REG NASA-LLIS-0047-1991 Lessons Learned - Mercoid Pressure Switch Inadvertent Water Deluge Activation.pdf
《REG NASA-LLIS-0047-1991 Lessons Learned - Mercoid Pressure Switch Inadvertent Water Deluge Activation.pdf》由会员分享,可在线阅读,更多相关《REG NASA-LLIS-0047-1991 Lessons Learned - Mercoid Pressure Switch Inadvertent Water Deluge Activation.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、Lessons Learned Entry: 0047Lesson Info:a71 Lesson Number: 0047a71 Lesson Date: 1991-12-19a71 Submitting Organization: KSCa71 Submitted by: David PenningtonSubject: Mercoid Pressure Switch; Inadvertent Water Deluge Activation Description of Driving Event: The primary cause of the mishap was an activa
2、tion (closing) of the fire pump mercoid pressure switch which prematurely started the fire pump. This produced transient pressures that exceeded the 2:1 mechanical advantage of the deluge valves, forcing them open. The switch activation was caused by potable water system pressure fluctuations extern
3、al to the local facility.Lesson(s) Learned: 1. Mercoid pressure switches are overly sensitive to system pressure fluctuations and may cause inadvertent activation (switch bouncing).2. Water deluge systems are unable to adequately absorb water line transients, thus jeopardizing the integrity of the v