NAVY MIL-DTL-16377 82-2008 FIXTURES LIGHTING T8 FLUORESCENT EMERGENCY LIGHTING 17 WATTS 120 VOLTS 60 HERTZ WATERTIGHT SYMBOLS 331 1T8EM 331 2T8EM 347 2T8EM AND 347 3T8EM《照明设备固定装置 防.pdf
《NAVY MIL-DTL-16377 82-2008 FIXTURES LIGHTING T8 FLUORESCENT EMERGENCY LIGHTING 17 WATTS 120 VOLTS 60 HERTZ WATERTIGHT SYMBOLS 331 1T8EM 331 2T8EM 347 2T8EM AND 347 3T8EM《照明设备固定装置 防.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-DTL-16377 82-2008 FIXTURES LIGHTING T8 FLUORESCENT EMERGENCY LIGHTING 17 WATTS 120 VOLTS 60 HERTZ WATERTIGHT SYMBOLS 331 1T8EM 331 2T8EM 347 2T8EM AND 347 3T8EM《照明设备固定装置 防.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、AMSC N/A FSC 6210 INCH-POUND MIL-DTL-16377/82 18 December 2008 DETAIL SPECIFICATION SHEET FIXTURES, LIGHTING; T8 FLUORESCENT, EMERGENCY LIGHTING, 17 WATTS, 120 VOLTS, 60 HERTZ, WATERTIGHT, SYMBOLS 331.1T8EM, 331.2T8EM, 347.2T8EM, AND 347.3T8EM This specification is approved for use by the Naval Sea
2、Systems Command and is available for use by all Departments and Agencies of the Department of Defense. The requirements for acquiring the product described herein shall consist of this specification sheet and MIL-DTL-16377. All dimensions in inches. For tolerances, other than specified herein, see 3
3、.5.2 of MIL-DTL-16377. FIGURE 1. Typical view of symbols 331.1T8EM and 347.2T8EM, symbols 331.2T8EM and 347.3T8EM use identical construction with flush mounting flange not shown. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-16377/82 2 NOTE
4、S: 1. Symbols 331.2T8EM and 347.3T8EM use identical battery test switch construction with additional switch hardware (not shown) for switch operation below ceiling. 2. Type II label required on all fixtures. FIGURE 2. Typical section for symbols 331.1T8EM and 347.2T8EM. FIGURE 3. Typical section for
5、 symbols 331.1T8EM and 347.2T8EM. NOTE: 1. Type II Label required for all fixtures. FIGURE 4. Typical section for symbols 331.2T8EM and 347.3T8EM. FIGURE 5. Typical side view for symbols 331.2T8EM, 331.2T8EM, 347.2T8, and 347.3T8EM. Provided by IHSNot for ResaleNo reproduction or networking permitte
6、d without license from IHS-,-,-MIL-DTL-16377/82 3 FIGURE 6. Flush mounting dimension for symbols 331.2T8EM and 347.3T8EM. FIGURE 7. Standard mounting dimensions utilizing shock mounts for symbols 331.1T8EM and 347.2T8EM. Provided by IHSNot for ResaleNo reproduction or networking permitted without li
7、cense from IHS-,-,-MIL-DTL-16377/82 4 NOTES: 1. The black input conductor is the only switched power lead to the fixture, used for normal external on/off lamp control. 2. The white and green input conductors shall be connected directly to the power source and remain continuously energized for emerge
8、ncy lamp battery charging. The white and green input conductors shall not have power interrupted by on/off control switches. 3. The white input conductor is shared by the normal lamp circuit and by the emergency circuit. FIGURE 8. Typical wiring diagram. FIGURE 9. Candela distribution curves, white
9、diffusing window, symbols 331.1T8EM and 331.2T8EM. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-16377/82 5 FIGURE 10. Candela distribution curves, prismatic window, symbols 347.2T8EM and 347.3T8EM. FIGURE 11. Candela distribution curves, e
10、mergency mode. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-16377/82 6 TABLE I. Numerical candela distribution, white diffusing window, symbols 331.1T8EM and 331.2T8EM. Candela distribution Candela distribution Vertical angle 0-degree 90-d
11、egree Vertical angle 0-degree 90-degree 0 228 228 95 1 46 5 227 227 105 0 35 15 216 223 115 0 26 25 195 211 125 0 19 35 166 193 135 0 13 45 132 172 145 0 8 55 98 150 155 0 4 65 64 125 165 0 0 75 32 95 175 0 0 85 7 66 180 0 0 90 2 55 TABLE II. Numerical candela distribution, prismatic window, symbols
