ASTM C1534-2007e1 Standard Specification for Flexible Polymeric Foam Sheet Insulation Used as a Thermal and Sound Absorbing Liner for Duct Systems《用作管道系统吸热吸声衬垫的软质聚合物泡沫薄片的标准规范》.pdf
《ASTM C1534-2007e1 Standard Specification for Flexible Polymeric Foam Sheet Insulation Used as a Thermal and Sound Absorbing Liner for Duct Systems《用作管道系统吸热吸声衬垫的软质聚合物泡沫薄片的标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1534-2007e1 Standard Specification for Flexible Polymeric Foam Sheet Insulation Used as a Thermal and Sound Absorbing Liner for Duct Systems《用作管道系统吸热吸声衬垫的软质聚合物泡沫薄片的标准规范》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1534 071Standard Specification forFlexible Polymeric Foam Sheet Insulation Used as aThermal and Sound Absorbing Liner for Duct Systems1This standard is issued under the fixed designation C1534; the number immediately following the designation indicates the year oforiginal adoption or,
2、in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1NOTESection 1.3 was editorially revised in April 2010.1. Scope1.1 This specification covers
3、the composition, dimensions,and physical properties of flexible unfaced foam sheet, used toinsulate interior surfaces of HVAC ducts, plenums and equip-ment used for the distribution of conditioned air with atemperature of up to 250F (121C).1.2 HVAC ducts, plenums and equipment systems typicallyopera
4、te between a temperature range of 50F to 150F (10C to65C) and are designed to meet building code requirements ofmaximum temperatures of 250F (121C).1.3 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that ar
5、e provided for information onlyand are not considered standard.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applic
6、a-bility of regulatory requirements prior to use.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationC177 Test Method for Steady-State Heat Flux Measure-ments and Thermal Transmission Properties by Means ofthe Guarded-Hot-Plate ApparatusC209 Test Methods for Cel
7、lulosic Fiber Insulating BoardC390 Practice for Sampling and Acceptance of ThermalInsulation LotsC411 Test Method for Hot-Surface Performance of High-Temperature Thermal InsulationC423 Test Method for Sound Absorption and Sound Ab-sorption Coefficients by the Reverberation Room MethodC518 Test Metho
8、d for Steady-State Thermal TransmissionProperties by Means of the Heat Flow Meter ApparatusC634 Terminology Relating to Building and EnvironmentalAcousticsC665 Specification for Mineral-Fiber Blanket Thermal In-sulation for Light Frame Construction and ManufacturedHousingC1045 Practice for Calculati
9、ng Thermal Transmission Prop-erties Under Steady-State ConditionsC1071 Specification for Fibrous Glass Duct Lining Insula-tion (Thermal and Sound Absorbing Material)C1104/C1104M Test Method for Determining the WaterVapor Sorption of Unfaced Mineral Fiber InsulationC1114 Test Method for Steady-State
10、Thermal TransmissionProperties by Means of the Thin-Heater ApparatusC1304 Test Method for Assessing the Odor Emission ofThermal Insulation MaterialsC1338 Test Method for Determining Fungi Resistance ofInsulation Materials and FacingsE84 Test Method for Surface Burning Characteristics ofBuilding Mate
11、rialsE176 Terminology of Fire StandardsE795 Practices for Mounting Test Specimens During SoundAbsorption TestsE2231 Practice for Specimen Preparation and Mounting ofPipe and Duct Insulation Materials to Assess SurfaceBurning CharacteristicsG21 Practice for Determining Resistance of Synthetic Poly-me
12、ric Materials to Fungi2.2 Other Standards:CAN/ULC-S10203 Standard Method of Test for SurfaceBurning Characteristics of Building Materials and Assem-blies3. Terminology3.1 The definitions of terms used in this specification shallbe in accordance with Terminologies C168, C634, and E176.Incase of any c
13、onflicts, Terminology C168 shall be the authority.1This specification is under the jurisdiction of ASTM Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.22 onOrganic and Nonhomogeneous Inorganic Thermal Insulations.Current edition approved Sept. 1, 2007. Publis
14、hed September 2007. Originallyapproved in 2002. Last previous edition approved in 2004 as C153404. DOI:10.1520/C1534-07.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer
15、 to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.2 Definitions of Terms Specific to This Standard:3.2.1 closed cell foama foam comprised of predominatelyindividual non inter
16、connecting cells.3.2.2 flexible cellulara cellular material that will notrupture within 60 s when a specimen 1 3 1 3 8 in. in length(25 3 25 3 200 mm) is bent around a 1 in. (25 mm) diametermandrel at a uniform rate of one lap in5sintheform of a helixat a temperature between 65 and 85F (18 and 29C).
17、3.2.3 open cell foama foam made porous by interconnect-ing cells.4. Classification4.1 The flexible polymeric insulations of this specificationare classified into Types I and II. Type I is a closed flexiblefoam. Type II is an open cell flexible foam.NOTE 1The primary difference between Type I and Typ
18、e II materialsare: Type I materials exhibit lower water absorption properties and TypeII materials have greater acoustical properties as noted in Tables 1 and 2.5. Materials5.1 These products shall be made of a homogeneous blendof natural or synthetic polymeric materials. Modifications withvarious t
19、hermoplastic or thermosetting resins, plasticizers,modifiers, antioxidants, curatives, blowing agents and otheradditives are allowed. These products do not melt whenexposed to heat and are considered to be thermoset materials.5.2 Flexible, polymeric cellular thermal insulations shall beof uniform co
20、re density. These insulation materials are avail-able with a smooth skin surface or coating on one or both sides,and they are to be considered homogeneous for the purposes ofdetermining thermal performance.6. Ordering Information6.1 Specific installation, insulation type, thickness, length,and width
21、 suited for the intended use shall be agreed upon bythe purchaser and supplier.7. Physical PropertiesSee Tables 1 and 2 for Summaryof Requirements7.1 Apparent Thermal ConductivityThe material shall betested for apparent thermal conductivity at 75F (24C) meantemperature in accordance with 12.1. The t
22、hermal conductivityfor the average of any four randomly selected samples, shallnot be more than 0.30 Btu-in./h-sq ftF (0.043 W/m-K) whentested in accordance with 12.1. See Table 1.NOTE 2Consult the local or state building codes for the minimuminstalled thermal resistance, R-value, required to be ins
23、talled.7.2 Surface Burning CharacteristicsShall be in accor-dance with 12.2. See Table 1 for requirements.7.3 Hot Surface PerformanceThe insulation shall have noevidence of flaming, glowing, smoldering, visible smoke,delamination, cracking, warpage, melting, dripping or reduc-tion in thickness when
24、tested in accordance with 12.3 at thetemperature specified in Table 1.NOTE 3Hot Surface Performance Characteristics for Type 1MaterialWhen this type of material is used on hot applications, thematerials characteristics will change and should be considered whenselecting the material for an applicatio
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC15342007E1STANDARDSPECIFICATIONFORFLEXIBLEPOLYMERICFOAMSHEETINSULATIONUSEDASATHERMALANDSOUNDABSORBINGLINERFORDUCTSYSTEMS

链接地址:http://www.mydoc123.com/p-465038.html