1、Accredited Standards Committee C2-2012 25 April 2013 Insert to STDPT97085 Errata to 2012 Edition National Electrical Safety CodeCorrection Sheet Issued 29 April 2013 The following corrections should be made: Page 2: There is a typographical error in Rule 011A4. The sentence should contain a closing
2、parenthesis. 4. Street and area lights that provide a supply of lumens where these facilities are supplied by underground or overhead conductors installed and/or maintained under the exclusive control of utilities (including their authorized contractors or other qualified persons). Page 33: There is
3、 an error in Rule 97D2. The last sentence should refer to Rule 93D3. Page 90: There is an error in Table 230-1. The heading for Zone 4 should read “Warm islands located at 0 to 25 degrees latitude.” Page 90: The values in the last two columns of Table 230-1 should not be underlined. Pages 94 and 98:
4、 There is an error in Table 232-1 (m) and Table 232-1 (ft). References to Footnote 25 should be references to Footnote 26. Page 96: There is an error in item (f) of Footnote 10 that appears at the end of Table 232-1 (m). Item (f) should contain “215C4 or.” (f) Grounded guys, guys meeting Rules 279A1
5、 and 215C4 or 215C5 exposed to 0 to 300 V 2.9 Page 96: There is an error in Footnote 15 that appears at the end of Table 232-1 (m). The word “215C5” should be replaced with “215C4.” The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance as gro
6、unded guys. Copyright 2013 by the Institute of Electrical and Electronics Engineers, Inc. All rights reserved. Published 2013. Printed in the United States of America. This correction sheet may be freely reproduced and distributed in order to maintain the utility and currency of the underlying Stand
7、ard. This correction sheet may not be sold, licensed, or otherwise distributed for any commercial purposes whatsoever. The content of this correction sheet may not be modified. Accredited Standards Committee C2-2012 25 April 2013 Insert to STDPT97085 Page 97: There are errors that appear at the end
8、of Table 232-1 (m). Although Footnote 25 was deleted from the previous version, it should have been listed as follows. Therefore, the inserted footnote should have been shown as Footnote 26. This footnote not used in this edition. When designing a line to accommodate oversized vehicles, these cleara
9、nce values shall be increased by the difference between the known height of the oversized vehicle and 4.3 m. Pages 97, 98, and 99: There is an error in Table 232-1 (ft). The cells in columns 2 and 5 of the header row should state “(ft)” for feet and not “(m)” for meters. Nature of surface underneath
10、 wires, conductors, or cables Insulatedcommunication conductors and cable; messengers; overhead shield/ surge-protection wires; grounded guys; ungrounded portions of guys meeting Rules 215C4, 215C5, and 279A1 exposed to 0 to 300 V; neutral conductors meeting Rule 230E1; supply cables meeting Rule 23
11、0C1 (ft) Noninsulated communication conductors; supply cables of 0 to 750 V meeting Rule 230C2 or 230C3 (ft) Supply cables over 750 V meeting Rule 230C2 or 230C3; open supply conductors, 0 to 750 V; ungrounded portions of guys meeting Rules 215C4, 215C5, and 279A1 exposed to over 300 V to 750 V(ft)
12、Open supply conductors, over 750 V to 22 kV; unground -ed portions of guys meeting Rules 215C4, 215C5, and 279A1 exposed to 750 V to 22 kV(ft) Trolley and electrified railroad contact conductors and associated span or messenger wires0 to 750 V to ground (ft) Over 750 V to 22 kV to ground (ft) Page 1
13、00: There is an error in item (f) of Footnote 10 that appears at the end of Table 232-1 (ft). Item (f) should contain “215C4 or.” (f) Grounded guys, guys meeting Rules 279A1 and 215C4 or 215C5 exposed to 0 to 300 V 9.5 Page 100: There is an error in Footnote 15 that appears at the end of Table 232-1
14、 (ft). The word “215C5” should be replaced with “215C4.” The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance as grounded guys. Although Footnote 25 was deleted from the previous version, it should have been listed as follows. Therefore, the
15、 inserted footnote should have been shown as Footnote 26. This footnote not used in this edition. When designing a line to accommodate oversized vehicles, these clearance values shall be increased by the difference between the known height of the oversized vehicle and 14 ft. Accredited Standards Com
16、mittee C2-2012 25 April 2013 Insert to STDPT97085 Page129: There are three errors in Figure 234-4(b). At the top of the figure, the two instances of “H” should read “A.” The text associated with “A” in the legend should read “B + 5.5 m (18 ft)” and not “V + 5.5 m (18 ft).” Figure 234-4(b)Clearance e
17、nvelope for grain bins filled by portable augers, conveyors, or elevators Accredited Standards Committee C2-2012 25 April 2013 Insert to STDPT97085 Pages 130, 131, and 132: There is an error in Table 234-1 (m). The cell in column 6 of the header row should contain “ungrounded equipment cases, 750 V
18、to 22 kV.” Clearance of Insulated communication conductors and cables; messengers; overhead shield/ surge-protection wires; grounded guys; ungrounded portions of guys meeting Rules 215C4, 215C5, and 279A1 exposed to 0 to 300 Vneutral conductors meeting Rule 230E1; supply cables meeting Rule 230C1 (m
19、) Supply cables of 0 to 750 V meeting Rule 230C2 or 230C3 (m) Unguarded rigid live parts, 0 to 750 V; noninsulated communication conductors; ungrounded equipment cases, 0 to 750 V; and ungrounded portions of guys meeting Rules 215C4, 215C5, and 279A1 exposed to open supply conductors of over 300 V t
20、o 750 V(m) Supply cables over 750 V meeting Rule 230C2 or 230C3; open supply conductors, 0 to 750 V(m) Unguarded rigid live parts, over 750 V to 22 kV; ungrounded equipment cases, 750 V to 22 kV; ungrounded portions of guys meeting Rules 215C4, 215C5, and 279A1 exposed to over 750 V to 22 kV(m) Open
21、 supply conductors, over 750 V to 22 kV (m) Pages 130, 131, and 132: There are errors in some of the footnotes that appear in Table 234-1 (m). All mentions of Footnote 12 should be Footnote 14. All mentions of Footnote 13 should be Footnote 15. All mentions of Footnote 14 should be Footnote 16. All
22、mentions of Footnote 15 should be Footnote 17. All mentions of Footnote 16 should be Footnote 18. Page 131: The symbol in row 1b(4), first value column of Table 234-1(m), should be replaced with 4.7 since this is a metric table. Page 133: There is an error in Footnote 11 that appears at the end of T
23、able 234-1 (m). The word “215C5” should be replaced with “215C4.” The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance as grounded guys. Although Footnotes 12 and 13 were deleted from the previous version, the remaining footnotes should not
24、have been renumbered. They should be listed as follows: This footnote not used in this edition. This footnote not used in this edition. For clearances above railings, walls, or parapets around balconies, decks, or roofs, use the clearances required for row 1b(1). For such clearances where an outside
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- IEEEC2ERTA2013ERRATATONATIONALELECTRICALSAFETYCODE 国家 电气 安全 规程 勘误 PDF

链接地址:http://www.mydoc123.com/p-1366118.html