1、Designation: F479 06 (Reapproved 2017)Standard Specification forIn-Service Care of Insulating Blankets1This standard is issued under the fixed designation F479; the number immediately following the designation indicates the year of originaladoption or, in the case of revision, the year of last revis
2、ion. A number in parentheses indicates the year of last reapproval. A superscriptepsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the in-service care, inspection,testing, and use voltage of insulating blankets for protection ofworke
3、rs from accidental contact with live electricalconductors, apparatus, or circuits. The product requirementsand acceptance testing are as shown in Specification D1048.1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions t
4、o SI units that are provided for information onlyand are not considered standard.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety, health, and environmental
5、practices and deter-mine the applicability of regulatory limitations prior to use.SeeSection 6 and 8.2 for specific precautionary statements.1.4 This international standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Prin
6、ciples for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:2D1048 Specification for Rubber Insulating BlanketsD2865 Practice for Calibration of Standards
7、 and Equipmentfor Electrical Insulating Materials TestingF819 Terminology Relating to Electrical Protective Equip-ment for Workers2.2 ANSI Standard:3C39.5 Safety Requirements for Electrical and ElectronicMeasuring and Controlling InstrumentationC84.1 Voltage Ratings for Electric Power Systems andEqu
8、ipment (60 Hz)3. Terminology3.1 Definitions:3.1.1 breakdownthe electrical discharge or arc occurringbetween the electrodes and through the equipment being tested.3.1.2 compatiblenot injurious to or changing the physicalor electrical characteristics of the blankets or affecting theirapplication, use,
9、 or acceptability.3.1.3 designated personan individual who is qualified byexperience or training to perform an assigned task.3.1.4 electrical testing facilitya location with qualifiedpersonnel, testing equipment, and procedures for the inspectionand electrical testing of electrical insulating protec
10、tive equip-ment.3.1.5 electrodethe energized or grounded conductor por-tion of electrical test equipment which is placed near or incontact with the material or equipment being tested.3.1.6 flashoverthe electrical discharge or arc occurringbetween electrodes and over or around, but not through, theeq
11、uipment being tested.3.1.7 insulatedseparated from other conducting surfacesby a dielectric substance (including air space) offering a highresistance to the passage of current.3.1.7.1 DiscussionWhen any object is said to be insulated,it is understood to be insulated in a suitable manner for thecondi
12、tions to which it is subjected. Otherwise, it is, within thepurposes of this definitions, uninsulated. Insulating covering ofconductors is one means of making the conductor insulated.3.1.8 ozonea very active form of oxygen that may beproduced by corona, arcing, or ultraviolet rays.3.1.9 ozone cuttin
13、g and checkingthe cracks produced byozone in a material under mechanical stress.3.1.10 retestthe tests given after the initial acceptance testusually performed at regular periodic intervals or as requiredbecause of physical inspection.3.1.11 unassigned blanketsblankets that are in storageprior to be
14、ing issued for use.3.1.12 voltage, maximum usethe ac voltage (rms), classi-fication of the protective equipment that designates the maxi-mum nominal design voltage of the energized system that may1This specification is under the jurisdiction of ASTM Committee F18 onElectrical Protective Equipment fo
15、r Workers and is the direct responsibility ofSubcommittee F18.25 on Insulating Cover-Up Equipment.Current edition approved Dec. 15, 2017. Published January 2018. Originallyapproved in 1976. Last previous edition approved in 2011 as F47906(2011). DOI:10.1520/F0479-06R17.2For referenced ASTM standards
16、, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New
17、 York, NY 10036, http:/www.ansi.org.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Pr
18、inciples for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.1be safely worked. The nominal design voltage is equal to thephase-to-phase voltage on multiphase circuits.3.1.12.1 DiscussionIf there
19、 is no multiphase exposure in asystem area, and the voltage exposure is limited to the phase(polarity on dc systems) to ground potential, the phase (polarityon dc systems) to ground potential shall be considered to be thenominal design voltage.3.1.12.2 DiscussionIf electrical equipment and devicesar
20、e insulated or isolated, or both, such that the multiphaseexposure on a grounded wye circuit is removed, then thenominal design voltage may be considered as the phase-to-ground voltage on that circuit.3.1.12.3 DiscussionThe work practices and methods as-sociated with removing multiphase exposures at
21、 any givenwork site are not addressed in the ASTM standards. The usersof ASTM standards should reference appropriate industryconsensus standards for proper work practices.3.1.13 voltage, maximum retestthe voltage, either ac rmsor dc avg, that is equal to the proof test voltage for newprotective equi
22、pment.3.1.14 voltage, nominal designa nominal value consistentwith ANSI C84.1-2001, assigned to the circuit or system forthe purpose of conveniently designating its voltage class.3.1.15 voltage, retestthe voltage, either ac rms or dc avg,that used protective equipment must be capable of withstand-in
23、g for a specified test period without breakdown.3.2 For definitions of other terms, refer to TerminologyF819.4. Significance and Use4.1 Compliance with this specification should continue toprovide personnel with insulating blankets of known andacceptable quality after initial acceptance in accordanc
24、e withSpecification D1048. The standards herein are to be consideredas minimum requirements.5. Classification5.1 Blankets covered under this specification shall be des-ignated as Type I or Type II; Class 0, Class 1, Class 2, Class 3,or Class 4; Style A or Style B.5.2 Type I, not resistant to ozone,
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTM F479 06 2017 Standard Specification for In Service Care of Insulating Blankets

链接地址:http://www.mydoc123.com/p-287236.html