VA 09 69 00-2011 ACCESS FLOORING.pdf
《VA 09 69 00-2011 ACCESS FLOORING.pdf》由会员分享,可在线阅读,更多相关《VA 09 69 00-2011 ACCESS FLOORING.pdf(14页珍藏版)》请在麦多课文档分享上搜索。
1、11-11 09 69 00 - 1 SECTION 09 69 00 ACCESS FLOORING SPEC WRITER NOTES: 1. Delete between / - / if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. 2. Use stringer type construction in seismic zones or large floor areas 278m
2、 (over 3000 sq. ft.) or where floor height is more than 300 mm (12 inches) above sub-floor. 3. Where more than one type of access flooring system is required consider developing separate narrow scope sections for each. The most commonly used underfloor system consist of a welded steel casing filled
3、with lightweight concrete screwed down to an adjustable pedestal systems. For most office spaces, underfloor systems rated at 1000 to 1250 PSI concentrated load are adequate. For heavier traffic loads at loading docks, elevator entrances, and corridors underfloor systems rated at 1500 PSI are approp
4、riate. Underfloor systems rated at 2500 PSI are available for heavy equipment. 4. From the stand-point of static build-up, high pressure laminate is most desirable floor covering, followed by carpet. Wax build up on vinyl tile is a prime cause of static problems. PART 1 - GENERAL 1.1 DESCRIPTION Acc
5、ess flooring shall consist of a series of modular, removable, interchangeable panels on an elevated support system forming an accessible underfloor cavity to accommodate electrical and mechanical services. System shall be bolted filled formed or cast panels on stringerless understructure / gravity-h
6、eld panels on stringerless understructure / gravity-held panels on snap-on stringer understructure / gravity-held panels on bolted stringer understructure. / 1.2 RELATED WORK A. Color and texture of / conductive / vinyl tile, carpet, plastic laminate, vinyl edge strip, sealant, baked enamel and fiel
7、d paint: Section 09 06 00, SCHEDULE FOR FINISHES. SPEC WRITER NOTE: Verify with Mechanical for requirements of active underfloor fire suppression system and coordinate document requirements. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 09 69
8、 00 - 2 /B. Underfloor Fire Suppression System: Refer to Mechanical Contract documents. / B. Connection of access flooring systems to building ground: Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS / Section 27 05 26, GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS / Section 28 05 2
9、6, GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY. C. Electrical distribution components: Refer to Electrical Contract documents. 1.3 DESIGN CRITERIA A. Structural Performance per CISCA A/F: Provide access flooring systems capable of withstanding the following loads and stresses within lim
10、its and under conditions indicated, as determined by testing manufacturers current standard products according to referenced procedures in CISCA A/F, “Recommended Test Procedures for Access Floors“: 1. Ultimate-Load Performance: Provide access flooring systems capable of withstanding a minimum ultim
11、ate concentrated load equal to value obtained by multiplying specified concentrated floor panel design load by a factor of 2.5, without failing, according to CISCA A/F, Section II, “Ultimate Loading.“ Failure is defined as the point at which access flooring system will not take any additional load 2
12、. Rolling-Load Performance: Provide access flooring systems capable of withstanding rolling loads of the following magnitude applied to non-perforated panels, with a combination of local and overall deformation not to exceed 1.02 mm (0.040 inch) after exposure to rolling load over CISCA A/F Path A o
13、r B, whichever path produces the greatest top-surface deformation, according to CISCA A/F, Section III, “Rolling Loads.“ SPEC WRITER NOTE: Use below when only move-in rolling loads tested at 10 passes are anticipated. a. CISCA A/F Wheel 1 Rolling Load: / 2669 N (600 lbf) / 3559 N (800 lbf) / 4448 N
14、(1000 lbf) / 5338 N (1200 lbf). / SPEC WRITER NOTE: Use below when frequent rolling loads tested at 10,000 passes is anticipated. b. CISCA A/F Wheel 2 Rolling Load: / 2224 N (500 lbf) / 2669 N (600 lbf) / 3559 N (800 lbf) / 4448 N (1000 lbf). / Provided by IHSNot for ResaleNo reproduction or network
15、ing permitted without license from IHS-,-,-11-11 09 69 00 - 3 B. Pedestal Assembly: 1. Pedestal Axial-Load Performance: Provide pedestal assemblies, without panels or other supports in place, capable of withstanding a / 22. kN (5000 lbf) / axial load per pedestal, according to CISCA A/F, Section V,
16、“Pedestal Axial Load Test.“ 2. Pedestal Overturning-Moment Performance: Provide pedestal assemblies, without panels or other supports in place, capable of withstanding an overturning moment per pedestal of / 113 N x meters (1000 lbf x inches) / , according to CISCA A/F, Section VI, “Pedestal Overtur
17、ning Moment Test.“ 3. Provide a means of leveling and locking the assembly at a selected height which requires deliberate action to change height setting and which prevents vibrating displacement. 4. Height between the finish floor and underside of / panel / stringer /: a. Not less than _ mm (inches
18、). /B. Stringer: 1. Stringer Concentrated-Load Performance: Provide stringers, without panels in place, capable of withstanding a concentrated load of / 890 N (200 lbf) / at center of span with a permanent set not to exceed 0.25 mm (0.010 inch), as determined per CISCA A/F, Section IV, “Stringer Loa
19、d Testing.“ / C. Panels: 1. All panels shall be interchangeable except those altered to meet special conditions. SPEC WRITER NOTE: Concentrated load performance requirement is for filled formed steel panels and cast panels only. 2. Concentrated-Load Performance: Provide floor panels, including those
20、 with cutouts, capable of withstanding a concentrated design load of the following magnitude, with a top-surface deflection under load and a permanent set not to exceed, respectively, 2.03 and 0.25 mm (0.080 inch and 0.010 inch), according to CISCA A/F, Section I, Concentrated Loads.“ SPEC WRITER NO
21、TE: lbf=PSI for ratings. a. 4448 N (1000 lbf) / 5560 N (1250 lbf) / 5783 N (1300 lbf) / 6672 N (1500 lbf). / Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 09 69 00 - 4 SPEC WRITER NOTE: Use below when routine impact loading is anticipated. Th
22、is is not a CISCA tested characteristic. /3. Floor Panel Impact-Load Performance: Provide access flooring system capable of withstanding an impact load of / 334 N (75 lbf) / 445 N (100 lbf) / 566 N (125 lbf) / 667 N (150 lbf) / 778 N (175 lbf) / when dropped from 914 mm (36 inches) onto a 6.5-sq. cm
23、 (1-sq. in.) area located anywhere on panel, without failing. Failure is defined as collapse of access flooring system. / D. Installed access floor shall be level within plus or minus 1 in 2000 (0.060 inches in 10 feet), and plus or minus 2.5 mm (0.10 inches) over the entire area. Floor assembly to
24、be rigid, free of vibration, rocking panels, rattles and squeaks. SPEC WRITER NOTE: Use following subparagraph only when the air space below the finish floor is to serve as a plenum. /E. Leakage: Air leakage through the joints between panels and around the perimeter of the floor system not to exceed
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA0969002011ACCESSFLOORINGPDF
