IEEE 65-1956 - AIEE Proposed Test Procedure for Thermal Evaluation of Ventilated Dry-Type Power and Distribution Transformers.pdf
《IEEE 65-1956 - AIEE Proposed Test Procedure for Thermal Evaluation of Ventilated Dry-Type Power and Distribution Transformers.pdf》由会员分享,可在线阅读,更多相关《IEEE 65-1956 - AIEE Proposed Test Procedure for Thermal Evaluation of Ventilated Dry-Type Power and Distribution Transformers.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、(E ST*?! AIEE No. 65 Nov. 1956 .r MR VNS Rwove /V/Msedf Tesf Procedure for THERMAL EVALUATION of VENTILATED DRY-TYPE POWER and DISTRIBUTION TRANSFORMERS (Published for trial use) 10 Published by AMERICAN INSTITUTE OF ELECTRICAL ENGINEERS 33 West Thirty-ninth Street, New York 18, N. Y. PREFACE For ma
2、ny years, temperature limits for electric appa ratus have been founded upon classification of insulating materials by broad general definitions based upon chemi cal composition1. Recently, it has become apparent that this method no longer meets the needs of the industry and that a new approach is ne
3、eded, based upon functional tests.w66 The latest revision of AIEE No. I1 recognizes this need by the following statement: The electrical insulation of equipment is made up of many different components, selected to withstand the widely different electric, mechanical and thermal stresses occurring in
4、different parts of the structure. To assure satisfactory service life, therefore, insulation specifica tions need to be supported by service experience or life tests, on the complete insulation system. Accelerated life tests are increasingly important as a means of evaluating the many new synthetic
5、insulating materials that are available, thus shortening the period of service experience required before they can be used with confi dence. It is desirable that life tests on materials be supplemented by tests on complete insulation systems, representative of the different types of equipment. It is
6、 contemplated that, in the course of time, Insti tute Test Codes will be developed, giving procedures for such accelerated life tests, and other methods of evaluating insulating materials and systems. Accordingly, this test procedure is intended to establish methods for evaluating the insulating sys
7、tems of venti lated dry-type power and distribution transformers. It is expected that test procedures covering other classes of transformers will be prepared from time to time as the lengthy but necessary study and trials are completed. During the preparation of this test procedure, members of the s
8、ubgroup built and tested more than fifty trans former models in accordance with the recommended methods. The results demonstrated that the methods are workable, even though there were a few details on which further work will be necessary before final decisions can be made. The test procedure, theref
9、ore, is offered for trial use in order to obtain wider distribution and to encourage discussion, criticism, and trial by others. ACKNOWLEDGEMENT Acknowledgment and thanks are extended to those who have so freely given their time and knowledge and have conducted experimental work on which this test c
10、ode is based. The major work of preparing the code and trying out its procedures was done by the Subgroup on Functional Tests for Dry-Type Transformers of the Working Group on Life of Materials, with personnel as follows: Paul Narbut, Chairman T. R. Walters M. L. Manning H. G. Zambell Personnel of t
11、he Working Group on Life of Materials: J. L. Cantwell (chairman) W. C. Farneth W. W. Satterlee C. E. Arntzen W. E. Harrison, Jr. F. J. Vogel L. H. Cardwell F. T. Hausle T. R. Walters F. M. Clark M. L. Manning A. J. Wiltzer T. W. Dakin A. S. Mickley C. P. Xenis J. F. Dexter G. A. Monito H. G. Zambell
12、 2 Proposed Test Procedure of the American Institute of Electrical Engineers THERMAL EVALUATION OF VENTILATED DRY-TYPE POWER AND DISTRffiUTION TRANSFORMERS The object of this Test Procedure is to establish a uniform method for determining operating temperature limits for ventilated dry-type power an
13、d distribution transformers, to give a reasonable life expectancy under normal operating conditions. The subjects covered by this Test Procedure are sub divided according to the following plan: Sections 1 to 7 Basic considerations Sections 10 to 12 Specifications for test samples Sections 20 to 27 T
14、he test procedure Section 30 Reporting Section 1. The test covered by this Test Procedure is intended to give a direct evaluation of the composite insulation system of a dry-type transformer, tested as an integral unit. Section 2. It is the intent of this Test Procedure to have each component of the
15、 composite structure operate and perform during the test under conditions which are as nearly as possible the same as its actual operating conditions in the transformer. Thus, it is intended that each of the com ponents is evaluated in accordance with its actual function. Section 3. The primary agin
16、g factors shall be temperature and time. Section 4. Each test shall be carried out simultaneously on a group consisting of a number of identical samples, sufficient to give the desired statistical accuracy. Section 5. The life of a sample, aged at one temperature, shall be equal to the duration of t
17、emperature exposure during one test cycle, multiplied by the number of cycles to failure, less one half of one cycle. The word “failure“, above, shall be construed to mean any form of dielectric breakdown of insulation or a dielec tric flashover, which may occur on any of the specified electrical te
18、sts. The type of failure shall be reported. Section 6. If a transformer is operated continuously at the per missible maximum hottest-spot temperature, its life ex pectancy will be less than that obtained under usual serv ice conditions. Consequently, and because of the severity of the test condition
19、s specified in this test procedure, the minimum acceptable value of extrapolated life of the test sample shall be taken as 4 years (35,000 hours). Ex perience and experimental evidence indicate that attain ment of this nominal life under test results in a service life comparable to that of dry-type
20、transformers now in use. Section 7. Tests specified in this Test Procedure are of an ac celerated nature. Hence, extrapolation of the life obtained at the test temperature is required in order to obtain the temperature limit for normal life expectancy. Furthermore, a certain amount of variation in t
21、he life of individual samples tested at the same temperature is to be expected. In order to insure valid results obtained from such data, free of bias, and suitable for comparative studies, the test data shall be reduced statistically, according to procedure given in Appendix II, and the results rep
22、orted according to Section 30. Tests may be carried out in accordance with Method 2, described below, when ap plicable ; otherwise, Method 1 shall be used. Extrapolations indicated in Section 30 shall be applied only for failures occurring in the same part of the insulat ing system. Should failures
23、be occurring in more than one part of the system, data for each mode of failure shall be treated separately from others. Likewise, the temperature class shall be determined by extrapolation separately for each mode of failure, and the lowest value obtained shall be used as representing the temperatu
24、re class for the complete transformer. a. Method 1. This method shall be used when incomplete informa tion is available regarding the life of the insulating materials involved, or the life-temperature dependence. At least three groups of samples shall be tested at three (or more) different temperatu
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- IEEE651956AIEEPROPOSEDTESTPROCEDUREFORTHERMALEVALUATIONOFVENTILATEDDRYTYPEPOWERANDDISTRIBUTIONTRANSFORMERSPDF

链接地址:http://www.mydoc123.com/p-344765.html