to-ground voltage onthat circuit.3.14 voltage, maximum retestvoltage, either a-c rms ord-c average, that is equal to the proof test voltage for newprotective equipment.3.15 voltage, nominal designa nominal value consistentwith the latest revisio
18、n of ANSI C 84.1, assigned to the circuitor system for the purpose of conveniently designating itsvoltage class.3.16 voltage, retest voltage, either a-c rms or d-c average,that used protective equipment must be capable of withstand-ing for a specific test period without breakdown.4. Significance and
19、 Use4.1 Compliance with this specification should continue toprovide personnel with insulating line hose and covers ofknown and acceptable quality after initial acceptance in accor-dance with Specifications D 1050 and D 1049. The standardsherein are to be considered as minimum requirements.4.2 A mar
20、gin of safety shall be provided between themaximum use voltage and their class proof voltage in accor-dance with Specifications D 1050 and D 1049, as shown inTable 1.4.3 The user of this type of protective equipment shall beknowledgeable of and instructed in the correct and safeinspection and use of
21、 this equipment.5. Classification5.1 Line hose covered in this specification are designed asType I or Type II; Class 0, Class 1, Class 2, Class 3 or Class 4;Style A, Style B, Style C or Style D. Covers covered in thisstandard are designated as Type I or Type II; Class 0, Class 1,Class 2, Class 3 or
22、Class 4; Style A, Style B, Style C, Style Dor Style E.5.1.1 Type IHigh-grade cis-1,4-polyisoprene rubber com-pound of natural or synthetic origin, properly vulcanized.5.1.2 Type IIOzone resistant, made of any elastomer orcombination of elastomeric compounds.5.1.3 The class designations are based on
23、the electricalproperties in Specifications D 1050 and D 1049.5.1.4 The style designations are based on the designs anddescriptions in Specifications D 1050 and D 1049.6. Washing and Inspection6.1 The recommended sequence of washing and inspectionof contaminated insulating line hose and covers is as
24、follows:6.1.1 Washing,6.1.2 Drying,6.1.3 Inspection,6.1.4 Marking, and6.1.5 Packing for storage and shipment.6.2 The hose and covers may be washed with a soap, mildnon-bleaching detergent, or a cleaner recommended by theequipment manufacturer. After washing, the hose and coversshall be rinsed thorou
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF47819922007STANDARDSPECIFICATIONFORINSERVICECAREOFINSULATINGLINEHOSEANDCOVERS 绝缘 线路 软管 覆盖 使用 保养

链接地址:http://www.mydoc123.com/p-536747.html