BS PD CLC TR 50173-99-1-2007 Cabling guidelines in support of 10 GBASE-T《支持10 GBASE-T电缆铺设指南》.pdf
《BS PD CLC TR 50173-99-1-2007 Cabling guidelines in support of 10 GBASE-T《支持10 GBASE-T电缆铺设指南》.pdf》由会员分享,可在线阅读,更多相关《BS PD CLC TR 50173-99-1-2007 Cabling guidelines in support of 10 GBASE-T《支持10 GBASE-T电缆铺设指南》.pdf(36页珍藏版)》请在麦多课文档分享上搜索。
1、Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 29/04/2008 08:07, Uncontrolled Copy, (c) BSIg49g50g3g38g50g51g60g44g49g42g3g58g44g55g43g50g56g55g3g37g54g44g3g51g40g53g48g44g54g54g44g50g49g3g40g59g38g40g51g55g3g36g54g3g51g40g53g48g44g55g55g40g39g3g37g60g3g38g50g51g60g53g44g42g43g55g3g47g36g58I
2、CS 35.110Cabling guidelines in support of 10 GBASE-TPUBLISHED DOCUMENTPD CLC/TR 50173-99-1: 2007PD CLC/TR 50173-99-1:2007Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 29/04/2008 08:07, Uncontrolled Copy, (c) BSIThis Published Document was published under the authority of the Standards Polic
3、y and Strategy Committee on 31 January 2008 BSI 2008ISBN 978 0 580 61549 8Amendments/corrigenda issued since publicationDate Commentscontract. Users are responsible for its correct application.National forewordThis Published Document is the UK implementation of CLC/TR 50173-99-1:2007.The UK particip
4、ation in its preparation was entrusted to Technical Committee TCT/7, Telecommunications Installation requirements.A list of organizations represented on this committee can be obtained on request to its secretary.This publication does not purport to include all the necessary provisions of a TECHNICAL
5、 REPORT CLC/TR 50173-99-1 RAPPORT TECHNIQUE TECHNISCHER BERICHT December 2007 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B - 1050 Brussels 20
6、07 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. CLC/TR 50173-99-1:2007 E ICS 35.110 English version Cabling guidelines in support of 10 GBASE-T Guide de cblage pour supporter le 10 GBASE-T Verkabelungsleitfaden zur Untersttzung vo
7、n 10 GBASE-T This Technical Report was approved by CENELEC on 2007-11-02. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, L
8、uxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 29/04/2008 08:07, Uncontrolled Copy, (c) BSIForeword This Technical Report was prepared by the Technical
9、 Committee CENELEC TC 215, Electrotechnical aspects of telecommunication equipment. The text of the draft was submitted to vote and was approved by CENELEC as CLC/TR 50173-99-1 on 2007-11-02. This Technical Report provides guidance whether an installed generic cabling channel meeting the requirement
10、s of EN 50173-1:2007, Class E, will support 10 GBASE-T as specified by IEEE 802.3an. The Technical Report also provides mitigation procedures to improve the performance of Class E channels to the point where the application is supported. Generic cabling channels meeting the requirements of EN 50173-
11、1:2007, Class F, will support IEEE 802.3an up to 100 m without mitigation. The support of IEEE 802.3an includes additional parameters and an extended frequency range beyond Class E. Conformance of installed cabling beyond the original cabling specifications must be determined on a case-by-case basis
12、, and is primarily needed due to new external noise requirements. Whether these requirements are met by a specific channel is influenced by the components and installation practices used. As IEEE 802.3an uses frequencies above those specified for Class E of EN 50173-1:2007, input from supplier and i
13、nstaller may be helpful to evaluate the performance of installed Class E channels. This Technical Report takes into account the design goals for IEEE 802.3an (10 GBASE-T) equipment such as: a) frequency signal range up to 500 MHz; b) meet EMC limits specified for EN 55022:2006, Class A; NOTE While I
14、EEE 802.3an specifies an application to meet Class A on unshielded cabling, meeting Class B may require application specific equipment and/or cabling that exceeds the requirements of this TR respectively. c) support a bit error rate of 1012; d) support operation over four-connector, four-pair balanc
15、ed cabling. It is expected that IEEE 802.3an will be supported by the following cabling channels specified in EN 50173-1:2007: Class F channels will support IEEE 802.3an to distances of at least 100 m; Class E channels using screened Category 6 components and assessed and mitigated according to the
16、guidelines in this Technical Report will support IEEE 802.3an over distances up to 100 m; Class E channels assessed and mitigated according to the guidelines in this Technical Report are expected to support IEEE 802.3an over distances from 55 m up to 100 m using unscreened Category 6 components. In
17、order to provide normative cabling specifications in explicit support of IEEE 802.3an, an amendment to EN 50173-1:2007 is under consideration. This amendment will provide new channel specifications that will include all characteristics needed to meet and/or exceed the IEEE 802.3an requirements (Clas
18、s EAand Class FA). This Technical Report is derived from ISO/IEC TR 24750, which has been developed by ISO/IEC JTC 1/SC 25 as a Technical Report Type 2. 2 CLC/TR 50173-99-1:2007Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 29/04/2008 08:07, Uncontrolled Copy, (c) BSIContents Introduction 5
19、1 Scope 7 2 Normative references . 7 3 Definitions and abbreviations 7 3.1 Definitions 7 3.2 Abbreviations 9 4 Channel requirements 9 4.1 General 9 4.2 Return loss10 4.3 Insertion loss .10 4.4 Near-end crosstalk loss (NEXT).11 4.5 Attenuation to crosstalk loss ratio near-end (ACR-N) .13 4.6 Attenuat
20、ion to crosstalk loss ratio far-end (ACR-F).14 4.7 Alien (exogenous) crosstalk.16 4.8 Propagation delay21 4.9 Delay skew21 5 Guidance for mitigation.21 5.1 Planning certification, measurement and documentation21 5.2 Mitigation techniques if in-channel parameters of the channel from Clause 4 are not
21、met 22 5.3 Mitigation techniques in case external parameters of the channel (alien noise) from 4.7 are not met.22 Annex A (informative) Permanent link performance guidelines24 Annex B (normative) Alien crosstalk margin computation26 Annex C (informative) Analytical approach to alien crosstalk mitiga
22、tion .31 Tables Table 1 Changes and additions to definitions in EN 50173-1:2007. 6 Table 2 Equations for return loss limits for a channel 10 Table 3 Return loss limits for a channel at key frequencies .10 Table 4 Equation for insertion loss limits for a channel11 Table 5 Insertion loss limits for a
23、channel at key frequencies 11 Table 6 Equations for NEXT limits for a channel .11 Table 7 NEXT limits for a channel at key frequencies .11 Table 8 Equations for PSNEXT limits for a channel.12 Table 9 PSNEXT limits for a channel at key frequencies.12 Table 10 ACR-N limits for a channel at key frequen
24、cies13 Table 11 PSACR-N limits for a channel at key frequencies .14 Table 12 Equation for ACR-F limits for a channel15 Table 13 ACR-F limits for a channel at key frequencies 15 Table 14 Equation for PSACR-F limits for a channel.15 3 CLC/TR 50173-99-1:2007Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA S
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BSPDCLCTR501739912007CABLINGGUIDELINESINSUPPORTOF10GBASET 支持 10 GBASET 电缆 铺设 指南 PDF

链接地址:http://www.mydoc123.com/p-588847.html