ASTM F1669M-2012(2018) Standard Specification for Insulation Monitors for Shipboard Electrical Systems [Metric].pdf
《ASTM F1669M-2012(2018) Standard Specification for Insulation Monitors for Shipboard Electrical Systems [Metric].pdf》由会员分享,可在线阅读,更多相关《ASTM F1669M-2012(2018) Standard Specification for Insulation Monitors for Shipboard Electrical Systems [Metric].pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F1669M 12 (Reapproved 2018) An American National StandardStandard Specification forInsulation Monitors for Shipboard Electrical SystemsMetric1This standard is issued under the fixed designation F1669M; the number immediately following the designation indicates the year oforiginal adopti
2、on or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers two (2) types of electricalsystem insulation mon
3、itoring devices.1.1.1 Type I is an AC device intended as a permanentlyinstalled unit for use in the detection of ohmic insulation faultsto ground in active AC ungrounded electrical systems up to1000 VAC, having DC components up to 1500 VDC.1.1.2 Type II is a DC device intended as a permanentlyinstal
4、led unit for use in the detection of ohmic insulation faultsto ground in DC ungrounded electrical systems up to 1500VDC.1.2 LimitationsThis specification does not cover devicesthat are intended for operation in AC ungrounded systemswithout DC components.1.3 The values stated in SI units are to be re
5、garded asstandard. The values given in parentheses after SI units areincluded for information only and are not considered standard.1.4 The following precautionary caveat pertains only to thetest methods portion, Section 7 of this specification: Thisstandard does not purport to address all of the saf
6、ety concerns,if any, associated with its use. It is the responsibility of the userof this standard to establish appropriate safety, health, andenvironmental practices and determine the applicability ofregulatory limitations prior to use.1.5 This international standard was developed in accor-dance wi
7、th internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 UL Standard:2
8、UL STD 840 Insulation Coordination Including Clearancesand Creepage Distances for Electrical Equipment2.2 IEC Standards:3IEC 255-5 Insulation Tests for Electrical RelaysIEC 364-4-41 Electrical Installations of Buildings/Protection for Safety/Protection Against Electrical Shock2.3 Military Standard:4
9、MIL-STD-1399 (NAVY) Section 300A Interface Standardsfor Shipboard Systems; Electrical Power, AlternatingCurrent3. Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 AC or DC ungrounded electrical system, na systemthat has no intentional connection to ground and can continueto perfor
10、m normally if one conductor becomes connected toground.3.1.2 measuring signal, nthe output signal from the insu-lation monitor that is superimposed between the AC or DCungrounded system to be monitored and ground.3.1.3 response value, nthe adjustable or preset set-pointvalue of the system insulation
11、 resistance at which an insulationmonitor will provide an alarm indication.3.1.4 system leakage capacitance, nthe total capacitanceto ground of the system including all connected consumers.3.1.5 touch voltage, nthe voltage appearing during aninsulation fault, between simultaneously accessible parts.
12、 Thisterm is used only in connection with protection against indirect1This specification is under the jurisdiction of ASTM Committee F25 on Shipsand Marine Technology and is the direct responsibility of Subcommittee F25.10 inElectrical.Current edition approved April 1, 2018. Published May 2018. Orig
13、inallyapproved in 1996. Last previous edition approved in 2012 as F1669M 12. DOI:10.1520/F1669M-12R18.2Available from Underwriters Laboratories (UL), 333 Pfingsten Rd.,Northbrook, IL 60062-2096, http:/.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York,
14、NY 10036, http:/www.ansi.org.4Available from DLA Document Services, Building 4/D, 700 Robbins Ave.,Philadelphia, PA 19111-5094, http:/quicksearch.dla.mil.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was d
15、eveloped in accordance with internationally recognized principles on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.1human contacts,
16、 that is, no direct human contact with a liveconductor. The International Electrotechnical Commission(IEC) limits the maximum prospective touch voltage which canbe maintained indefinitely to 50 VAC rms or 120 V ripple-freeDC.4. Ordering Information4.1 Orders for monitoring devices under this specifi
17、cationshall state the following information:4.1.1 Type and quantity.4.1.2 Nominal system voltage and frequency (for AC sys-tem).4.1.3 Input supply voltage.4.1.4 Response value/set-point range expressed in K-Ohms.4.1.5 ASTM designation and year of issue.4.1.6 System leakage capacitance or data from w
18、hich anestimate of its magnitude can be determined.4.1.7 Special requirements such as Test/Reset buttons,ohmmeters, visual indicators, memory fault retention, and soforth.5. Materials and Manufacturing Methods5.1 The materials and manufacturing methods used shall besuch that the resulting products w
19、ill conform to the propertiesand characteristics prescribed in this specification.6. Performance Requirements6.1 Response of Insulation Monitor to a Step Input Theinsulation monitor measures the combined parallel resistanceto ground from all power or circuit conductors. The time torespond to a step
20、change in the actual resistance to a value lessthan or equal to 50 % of the desired response value shall begoverned by the expression:t s! #100140 RI3 Cs! (1)where:RI= internal resistance of monitor, ohm, andCs= total system capacitance, farad.For example,t 5 124 sifRI5 120000 ohm and Cs5 5 31026far
21、ad6.2 Measuring Signal Voltage LimitsThe peak value of themeasuring signal shall under all operating conditions be limitedto a magnitude deemed acceptable by applicable safety stan-dards for the intended use. The peak value of the measuringsignal shall be less than the touch voltage limits: 120 VDCr
22、ipple-free and 50 VAC rms.6.3 Internal Impedance and Internal ResistanceThe ACinternal impedance and DC internal resistance shall be at least30 ohms per volt nominal system voltage but in either caseshall not be less than 12 K-Ohms.6.4 Response ToleranceThe response tolerance of themonitor shall not
23、 exceed 0 to +50 % of the upper value of theset point range when measured at a room temperature of 25 65C (72 6 9F), with an input supply voltage 80115 % of itsnominal value and with a system leakage capacitance equal tothe value at which the monitor is calibrated (1 fd minimum).6.5 Working Range of
24、 System Voltage and Frequency Theinsulation monitor shall perform as specified when operatingwith a system voltage of 0115 % nominal over the frequencyrange 50400 hz.6.6 Self-TestThe insulation monitor shall include a built-intest device or be equipped with connection provisions for aseparate device
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF1669M20122018STANDARDSPECIFICATIONFORINSULATIONMONITORSFORSHIPBOARDELECTRICALSYSTEMSMETRICPDF

链接地址:http://www.mydoc123.com/p-535369.html