1、Designation: B416 98 (Reapproved 2018)Standard Specification forConcentric-Lay-Stranded Aluminum-Clad Steel Conductors1This standard is issued under the fixed designation B416; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the ye
2、ar of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers bare concentric-lay-strandedconductors made from bare, hard-drawn, round, aluminum-cla
3、d steel wires of 20.3 % conductivity for general use ofelectrical purposes. This specification does not apply tostranded conductors for reinforcement in ACSR conductors.1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversion
4、s to SI units that are provided for information onlyand are not considered standard.1.3 This international standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Gui
5、des and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 The following documents of the issue in effect on dateof material purchase form a part of this specification to theextent referenced herein:2.2 ASTM Standards:2B354 T
6、erminology Relating to Uninsulated Metallic Electri-cal ConductorsB415 Specification for Hard-Drawn Aluminum-Clad SteelWire2.3 Other Documents:C8.1 Definitions and General Standards for Wires andCables3NBS Handbook 100 Copper Wire Tables of the NationalInstitute of Standards and Technology43. Descri
7、ption of Conductor3.1 The designation of the finished conductor shall beexpressed as the number of wires and the diameter of theseindividual wires, usually expressed as the AWG size of thewires.4. Ordering Information4.1 Orders for material under this specification shall includethe following informa
8、tion:4.1.1 Quantity of each size,4.1.2 Conductor size expressed as number and AWG size ofindividual wires (Section 3 and Table 1),4.1.3 Direction of lay of outer layer, if other than left-hand(see 6.3),4.1.4 Package size (see 15.1),4.1.5 Special package markings if required (see 15.3),4.1.6 Special
9、lagging if required (see 15.2), and4.1.7 Place of inspection if other than place of manufacture(Section 13).5. Joints5.1 Joints or splices may be made in the finished individualaluminum-clad steel wires composing concentric-lay strandedconductors using more than three wires, provided that suchjoints
10、 or splices have a protection and electrical conductanceequivalent to that of the wire itself and that they do notdecrease the strength of the finished stranded conductor belowthe minimum breaking strength shown in Table 1. Such jointsor splices shall be not closer than 50 ft (15 m) to any other joi
11、ntin the same layer in the conductor.NOTE 1Joints are made by electrical butt-welding. The ends must becut and the end of each wire must be straightened for a distance of 12 to15 in. (300 to 380 mm). The proper sleeve is slipped over the end of oneof the wires. The wires are then butt-welded and dre
12、ssed off to a finisheddiameter equal to that of the wire. The weld area is then tempered, thesleeve centered over the weld area and compressed to provide a finishedjoint that is smooth and neat in appearance. This joint has a tensile strengthof approximately 90 % of rated breaking strength of the wi
13、re, but anallowance is made for this in the rated strength of the conductor as awhole. The completed conductor when containing such joints is required1This specification is under the jurisdiction of ASTM Committee B01 onElectrical Conductors and is the direct responsibility of Subcommittee B01.06 on
14、Bi-Metallic Conductors.Current edition approved Oct. 1, 2018. Published October 2018. Originallyapproved in 1964. Last previous edition approved in 2013 as B416 98 (2013).DOI: 10.1520/B0416-98R18.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at
15、 serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.4Available from National Institute of
16、Standards and Technology (NIST), 100Bureau Dr., Stop 1070, Gaithersburg, MD 20899-1070, http:/www.nist.gov.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordance with internationally rec
17、ognized principles on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.1to have the full rated strength.6. Lay6.1 For 3-wire conductor
18、s, the preferred lay is 1612 timesthe outside diameter, but the lay shall not be less than 14 timesnor more than 20 times this diameter.6.2 For 7, 19, and 37-wire conductors, the preferred lay is1312 times the diameter of that layer, but the lay shall not beless than 10 nor more than 16 times this d
19、iameter.6.3 The direction of lay of the outer layer shall be left-handunless the direction of lay is specified otherwise by thepurchaser.6.4 The direction of lay shall be reversed in consecutivelayers.6.5 All wires in the conductor shall lie naturally in their truepositions in the completed conducto
20、r. They shall tend to remainin position when the conductor is cut at any point and shallpermit restranding by hand after being forcibly unraveled at theend of the conductor.7. Strength of Conductor7.1 The breaking strength of the completed conductorscomposed of 7 wires, 19 wires, and 37 wires shall
21、be taken as90 % of the sum of the breaking strengths of the aluminum-clad wires, calculated from their nominal diameter and theappropriate specified minimum tensile strength given in Table1, Tensile Requirements, of Specification B415 (20 % columnonly). The breaking strength of completed conductors
22、com-posed of 3 wires shall be taken as 95 % of the sum of thebreaking strengths of the aluminum-clad wires calculated in thesame manner.8. Construction8.1 The number and diameter of the wires in the concentric-lay stranded conductors shall conform to the requirementsprescribed in Table 1.NOTE 2For d
23、efinitions of terms relating to conductors, referenceshould be made to ANSI C8.1 and Terminology B354.9. Physical and Electrical Tests9.1 Tests for physical and electrical properties of wirescomposing concentric-lay stranded conductors made fromaluminum-clad steel wire shall be made before stranding
24、.9.2 At the option of the purchaser, tension and elongationtests before stranding may be waived and the completeconductors may be tested as a unit. The breaking strength of theconductors so tested shall be not less than that required in Table1.9.3 Where breaking strength tests are required on thefin
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMB41619982018STANDARDSPECIFICATIONFORCONCENTRICLAYSTRANDEDALUMINUMCLADSTEELCONDUCTORSPDF

链接地址:http://www.mydoc123.com/p-461174.html