UFC 3-440-01 CHANGE 1-2007 ACTIVE SOLAR PREHEAT SYSTEMS《主动式太阳能预热系统》.pdf
《UFC 3-440-01 CHANGE 1-2007 ACTIVE SOLAR PREHEAT SYSTEMS《主动式太阳能预热系统》.pdf》由会员分享,可在线阅读,更多相关《UFC 3-440-01 CHANGE 1-2007 ACTIVE SOLAR PREHEAT SYSTEMS《主动式太阳能预热系统》.pdf(98页珍藏版)》请在麦多课文档分享上搜索。
1、UFC 3-440-01 14 June 2002 Including change 1, December 2007 UNIFIED FACILITIES CRITERIA (UFC) ACTIVE SOLAR PREHEAT SYSTEMS APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 3-440-01 14 June 2002 I
2、ncluding change 1, December 2007 1UNIFIED FACILITIES CRITERIA (UFC) ACTIVE SOLAR PREHEAT SYSTEMS Any copyrighted material included in this UFC is identified at its point of use. Use of the copyrighted material apart from this UFC must have the permission of the copyright holder. U.S. ARMY CORPS OF E
3、NGINEERS (Preparing Activity) NAVAL FACILITIES ENGINEERING COMMAND AIR FORCE CIVIL ENGINEER SUPPORT AGENCY Record of Changes (changes are indicated by 1 . /1/) Change No. Date Location 1 Dec 2007 Page 2-2 add Para 2-5 and Page A-1 Provided by IHSNot for ResaleNo reproduction or networking permitted
4、without license from IHS-,-,-UFC 3-440-01 14 June 2002 Including change 1, December 2007 2FOREWORD 1 The Unified Facilities Criteria (UFC) system is prescribed by MIL-STD 3007 and provides planning, design, construction, sustainment, restoration, and modernization criteria, and applies to the Milita
5、ry Departments, the Defense Agencies, and the DoD Field Activities in accordance with USD(AT those having more heating degree days should use a 50 percent solution. This heating day criteria is provided as a suggested guideline only. It is up to the designer to take into account each locations parti
6、cular climate and freezing-day characteristics when determining whether a 30 or 50 percent solution should be used. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 3-440-01 14 June 2002 3-6 Figure 3-4. Flat-Plate Collector 3-4.1.2 Array Size. The
7、 first step in the system layout is to estimate collector array size (the actual array size cannot be determined until a specific collector is chosen for the detailed design). 3-4.1.3 Array Tilt Angle. The collector array tilt angle is defined to be the angle between the collector and the horizontal
8、, with 0 degrees being horizontal and 90 degrees being vertical. The proper tilt angle is a function of the time of year when the load occurs. For annual loads, such as service and process water heating, the widely accepted practice is to tilt the collectors to the value of the local latitude. If th
9、e load tends to have a seasonal variation, the tilt can be varied to favor the season. Examples include seasonal hot water requirements, space heating, and space cooling. If the collectors are tilted to the latitude angle plus 10 degrees, the energy output will be more evenly distributed over the en
10、tire year, although winter losses will tend to increase, due to lower outdoor temperatures. Tilting the array to the latitude minus 10 degrees favors summer energy output. It is not generally recommended to tilt the array any more than Provided by IHSNot for ResaleNo reproduction or networking permi
11、tted without license from IHS-,-,-UFC 3-440-01 14 June 2002 3-7 plus or minus 10 degrees from the site latitude. It should be noted that as the tilt angle increases, the minimum spacing between rows due to shading increases and larger roof area is required. 3-4.1.4 Array Azimuth Angle. The array azi
12、muth angle is defined to be the angle between the projection of the normal to the surface on a horizontal plane and the local meridian (north-south line). Zero degrees is defined as due south, a due west facing array is defined as plus 90 degrees, and a due east facing array is defined as minus 90 d
13、egrees (in the northern hemisphere). The optimal orientation requires the azimuth angle to be 0 degrees (due south) whenever possible, although deviations of plus or minus 20 degrees off of due south have a minimal effect on flat-plate system performance. 3-4.1.5 Collector Grouping. Internal-manifol
14、d collectors should be grouped into banks ranging from four to seven collectors each, with each bank containing the same number of collectors. Proper sizing of the collector banks is essential to maintaining uniform flow throughout the collector array. The maximum number of collectors that can be ba
15、nked together is a function of the maximum flow rate allowed in the plumbing, internal manifold and riser diameters, thermal expansion characteristics of the collector piping and absorber plate assembly, and the recommended flow rate of the particular collector chosen (usually given in gallons per m
16、inute (liters per second) per collector or gallons per minute per square feet (liters per second per square meter) of collector area). Thermal expansion problems are minimized by keeping the bank size less than eight collectors. 3-4.1.6 Minimum Array Row Spacing. The minimum row spacing must be calc
17、ulated for multi-row arrays. A general routine for north-south spacing of collector banks can be devised, based on a “no shading“ criterion for a particular time of year. The guidance presented assumes no shading of the array on the “worst“ solar day of the year (21 December, when the sun is lowest
18、in the sky in the northern hemisphere) for the designated time period of 10 a.m. to 2 p.m. solar time. Most large-scale military solar systems are installed on low-slope flat roofs, and there are two possible cases to consider. The first is for a flat roof with enough space to locate the collector a
19、rray at one elevation. The second case is for a flat roof with too little space for the collector array. This requires the collector banks to be “stepped“, that is, each succeeding row of collectors must be elevated. This arrangement is necessary if the collector roof area required is larger than th
20、at available or if roof area costs are more expensive than elevated rack costs. The equations developed for minimum collector row spacing are presented graphically in Figure 3-5. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 3-440-01 14 June 20
21、02 3-8 Figure 3-5. Minimum Collector Row Spacing 3.4.1.6.1 Azimuth Orientations. The curves shown in Figure 3-5 are for collector azimuth orientations of plus or minus 20 degrees. For the due south orientation (0 degrees), the deviation from these results is less than 10 percent. Use of Figure 3-5 f
22、or due south orientations is thus slightly conservative. The effect of elevating the rear collector row (larger C/L values) shows a marked decrease in the minimum spacing (S/L). The flat roof, no elevation collector case is represented by the curves where C/L = 0. 3.4.1.6.2 Roof Pitch. Collectors ca
23、n also be mounted on pitched roofs. Often, when a solar energy system is to be added to a building, the roof is pitched and constructed such that the collectors could be mounted on the roof surface. This practice does not necessarily impose unreasonable constraints in the roof design, since there is
24、 some flexibility in the choice of collector tilt angle. If the roof cannot be pitched to allow flush mounting of the collectors, or if the tilt angle must be fixed, then the collectors can be raised at one end to give them the proper tilt. Figure 3-5 can be used to determine the spacing by includin
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UFC344001CHANGE12007ACTIVESOLARPREHEATSYSTEMS 主动 太阳能 预热 系统 PDF

链接地址:http://www.mydoc123.com/p-1066940.html