NAVY MIL-F-82165 B-1982 FUEL MONITORS FRAME MOUNTED 100-& 350- GALLON PER MINUTE CAPACITIES《框架每分钟容量100-& 350-加仑燃油监控器》.pdf
《NAVY MIL-F-82165 B-1982 FUEL MONITORS FRAME MOUNTED 100-& 350- GALLON PER MINUTE CAPACITIES《框架每分钟容量100-& 350-加仑燃油监控器》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-F-82165 B-1982 FUEL MONITORS FRAME MOUNTED 100-& 350- GALLON PER MINUTE CAPACITIES《框架每分钟容量100-& 350-加仑燃油监控器》.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、MIL-F-ZL65B 47 m 7997906 0257085 m PkL-FI-8 216 5 B (iW) 18 Jum 1982 SJPERSEDING MIL-F-82165A(K) 1 December 1978 MILITM SPEC1 FI CATI CN FUEL IVYINITORS: FRA“ IVK)UNTED, 100- AND 350- GALLCN P!3R MINUJX CWACITIES This specification is approved for use by U. S. Marine Corps, Department of the Navy, a
2、nd is available for use by all Departments and Agencies of the Department of Defense 1. SCOPE 1.1 Scope. This specification avers requirements for fuel mnitors for use downstream of 100 gallon per minute (gal/min) and 350 gal/min filter-separators. 1.2 Classification. Fuel monitors covered by this s
3、pecification shall 5e of the following types, as specifid (see 6.2): Type I - lOO-gal/min Capacity Type II - 350-gal/inin Capacity 2. APPLICABLE DOCUmNTS 2.1 Government documents. 2.1.1 Specifications and standards. Unless otherwise specified, the following specifications and standards of the issue
4、listed in that issue of the Department of Defense Index of Spcifications and Standards (DODISS) specified in the solicitation, form a part of this specification to the extent specified herein. SPECIFICAIIONS FEDERAL L-P-37s - Plastic Sheet and Strip, Thin Gauge, Polyolefin. QaP-416 - Platiq, Cadnium
5、 (Electrodeposited) . Q-Z-325 - Zinc Coating, Electrodeposited, Rquireinents for. PPP-B-601 - Boxes, Wood, Cleated-Plywood PPP-5536 - Boxes, Shipping, Fiberboard. Benefical comments (recokmendations, additions, deletions), and any pertinent data which may be of use in improvitig this document, shoul
6、d be addressed to Cmandant of the Marine Corps, Yeadquarters Marine Corps (Code LMA-1) , Washington, X 20380, by using the self-addressed Standard- ization Docuiri-nt Improvement Proposal (DD Forn 1425), apparing at the encl of this document, or by letter. 1 THIS DOCUMENT CONTAINS 2.i. PAGES. FSC 49
7、30 -7 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-F-2Lb5B 49 W 9999906 0257086 T W MILITAN MIL-T-704 MIL-65541 MI L-A-9 6 25 MIL-T-22085 MIL-W-22248 MIL-E-52798 MI L-netals in intimate contact with each other shall be avoided wherever possibl
8、e. of dissimilar inetals cannot be avoided, an interposing material which will eliminate or minimize galvanic corrosion shall be used. metals shall be defined in MIL-STD-889. All inetal surfaces shall be treated alid finished in accordance with MIL-T-704, type B. When the use Dissinilar 3,lO Identif
9、ication marking. Each fuel mnitor shall be identified in accordance with MIL-STD-130. The identification, instruction, and warning plates and markings shall be in accordance with Drawing Nos. f305016AOO6 through 805015A0010 , 3.11 Workmanship. The fuel mnitors shall be free from defects such as inis
10、aligned can,oonents, incmplete welds, cracks, burns, leaks, and other defects that-could imgair operation and ssrviceability. parts shall be clean and free from dirt, sard, grease, oil and metal chips. Nonfknctional sharp edges and projecting pints, which might preaciit a hazard to personnel, shall
11、be avoided. All 4. flALITY ASSOWINCE PR3VISIONS 4.1 Responsibility for inspectiori. Unless otherwise specified in the contract or prirchase order, the contractor is res,oonsible for the per- forinance of all inspction requirements as specified herein. Except as otherwice specified in the contract or
12、 pirchase order, the contractor may use his own or any other facilities suitable for the performance of the iiispction requirements specified herein, unless disapproved by the Gsverrunent. inspsctions set forth in the specification whsre such insj?ections are deemed necessary to assure supplies and
