ASTM D5424-2014 red 8023 Standard Test Method for Smoke Obscuration of Insulating Materials Contained in Electrical or Optical Fiber Cables When Burning in a Vertical Cable Tray Co.pdf
《ASTM D5424-2014 red 8023 Standard Test Method for Smoke Obscuration of Insulating Materials Contained in Electrical or Optical Fiber Cables When Burning in a Vertical Cable Tray Co.pdf》由会员分享,可在线阅读,更多相关《ASTM D5424-2014 red 8023 Standard Test Method for Smoke Obscuration of Insulating Materials Contained in Electrical or Optical Fiber Cables When Burning in a Vertical Cable Tray Co.pdf(28页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D5424 10D5424 14Standard Test Method forSmoke Obscuration of Insulating Materials Contained inElectrical or Optical Fiber Cables When Burning in a VerticalCable Tray Configuration1This standard is issued under the fixed designation D5424; the number immediately following the designation
2、 indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This is a fire-test-response standar
3、d.1.2 This test method provides a means to measure the smoke obscuration resulting from burning electrical insulating materialscontained in electrical or optical fiber cables when the cable specimens, excluding accessories, are subjected to a specified flamingignition source and burn freely under we
4、ll ventilated conditions.1.3 This test method provides two different protocols for exposing the materials, when made into cable specimens, to an ignitionsource (approximately 20 kW), for a 20 min test duration. Use it to determine the flame propagation and smoke releasecharacteristics of the materia
5、ls contained in single and multiconductor electrical or optical fiber cables designed for use in cabletrays.1.4 This test method does not provide information on the fire performance of electrical or optical fiber cables in fire conditionsother than the ones specifically used in this test method, nor
6、 does it measure the contribution of the cables to a developing firecondition.1.5 Data describing the burning behavior from ignition to the end of the test are obtained.1.6 The production of light obscuring smoke is measured.1.7 The burning behavior is documented visually, by photographic or video r
7、ecordings, or both.1.8 The test equipment is suitable for making other, optional, measurements, including the rate of heat release of the burningspecimen, by an oxygen consumption technique and weight loss.1.9 Another set of optional measurements are the concentrations of certain toxic gas species i
8、n the combustion gases.1.10 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.(See IEEE/ASTM SI 10.)1.11 This standard measures and describes the response of materials, products, or assemblies to heat and flame under controlledc
9、onditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, productsor assemblies under actual fire conditions.1.12 Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conductingthe
10、se tests.1.13 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatorylimitations prior to use.2. Refe
11、renced Documents2.1 ASTM Standards:2D1711 Terminology Relating to Electrical Insulation1 This test method is under the jurisdiction of ASTM Committee D09 on Electrical and Electronic Insulating Materials and is the direct responsibility of SubcommitteeD09.21 on Fire Performance Standards.Current edi
12、tion approved March 1, 2010Nov. 1, 2014. Published April 2010November 2014. Originally approved in 1993. Last previous edition approved in 20052010as D5424D5424 10.05. DOI: 10.1520/D5424-10.10.1520/D5424-14.2 For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer
13、Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summary page on the ASTM website.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the pre
14、vious version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.*A Summary of Ch
15、anges section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1E84 Test Method for Surface Burning Characteristics of Building MaterialsE176 Terminology of Fire StandardsE800 Guide for Measurement of
16、Gases Present or Generated During FiresE1354 Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen ConsumptionCalorimeterIEEE/ASTM SI 10 Standard for Use of the International System of Units (SI): The Modern Metric System2.2 NFPA Standard:Standards:3ANSI/NFP
17、A 70-1990NFPA 70 National Electrical Code1990, National Fire Protection AssociationCodeNFPA 289 Standard Method of Fire Test for Individual Fuel Packages2.3 Underwriters Laboratories Standards:4UL 1056 Fire Test of Upholstered Furniture, Underwriters Laboratories, 1989UL 1581 Reference Standard for
18、Electrical Wires, Cables, and Flexible Cords, March 6, 1987, Underwriters Laboratories, Inc.,ANSI/UL 1581-1985CordsUL 1685 Standard Vertical Tray Fire Propagation and Smoke Release Test for Electrical and Optical Fiber Cables, UnderwritersLaboratories, Inc., January 27, 1992Cables2.4 Canadian Standa
19、rds Association Standards:5CSA Standard FT-4 Vertical Flame Tests: Cables in Cable Trays, Section 4.11.4 in C22.2 No. 0.3-M1985,0.3, Test Methods forElectrical Wires and Cables2.5 IEEE Standards:6IEEE 1202 Standard for Flame Testing of Cables for Use in Cable Tray in Industrial and Commercial Occupa
20、ncies, May 29,1991.Occupancies2.6 Other Standards:CA Technical Bulletin 133 Flammability Test Procedure for Seating Furniture for Use in Public Occupancies, January, 19917Nordtest Method NT Fire 032 Upholstered Furniture: Burning BehaviorFull Scale Test8ISO 13943 Fire SafetyVocabulary93. Terminology
21、3.1 DefinitionsFor definitions of terms used in this test method and associated with fire issues, refer to Terminology E176 andISO 13943. In case of conflict, the definitions given in Terminology E176 shall prevail. For definitions of terms used in this testmethod and associated with electrical insu
22、lation issues, refer to Terminology D1711.3.2 Definitions of Terms Specific to This Standard:3.2.1 sample, nan amount of the cable type and construction to be tested, which is representative of the product for test.3.2.2 specimen, nthe individual length of cable, or cable bundle, to be placed in the
23、 cable tray, which is representative of theproduct to be tested.4. Summary of Test Method4.1 This fire-test-response standard determines a number of fire-test-response characteristics associated with smoke obscurationresulting from burning the materials insulating full-scale specimens of electrical
24、or optical fiber cables located in a vertical cabletray and ignited with a propane gas burner. This test method is also suitable for making other, optional measurements, includingrates of heat release, total amounts of heat released, rates and concentrations of carbon oxides released, and rates and
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD54242014RED8023STANDARDTESTMETHODFORSMOKEOBSCURATIONOFINSULATINGMATERIALSCONTAINEDINELECTRICALOROPTICALFIBERCABLESWHENBURNINGINAVERTICALCABLETRAYCOPDF

链接地址:http://www.mydoc123.com/p-519745.html