ASHRAE OR-16-C031-2016 Field Study of Energy Use-Related Effects of Ultraviolet Germicidal Irradiation of a Cooling Coil.pdf
《ASHRAE OR-16-C031-2016 Field Study of Energy Use-Related Effects of Ultraviolet Germicidal Irradiation of a Cooling Coil.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-16-C031-2016 Field Study of Energy Use-Related Effects of Ultraviolet Germicidal Irradiation of a Cooling Coil.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Joseph Firrantello is a doctoral candidate in the Department of Architectural Engineering, The Pennsylvania State University, University Park, PA. William Bahnfleth is a professor in the Department of Architectural Engineering and director of the Indoor Environment Center, The Pennsylvania State Uni
2、versity. Ross Montgomery is owner of Quality Systems and Technologies, Parrish, FL. Paul Kremer is a Research Associate in the Department of Architectural Engineering, The Pennsylvania State University. Field Study of Energy Use-Related Effects of Ultraviolet Germicidal Irradiation of a Cooling Coil
3、 Joseph Firrantello, PE Member ASHRAE Ross Montgomery, PE Paul Kremer Fellow ASHRAE ABSTRACT The energy use-related effects of ultraviolet germicidal irradiation (UVGI) to mitigate biological fouling (biofouling) of a chilled water cooling coil are investigated via a field study. A visibly bio-foule
4、d cooling coil in an air-handling unit serving an operational building in a hot, humid climate is monitored for 5 months to establish a fouled coil baseline. Parameters monitored include air flow rate, airside pressure drop, air temperature and humidity upstream and downstream of the coil, chilled w
5、ater flow rate, entering and leaving chilled water temperature, and waterside pressure drop. A UVGI coil irradiation system is installed on the downstream side of the coil following typical manufacturer guidelines, and the system is then passively monitored over a period of 14 months. The change in
6、operation is estimated by comparing data from the baseline and post-irradiation periods. The 95% confidence intervals for average improvement of coil airside pressure drop and heat transfer coefficient are 11.07% to 11.13%, and 14.5% to 14.6%, respectively. Complexities of the physical phenomena inv
7、olved, in particular, the combined effect of airflow and latent load on airside pressure drop, are taken into account. INTRODUCTION Finned tube cooling coils play a key role in the operation of air-conditioning systems. Coils are susceptible to fouling by particulate matter impinging on their closel
8、y spaced fins. Condensate that wets coil surfaces during operation helps to capture particles and also promotes microbial growth. Fouling increases airside pressure drop across a coil and decreases the air to water or refrigerant heat transfer coefficient. Both effects can increase energy use of an
9、HVAC system significantly. This investigation considers the biofouling of chilled water coils and its mitigation by low power ultraviolet germicidal irradiation (UVGI) systems. BACKGROUND Airside Biofouling of Cooling Coils Heat exchanger fouling is the buildup of organic and/or inorganic matter on
10、the heat transfer surfaces. Cooling coils, due to the close spacing of fins on the air side (10 to 15 fins per inch or 4 to 6 per cm), can act as particulate William Bahnfleth, PhD, PE Fellow ASHRAE filters and trap material such as dust, hair, debris, and microbes. Coil surfaces, by design, become
11、wet during operation in many applications, thereby presenting growth opportunities for impacted microbes. A number of studies quantify the benefits of cleaning a fouled coil. Most of these studies consider mechanical or chemical coil cleaning and do not distinguish between different types of fouling
12、. Montgomery and Baker (2006) describe a coil cleaning case study performed on two air-handling units (AHUs) serving part of a 34-story office building in New York City. Cleaning of coils resulted in a 14% decrease in pressure drop across the coils, an increase in ability to transfer sensible loads
13、of 25%, and an increase of 10% for latent loads. Overall, coil cleaning appeared to have the potential to save 10%-15% in HVAC system energy consumption. Yang, Braun, and Groll (2004; 2007a; 2007b) describe the energy use effects of coil fouling as measured in a laboratory study. The authors found t
14、hat the energy penalty from the increased pressure drop across the cooling coil was more significant than that from the change in heat transfer coefficient. In some cases with lower amounts of fouling, the heat transfer coefficient was found to increase due to an increase in air velocity, but this w
15、as offset by the increased thermal resistance as fouling accumulates. Biological particles that deposit and grow on a cooling coil contribute to increased energy use and IAQ problems (Siegel and Walker 2001; Siegel and Carey 2001). Single pass deposition in these studies ranged from 1% for 1.1 m par
16、ticles at low velocities of around 200 fpm (1.02 m/s), to 30% for 8 m particles at high velocities of 1024 fpm (5.2 m/s). Ali and Ismail (2008) collected fouling material from room air conditioners, classified its biological and non-biological components, deposited it in increasing amounts on a DX c
17、ooling coil in a laboratory apparatus, and measured the resulting degradation in performance. The organic component of the fouling material comprised 18.4% of the mass on the upstream face of the coil and 1.2% on the downstream face. The organic component consisted of masses of Aspergillus fungal co
18、lonies. The coefficient of performance (COP) of the unit dropped from a clean value of 2.82 to fouled values of 1.89, 1.73, and 1.23 after the injection of 100g, 200g, and 300g (0.22 lbm, 0.44 lbm, and 0.66 lbm ) of fouling material, respectively. Pu et al. (2010) seeded a cooling coil with biologic
19、al material and recorded the airside pressure drop and heat transfer coefficient resulting from different levels of fouling after 28 days of growth. They found a range of -15.6% to 13.1% for the heat transfer coefficient and 19.8% to 43.1% for the air-side pressure drop fouling factors. UVGI for Con
20、trol of Biofouling The UVC (or UV-C) wavelength band of ultraviolet light inactivates biological organisms by disrupting their DNA and rendering them unable to reproduce. UVC generated by low pressure mercury vapor lamps is used both for air and surface disinfection in HVAC systems. The basics of UV
21、GI coil treatment systems are described by ASHRAE (2008) and Kowalski (2009), which both review numerous sources on the subject. The devices are installed upstream, downstream, or on both sides of the coil. Bahnfleth (2011) provides a recent review of the technology used in air handlers and summariz
22、es published reports of its effectiveness. At the time of its publication, there were no peer-reviewed studies of the energy use impacts of UVGI for coil treatment applications. Several published reports describe the ability of coil surface UVGI to mitigate or prevent coil fouling but without quanti
23、tatively assessing the impact on system energy use. For example, Shaughnessy, Rogers, and Levetin (1998) documented the effectiveness of UVC in reducing contaminant concentrations on various AHU surfaces, and did extensive microbe classification, but did not measure energy impacts. Levetin et al. (2
24、001) also demonstrated the effectiveness of UVGI in reducing surface contamination without reporting energy use-related data. In a brief trade magazine article (Steril-Aire 2000a, 200b), a manufacturer describes the installation of UVC surface treatment technology in a facilitys twenty AHUs to addre
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR16C0312016FIELDSTUDYOFENERGYUSERELATEDEFFECTSOFULTRAVIOLETGERMICIDALIRRADIATIONOFACOOLINGCOILPDF

链接地址:http://www.mydoc123.com/p-455755.html