NAVY MIL-I-22076 B-1963 INSULATION TUBING ELECTRICAL NONRIGID VINYL VERY LOW TEMPERATURE GRADE《带电的非硬的非常低温乙烯基绝缘管道系统》.pdf
《NAVY MIL-I-22076 B-1963 INSULATION TUBING ELECTRICAL NONRIGID VINYL VERY LOW TEMPERATURE GRADE《带电的非硬的非常低温乙烯基绝缘管道系统》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-I-22076 B-1963 INSULATION TUBING ELECTRICAL NONRIGID VINYL VERY LOW TEMPERATURE GRADE《带电的非硬的非常低温乙烯基绝缘管道系统》.pdf(15页珍藏版)》请在麦多课文档分享上搜索。
1、MIL-I-22076B 5 August 1963 SUPERSEDING MIL-I-Z2076A(SHIPS) 28 March 1961 MILITARY SPECIFICATION INSULATION TUBING, ELECTRICAL, NONRIGID, VINYL, VERY LOW TEMPERATURE GRADE This specification has been approved by the Department of Defense and is man- datory for use by the Departments of the Army, the
2、Navy, and the Air Force. 1. SCOPE 1.1 This specification covers a very low temperature grade of nonrigid tubing of polyvinyl chloride or polyvinyl chloride-acetate for use as electrical insulation. 2. APPLICABLE DOCUMENTS 2.1 The following documents, of the issue in effect on date of invitation for
3、bids or request for proposal, form a part of the specification to the extent specified herein: SPECIFICATIONS FEDERAL VV-1-530 - Insulating Oil, Electrical (for Transformers, Switches, and Circuit Breakers), MILITARY MIL-S-3136 - Standard Test Fluids; Hydrocarbon. STANDARDS MILITARY MIL-STD-105 - Sa
4、mpling Procedures and Tables for Inspection by Attributes. (Copies of specifications, standards, drawings, and publications required by suppliers in connection with specific procurement functions should be obtained from the procuring activity or as directed by the contracting officer.) 2.2 Other pub
5、lications.- The following documents form a part of this specification to the extent specified herein. Unless otherwise specified, the issue in effect on date of invitation for bids or request for proposal shall apply. AMERICAN SOCIETY FOR TESTING AND MATERIALS trical Insulating Materials. . D150 - M
6、ethods of Test for A-C Capacitance, Dielectric Constant, and Loss Characteristics of Elec- D746 - Method of Test for Brittleness Temperature of Plastics and Elastomers by Impact. D876 - Methods of Testing Nonrigid Polyvinyl Tubing. (Application for copies should be addressed to the American Society
7、for Testing and Materials, 1916 Race Street, Philadelphia 3, Pa.) OFFICIAL CLASSIFICATION COMMITTEE Uniform Freight Classification Rules. (Application for copies should be addressed to the Official Classification Committee, 1 Park Avenue at 33rd Street, New York 16, N. Y.) Licensed by Information Ha
8、ndling ServicesProvided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-I-22076B (Technical society and technical association specifications and standards are generally available for ref- erence from libraries. They are also distributed among technical gr
9、oups and using Federal agencies,) 3, REQUIREMENTS 3.1 Qualification.“ Electrical insulation tubing furnished under this specification shall be a product which has been tested and has passed the qualification tests specified herein, and has been listed on or approved for listing on the applicable qua
10、lified products list. 3.2 Material.- The tubing shall be of polyvinyl chloride or polyvinyl chloride-acetate composition prop- erly formulated with plasticizers, pigment, stabilizers, or other ingredients necessary to conform to this specification. 3.2.1 Changes in material.- If the manufacturer des
11、ires to change his process or the composition of his material, after qualification approval has been granted (see 6.3), he shall submit to the qualifying agency (Bureau of Ships) a statement to that effect, describing the proposed change, together with evidence to sub- stantiate his claim that such
12、change is suitable. Similar notification and substantiating evidence shall be sub- mitted at any later time if a change again becomes necessary or desirable. At the discretion of the qualifying agency, test specimens may be required to prove the suitability of the proposed changes, 3.2.3 Surface def
