1、 6 February 2012 STDPT97085 Accredited Standards Committee C2-2012 Errata to 2012 Edition National Electrical Safety CodeCorrection Sheet Issued 6 February 2012 Copyright 2012 by the Institute of Electrical and Electronics Engineers, Inc. All rights reserved. Published 2012 Printed in the United Sta
2、tes of America. This correction sheet may be freely reproduced and distributed in order to maintain the utility and currency of the underlying Standard. This correction sheet may not be sold, licensed or otherwise distributed for any commercial purposes whatsoever. The content of this correction she
3、et may not be modified. 6 February 2012 STDPT97085 Page 2: There is a typographical error in Rule 011A4. The sentence should contain a closing parenthesis. 4. Street and area lights that provide a supply of lumens where these facilities are supplied by underground or overhead conductors installed an
4、d/or maintained under the exclusive control of utilities (including their authorized contractors or other qualified persons). Page 96: There is an error in item (f) of Footnote 10 that appears at the end of Table 232-1 (m). Item (f) should contain “215C4 or.” (f) Grounded guys, guys meeting Rules 27
5、9A1 and 215C4 or 215C5 exposed to 0 to 300 V 2.9 Page 96: There is an error in Footnote 15 that appears at the end of Table 232-1 (m). The word “215C5” should be replaced with “215C4.” The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance as
6、grounded guys. Page 97: There are errors that appear at the end of Table 232-1 (m). Although Footnote 25 was deleted from the previous version, it should have been listed as follows. Therefore, the inserted footnote should have been shown as Footnote 26. This footnote not used in this edition. When
7、designing a line to accommodate oversized vehicles, these clearance values shall be increased by the difference between the known height of the oversized vehicle and 4.3 m. Pages 97, 98, and 99: There is an error in Table 232-1 (ft). The cells in columns 2 and 5 of the header row should state “(ft)”
8、 for feet and not “(m)” for meters. Nature of surface underneath wires, conductors, or cables Insulatedcommunication conductors and cable; messengers; overhead shield/ surge-protection wires; grounded guys; ungrounded portions of guys meeting Rules 215C4, 215C5, and 279A1 exposed to 0 to 300 V; neut
9、ral conductors meeting Rule 230E1; supply cables meeting Rule 230C1 (ft) Noninsulated communication conductors; supply cables of 0 to 750 V meeting Rule 230C2 or 230C3 (ft) Supply cables over 750 V meeting Rule 230C2 or 230C3; open supply conductors, 0 to 750 V; ungrounded portions of guys meeting R
10、ules 215C4, 215C5, and 279A1 exposed to over 300 V to 750 V(ft) Open supply conductors, over 750 V to 22 kV; unground -ed portions of guys meeting Rules 215C4, 215C5, and 279A1 exposed to 750 V to 22 kV(ft) Trolley and electrified railroad contact conductors and associated span or messenger wires0 t
11、o 750 V to ground (ft) Over 750 V to 22 kV to ground (ft) Page 100: There is an error in item (f) of Footnote 10 that appears at the end of Table 232-1 (ft). Item (f) should contain “215C4 or.” (f) Grounded guys, guys meeting Rules 279A1 and 215C4 or 215C5 exposed to 0 to 300 V 9.5 6 February 2012 S
12、TDPT97085 Page 100: There is an error in Footnote 15 that appears at the end of Table 232-1 (ft). The word “215C5” should be replaced with “215C4.” The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance as grounded guys. Although Footnote 25 w
13、as deleted from the previous version, it should have been listed as follows. Therefore, the inserted footnote should have been shown as Footnote 26. This footnote not used in this edition. When designing a line to accommodate oversized vehicles, these clearance values shall be increased by the diffe
14、rence between the known height of the oversized vehicle and 14 ft. Page 129: There are three errors in Figure 234-4(b). At the top of the figure, the two instances of “H” should read “A.” The text associated with “A” in the legend should read “B + 5.5 m (18 ft)” and not “V + 5.5 m (18 ft).” Figure 2
15、34-4(b)Clearance envelope for grain bins filled by portable augers, conveyors, or elevators 6 February 2012 STDPT97085 Pages 130, 131, and 132: There is an error in Table 234-1 (m). The cell in column 6 of the header row should contain “ungrounded equipment cases, 750 V to 22 kV.” Clearance of Insul
16、ated communication conductors and cables; messengers; overhead shield/ surge-protection wires; grounded guys; ungrounded portions of guys meeting Rules 215C4, 215C5, and 279A1 exposed to 0 to 300 Vneutral conductors meeting Rule 230E1; supply cables meeting Rule 230C1 (m) Supply cables of 0 to 750 V
17、 meeting Rule 230C2 or 230C3 (m) Unguarded rigid live parts, 0 to 750 V; noninsulated communication conductors; ungrounded equipment cases, 0 to 750 V; and ungrounded portions of guys meeting Rules 215C4, 215C5, and 279A1 exposed to open supply conductors of over 300 V to 750 V(m) Supply cables over
18、 750 V meeting Rule 230C2 or 230C3; open supply conductors, 0 to 750 V(m) Unguarded rigid live parts, over 750 V to 22 kV; ungrounded equipment cases, 750 V to 22 kV; ungrounded portions of guys meeting Rules 215C4, 215C5, and 279A1 exposed to over 750 V to 22 kV(m) Open supply conductors, over 750
19、V to 22 kV (m) Page 133: There is an error in Footnote 11 that appears at the end of Table 234-1 (m). The word “215C5” should be replaced with “215C4.” The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance as grounded guys. Although Footnotes
20、 12 and 13 were deleted from the previous version, the remaining footnotes should not have been renumbered. They should be listed as follows: This footnote not used in this edition. This footnote not used in this edition. For clearances above railings, walls, or parapets around balconies, decks, or
21、roofs, use the clearances required for row 1b(1). For such clearances where an outside stairway exists to provide access to such balconies, decks, or roofs, use the clearances required for row 2b(2). Does not include neutral conductors meeting Rule 230E1. These clearance values also apply to guy ins
22、ulators. It is presumed that a flag or banner is fully extended but that there is no deflection or displacement of the flagpole or other supporting structure due to wind and that the conductors, cables, or rigid live parts are not displaced by the wind. The specified clearance is measured to the poi
23、nt of maximum displacement of the banner or flag towards the overhead utility facility. When designing a line to accommodate oversized vehicles, these clearance values shall be increased by the difference between the known height of the oversized vehicle and 4.3 m. 6 February 2012 STDPT97085 Pages 1
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- IEEEC2ERTA2012NATIONALELECTRICALSAFETYCODE2012 勘误表 国家 电气 安全 规程 PDF

链接地址:http://www.mydoc123.com/p-1366117.html