13、services conform tc, proscribed reyui rements. Tiie Goverrimant reserves the right to perform any of the 4.1.1 Component and material inspection. The contractor is respns- ible for insuriry that coinponents ad materials used are manufactured, sxainined, and tested in accordance with referenced speci
14、fications and standards. 4.2 Classification of inspections, he inspction requiremwts specified herein are classified as follows: G Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-F-82365B q7 777770b 0257073 3 a a MI L-F-8 2165 B (MC) . a. First a
15、rticle inspection (see 4.3). b. Quality conformance inspection (see 4.4) c. Inspection of packagitq (see 4.7). 4.3 First article inspection. Examination and tests shall be as follows anil, unless otherwise specified herein, all examinations and tests shall be conducted by the contractor subject to s
16、urveillance and approval by the Government (see 6.2). requirements for performing the quality conformance inspections. Approval of the first article does not preclude the 4.3.1 Examination. The first article shall be examined as specified in 4.5.1. Presence of one or mre mjor defects shall be cause
17、for rejection. 4.3.2 Tests. The first article shall be subjected to tests specified in 4.6.1 through 4.6.5. Failure of any test shall be cause for rejection or shall be cause for performirq the inspection specified in 4.3.3. 4.3.3 Disassenbly inspection. Failure of a ,prformance test by the first ar
18、ticle fuel monitors shall require disassembly of the fuel monitors in the presence of a Government representative. Each disasseinbled part shall be inspected in detail for compliance with this specification and referenced drawings in regard to materials, dimensions, tolerances, and workinanship. Par
19、ts not complying with such requirements shall be rejected. 4.4 Quality conformance inspection. 4.4.1 Sampling. Sampliq for examination shall be as specified in MIL-STD-105, inspection level II. 4.4.2 Examination. Sanples selected as specified in 4.4.1 shall be examined for the major and minor defeck
20、s specified in 4.S. Acceptable quality level (AQL) shall be 2.5 percent defective for major defects and 4.0 percent defective for minor defects. 4.4.3 Tests. Each fuel mnitor shall be subjected to tests specified in 4.5.1 and 4.6.5. Failure of either test shall be cause for rejection. 4.5 Visual exa
21、mination. Fuel mnitors shall be examined as specified herein for the followiq defects: Major. 101. Dimensions mt as specified (see 3.3) , 102, Materials not as specified (see 3.2). 103. Hardware such as bolts, nuts, washers, and screw threads not as specified (see 3.2.3). Aluminum parts and componen
22、ts riot coated as specified (see 3.9.2). Weldings and castings not as specified (see 3.4.2). Fuel monitors not cleaned and air-dried aEter testiq (see 4.6.6). .104. 105. 106. 7 , Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MTL-F-82Lh5B 47 W 77777
23、0b OZ57072 5 W MI L-F-8 2 16 5 B (Mc) 107. 108. Workmanship not as specified (see 3.11). Elements and gaskets not as specified (see 3.3.1 and 3.3.3). Minor . P 201. Identification marking incorrect, illegible or aissing 202. Instruction plates mt as specified (see 3.10) . 203, Treatment and paintirq
24、 not as specified (see 3.9.1).) (see 3.10). 4.6 Tests 4.6.1 Hydrostatic pressure test. Tk fuel ironitor shall be subjected to the hydrostatic pressure test specified in MIL-M-81380. Nonconformance to requirements specified in 3.2.1 and 3.2.2 or to the applicable require- ments of YIL-M-813.50 shall
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILF82165B1982FUELMONITORSFRAMEMOUNTED100350GALLONPERMINUTECAPACITIES 框架 每分钟 容量 100350 加仑 燃油 监控器

链接地址:http://www.mydoc123.com/p-979223.html