12、 347.2T8 and 347.3T8. Candela distribution Candela distribution Vertical angle 0-degree 90-degree Vertical angle 0-degree 90-degree 0 231 231 95 2 13 5 231 231 105 2 6 15 223 233 115 1 6 25 207 231 125 0 5 35 182 231 135 0 4 45 147 208 145 0 2 55 97 167 155 0 1 65 52 149 165 0 0 75 23 115 175 0 0 85
13、 9 51 180 0 0 90 2 25 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-16377/82 7 TABLE III. Numerical candela distribution, emergency mode. Candela distribution Candela distribution Vertical angle 0-degree 90-degree Vertical angle 0-degree 90
14、-degree 0 56 56 95 8 0 5 56 55 105 4 0 15 54 53 115 3 0 25 51 48 125 2 0 35 46 41 135 1 0 45 41 33 145 1 0 55 35 25 155 0 0 65 28 17 165 0 0 75 21 8 175 0 0 85 14 2 180 0 0 90 10 1 PHOTOMETRIC DATA: Photometry reports based on LM-41 and other pertinent IESNA procedures. Plane: 0 degrees is parallel
15、to lamp, 90 degrees is perpendicular to lamp. Electrical values: 120 volts, 60 hertz, 18.0 watts+4.0 watts (battery charging circuit)=22.0 watts total. Ambient temperature: 251C. Lamp: GE F17T8-SP41-ECO (seasoned for at least 100 hours). Lamp correction: lamp rated at 1325 lumens. Ballast: Furnished
16、 with fixture, see MIL-DTL-16377/81 for 17-watt lamp specification, MIL-DTL-16377/77 for emergency ballast specification. REQUIREMENTS: CLASSIFICATION: Type: I (fluorescent). Class: 2 (general). SYMBOL NUMBERS: 331.1T8EM: Complete lighting fixture assembly, standard mounting, with one 17-watt T8 coo
17、l white fluorescent lamp and white diffusing window assembly, includes emergency battery/ballast circuit for emergency lighting. 331.2T8EM: Complete lighting fixture assembly, flush mounting, with one 17-watt T8 cool white fluorescent lamp and white diffusing window assembly, includes emergency batt
18、ery/ballast circuit for emergency lighting. 347.2T8EM: Complete lighting fixture assembly, standard mounting, with one 17-watt T8 cool white fluorescent lamp, clear and white prismatic window assembly, includes emergency battery/ballast circuit for emergency lighting. Provided by IHSNot for ResaleNo
19、 reproduction or networking permitted without license from IHS-,-,-MIL-DTL-16377/82 8 347.3T8EM: Complete lighting fixture assembly, flush mounting, with one 17-watt T8 cool white fluorescent lamp, clear and white prismatic window assembly, includes emergency battery/ballast circuit for emergency li
20、ghting. DESIGN: Electrical rating: 17 watts, 120 volts, 60 hertz, ungrounded electrical distribution system total input power: 18.0 watts+4.0 watts (battery charging circuit)=22.0 watts total at 120 volts. Dimension and configurations: See figures 1, 2, 3, and 4. Photometric data: See figures 9, 10,
21、 and 11; and tables I, II, and III. Wiring diagram: See figure 8. Ballast: See MIL-DTL-16377/81 for 17-watt T8 lamp specification, MIL-DTL-16377/77 for emergency ballast specification. Mounting dimensions: Symbols 331.1T8 and 347.2T8: Standard mounting (surface), see figure 7. Symbols 331.2T8 and 34
22、7.3T8: Flush mounting (recessed), see figure 6. Window assembly: Symbols 331.1T8 and 331.2T8: White window, see table VI and figure 27 of MIL-DTL-16377. Symbols 347.2T8 and 347.3T8: Prismatic window, see table VI and figure 27 of MIL-DTL-16377. Enclosure: Watertight; see 3.5.11 of MIL-DTL-16377. Cab
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILDTL16377822008FIXTURESLIGHTINGT8FLUORESCENTEMERGENCYLIGHTING17WATTS120VOLTS60HERTZWATERTIGHTSYMBOLS3311T8EM3312T8EM3472T8EMAND3473T8EM

链接地址:http://www.mydoc123.com/p-978466.html