1、MSS SP-139-2014 Copper Alloy Gate, Globe, Angle, and Check Valves for Low Pressure/Low Temperature Plumbing Applications Standard Practice Developed and Approved by the Manufacturers Standardization Society of the Valve and Fittings Industry, Inc. 127 Park Street, NE Vienna, Virginia 22180-4602 Phon
2、e: (703) 281-6613 Fax: (703) 281-6671 E-mail: standardsmss-hq.org www.mss-hq.org MSS STANDARD PRACTICE SP-139i This MSS Standard Practice was developed under the consensus of the MSS Technical Committee 203 and the MSS Coordinating Committee. The content of this Standard Practice is the resulting ef
3、forts of competent and experienced volunteers to provide an effective, clear, and non-exclusive standard that will benefit the industry as a whole. This MSS Standard Practice describes minimal requirements and is intended as a basis for common practice by the manufacturer, the user, and the general
4、public. The existence of an MSS Standard Practice does not in itself preclude the manufacture, sale, or use of products not conforming to the Standard Practice. Mandatory conformance to this Standard Practice is established only by reference in other documents such as a code, specification, sales co
5、ntract, or public law, as applicable. MSS has no power, nor does it undertake, to enforce or certify compliance with this document. Any certification or other statement of compliance with the requirements of this Standard Practice shall not be attributable to MSS and is solely the responsibility of
6、the certifier or maker of the statement. “Unless indicated otherwise within this MSS Standard Practice, other standards documents referenced to herein are identified by the date of issue that was applicable to this Standard Practice at the date of approval of this MSS Standard Practice (see Annex A)
7、. This Standard Practice shall remain silent on the validity of those other standards of prior or subsequent dates of issue even though applicable provisions may not have changed.” By publication of this Standard Practice, no position is taken with respect to the validity of any potential claim(s) o
8、r of any patent rights in connection therewith. MSS shall not be held responsible for identifying any patent rights. Users are expressly advised that determination of patent rights and the risk of infringement of such rights are entirely their responsibility. In this Standard Practice, all text, not
9、es, annexes, tables, figures, and references are construed to be essential to the understanding of the message of the standard, and are considered normative unless indicated as “supplemental”. All appendices, if included, that appear in this document are construed as “supplemental”. Note that supple
10、mental information does not include mandatory requirements. U.S. customary units in this Standard Practice are the standard; (SI) metric units, unless otherwise indicated, are for reference only. Substantive changes in this 2014 edition are “flagged” by parallel bars as shown on the margins of this
11、paragraph. The specific detail of the change may be determined by comparing the material flagged with that in the previous 2010 edition. Non-toleranced dimensions in this Standard Practice are nominal unless otherwise specified. Excerpts of this Standard Practice may be quoted with permission. Credi
12、t lines should read Extracted from MSS SP-139-2014 with permission of the publisher, Manufacturers Standardization Society of the Valve and Fittings Industry. Reproduction and/or electronic transmission or dissemination is prohibited under copyright convention unless written permission is granted by
13、 the Manufacturers Standardization Society of the Valve and Fittings Industry Inc. All rights reserved. Originally Approved: January 2010 Originally Published: April 2010 Current Edition Approved: December 2013 Current Edition Published: September 2014 Copyright , 2014 by Manufacturers Standardizati
14、on Society of the Valve and Fittings Industry, Inc. Printed in U.S.A. MSS STANDARD PRACTICE SP-139ii TABLE OF CONTENTS SECTION PAGE PURPOSE . 1 1 SCOPE 1 2 PRESSURE-TEMPERATURE RATINGS . 1 3 MATERIALS 2 4 DESIGN 2 5 MARKINGS 5 6 TOLERANCE . 5 7 INSPECTION AND TESTING 5 TABLE 1 Minimum Length and Dep
15、th of Thread . 3 2 Diameter of Handwheels . 5 X1-1 Minimum Length and Depth of Thread 9 X1-2 Minimum Diameter of Handwheels 10 ANNEX A Referenced Standards and Applicable Dates 7 APPENDIX X1 Metric References . 9 MSS STANDARD PRACTICE SP-1391 PURPOSE This MSS Standard Practice establishes requiremen
16、ts for copper alloy gate, globe, angle, and check valves used in applications with connections and connected to materials which will not support the pressures and temperatures of applicable ANSI-approved Class standards and the requirements of MSS SP-80. 1. SCOPE 1.1 Scope This Standard Practice est
17、ablishes requirements for copper alloy gate, globe, angle and check valves for plumbing and other purposes where a non-Class, CWP pressure and temperature rating is sufficient. This Standard Practice provides requirements for the following: a) Pressure-Temperature Ratings b) Materials c) End Connect
18、ions d) Dimensions e) Markings f) Testing and Inspection 1.2 References Standards and specifications adopted by reference in this Standard Practice, along with names and addresses of the sponsoring organizations, are shown in Annex A. It is not considered practical to refer to a specific edition of
19、each of the standards and specifications within the individual references herein. Instead, the specific edition references are included in Annex A. A product made in conformance with the edition reference that is applicable during the time of manufacture, and in all other respects conforming to this
20、 standard, will be considered to be in conformance even though the edition reference may be changed in a subsequent revision of this Standard Practice. 1.3 Description 1.3.1 Gate Valve A valve with a closure member, such as a gate, wedge, disc, or double disc, which moves on an axis perpendicular to
21、 the direction of flow. 1.3.1.1 Inside-Screw, Non-Rising Stem A type of gate valve design in which the disc rises on the threaded part of the stem instead of the stem rising through the bonnet (the stem does not rise or descend as the stem is turned). 1.3.1.2 Inside-Screw, Rising-Stem A type of gate
22、 or globe valve design in which the stem has both rotary and axial motion and rises as the stem is turned (the stem threads are between the stem seal and the closure member). 1.3.2 Globe Valve A valve with a closure member, such as a disc or plug, which moves on an axis perpendicular to the seat. 1.
23、3.3 Angle Valves An angle pattern variant of the globe valve in which the body connection ends are at right angles. 1.3.4 Check Valve A unidirectional valve that is opened by the fluid flow in one direction and closes automatically to prevent flow in the reverse direction. 2. PRESSURE-TEMPERATURE RA
24、TINGS 2.1 Basis of Rating The pressure-temperature ratings for assembled valves shall be determined by the material of the body, seats, stem seals, end connections or any other component or type of construction that would be restrictive. Manufacturers should be consulted for exact ratings applicable
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- MSSSP1392014COPPERALLOYGATEGLOBEANGLEANDCHECKVALVESFORLOWPRESSURELOWTEMPERATUREPLUMBINGAPPLICATIONSPDF

链接地址:http://www.mydoc123.com/p-822976.html