13、ects.- Materials shall be free from blisters, bubbles, wrinkles, and cracks, and shall be reasonably free from other small defects such as scratches and dents, 3.2.4 Colors.- Unless otherwise specified, materials shall be furnished clear transparent (uncolored), Available colors considered standard
14、are black, white, yellow, green, blue, and red (see 6.2). 3.3 Quantitative requirements (property values).- When specimens are subjected to the tests specified in table I, the values obtained from any set of specimens for any specific property after any one conditioning procedure specified in the ta
15、ble shall be averaged, and this average value shall be not less than the minimum nor more than the maximum value (as applicable) specified in table I. Table I - Quantitative requirements (property values). 2 Property to be tested strengtd Dielectric strengthu Dissipation factor at 1 kilocycle Dielec
16、tric constant at 1 kilocycle Test reference 4.7.2 4.7.3 4.7.3 Conditioning procedure C-96/23/0 C-96/23/96 C-96/23/0 C-96/23/96 C-96/23/0 C-96/23/96 Unit of value Percent of dry value obtained on test (min.) Maximum Maximum Nominal dimensions Inches wall thickness 0.016 .O20 .O25 .O30 ,040 ,050 .O60
17、I All thick- ness “ “ Value required 650 550 480 430 350 300 280 ?O 0.14 b.16 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-Table I - Quantitative requirements (property values) (Contd). Property to be tested Test reference Conditioning procedure U
18、nit of value Value required Nominal dimensions Inches wall thickness 109 Dt-24/23 Volume resistivity 4.7.4 Ohm-centimeters (min.) Tensile strength 4.7.5 C-96/23/50 P.s.i. (min.) 1800 Elongation 250 450 C-96/23/50 C-96/23/50 Percent (min.) Percent (max.) Degrees centi- grade (min.) Softening temperat
19、ure (penetration) 4.7.6 C-96/23/50 80 Lengthwise shrinkage 4.7.7 E-2/100 Percent (max,) 10 4.7.12 “AS received“ -55 Degrees centi- grade (ma.) Maximum change in de- grees centi- grade from value obtained on test of “as received“ samples Cold brittle- ness Cold Brittle- ness (aged samples) 4.7.12 E-4
20、00/100 15 l/For thickness not shown, the dielectric strength shall be that given for the nearest thickness shown, 3.4 Dimensions and tolerances. - 3.4.1 Lengths,- Unless otherwise specified in the contract or order, tubing shall be furnished on reels in lengths specified in table II (see 6.2). Tubin
21、g furnished on reels shall be wound on the reels in such a man- ner that the tubing will not be flattened or kinked to an extent that printing of circuit identification machine, if desired, cannot be accomplished. Minimum lengths specified shall not be exceeded by more than 10 percent, Table II - Tu
22、bing Iengths. Nomina1 inside diameter Minimum length Inch Feet 1,000 500 200 100 0.034 - 0.059 .O66 - .166 ,186 - .330 .360 and over 3.4.2 Inside diameters and wall thicknesses.- Unless otherwise specified in the contract or order, tubing shall be furnished in the standard inside diameters and wall
23、thicknesses shown in table III, as specified (see 6.2). -8 r- “_ F? -, 1 3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-. MIL-I-22076B Table III - Inside diameters and wall thicknesses of tubing AWG sizes. AWG size number 24 22 20 19 18 17 16 15 1
24、4 13 12 11 10 9 8 7 6 5 4 3 2 1 O 5/16 inch 3/8 inch 7/16 inch 1/2 inch 5/8 inch 3/4 inch 7/8 inch 1 inch 1-1/4 inches 1-1/2 inches 1-3/4 inches 2 inches T Inside diameter (inches) Nominal 0.022 .O27 ,034 ,038 ,042 ,047 ,053 .O59 ,066 ,076 ,085 ,095 ,106 ,118 .133 ,148 ,166 ,186 ,208 ,234 .263 ,294
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILI22076B1963INSULATIONTUBINGELECTRICALNONRIGIDVINYLVERYLOWTEMPERATUREGRADE 带电 非常 低温 乙烯基 绝缘 管道 系统

链接地址:http://www.mydoc123.com/p-979742.html