BS 7835-2007 Electric cables – nArmoured cables with nthermosetting insulation nfor rated voltages from n3 8 6 6 kV to 19 33 kV nhaving low emission of nsmoke and corrosive gases n.pdf
《BS 7835-2007 Electric cables – nArmoured cables with nthermosetting insulation nfor rated voltages from n3 8 6 6 kV to 19 33 kV nhaving low emission of nsmoke and corrosive gases n.pdf》由会员分享,可在线阅读,更多相关《BS 7835-2007 Electric cables – nArmoured cables with nthermosetting insulation nfor rated voltages from n3 8 6 6 kV to 19 33 kV nhaving low emission of nsmoke and corrosive gases n.pdf(64页珍藏版)》请在麦多课文档分享上搜索。
1、BS 7835:2007Electric cables Armoured cables with thermosetting insulation for rated voltages from 3.8/6.6 kV to 19/33 kV having low emission of smoke and corrosive gases when affected by fire Requirements and test methodsICS 29.060.20NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT
2、 LAWBRITISH STANDARDIncorporatingCorrigendum No. 1Publishing and copyright informationThe BSI copyright notice displayed in this document indicates when the document was last issued. BSI 2008ISBN 978 0 580 64040 7The following BSI references relate to the work on this standard:Committee reference GE
3、L/20/16Draft for comment 07/30143023 DCPublication historyFirst published June 1996Second edition, December 2000Third edition, November 2007Amendments issued since publicationAmd. no. Date Text affectedC1 August 2008 See 21.6 and 21.7BS 7835:2007 BSI 2008 iBS 7835:2007ContentsForeword iii1 Scope 12
4、Normative references 13 Terms and definitions 24 Voltage designation 45 Non-metallic materials 46 Conductors 47 Conductor screen 48 Insulation 49 Insulation screen 510 Assembly of three-core cables, including inner coverings andfillers 511 Metallic layer 712 Metallic armour 813 Oversheath 914 Markin
5、g 1015 End sealing 1116 Schedule of tests 1217 Test conditions 1418 Routine tests 1419 Sample tests 1620 Type tests Materials 2121 Type tests Electrical 25AnnexesAnnex A (informative) Recommendations for the selection of cables 29Annex B (normative) Information to be supplied and items to be agreed
6、32Annex C (informative) Recommendations for the installation of cables 33Annex D (informative) Guide to use of cables 36Annex E (normative) Fictitious calculation method for determination of dimensions of protective coverings 38Annex F (normative) Rounding of numbers 43Annex G (informative) Guidance
7、 on the scope of type tests 44Annex H (normative) Thickness measurements 47Annex I (normative) Test method for cold strippability of the extruded semi-conducting layer of an insulation screen 47Annex J (normative) Method for measurement of resistivity of extruded semi-conducting conductor screen and
8、 insulation screen 48Annex K (normative) Method for measurement of resistivity of lapped inner covering 51Annex L (normative) Wet compatibility test for galvanized steel wires and semi-conducting tape layers 52Annex M (normative) Abrasion test 53Annex N (normative) Test for shrinkage of oversheath o
9、n cable 54Annex O (normative) Insulation resistance constant test on oversheath 55Bibliography 56BS 7835:2007ii BSI 2008List of figuresFigure J.1 Test piece and arrangement of electrodes for measurement of resistivity of the conductor screen 50Figure J.2 Test piece and arrangement of electrodes for
10、measurement of resistivity of the insulation screen 51Figure L.1 Test cell for wet compatibility test of galvanized steel wires and semi-conducting tape layers 52Figure M.1 Abrasion test 54List of tablesTable 1 Nominal thickness of insulation 5Table 2 Thickness of extruded inner covering 6Table 3 No
11、minal diameter of round armour wires 8Table 4 Schedule of tests 12Table 5 Tolerances on temperature values 14Table 6 DC resistance of copper wire screen 15Table 7 Voltage for partial discharge test 15Table 8 Voltage test on complete cable 16Table 9 Number of samples for the four-hour voltage test, t
12、he hot set test on the insulation and the smoke emission test 17Table 10 Minimum transmittance levels 20Table 11 Voltages for four-hour voltage test 21Table 12 Mass of zinc coating 22Table 13 Compatibility requirements 24Table 14 Tan in relation to voltage 26Table 15 Tan in relation to temperature 2
13、6Table 16 Voltage for impulse voltage test 27Table A.1 Selection of cables for three-phase a.c. systems 30Table C.1 Bending radius during installation 33Table C.2 Bending radius during installation for cables adjacent to joints or terminations 33Table E.1 Fictitious diameter of conductor 40Table E.2
14、 Increase of diameter for concentric conductors and metallic screens 41Table M.1 Vertical force on cable during abrasion test 53Summary of pagesThis document comprises a front cover, an inside front cover, pages i to iii, a blank page, pages 1 to 56, an inside back cover and a back cover. BSI 2008 i
15、iiBS 7835:2007ForewordPublishing informationThis British Standard is published by BSI and came into effect on 30 November 2007. It was prepared by Subcommittee GEL/20/16, Medium/high voltage cables, under the authority of Technical Committee GEL/20, Electric cables. A list of organizations represent
16、ed on this committee can be obtained on request to its secretary. SupersessionThis British Standard supersedes BS 7835:2000, which is withdrawn.Information about this documentThis revision of BS 7835 has been prepared to bring the requirements up to date in accordance with current practice in the in
17、dustry and to align with the methods used for calculating cable component dimensions given in IEC 60502-2.This standard specifies requirements for cables in the rated voltage range from 3.8/6.6 kV up to 19/33 kV which are insulated with cross-linked polyethylene (XLPE) or ethylene propylene rubber c
18、ompound (EPR), with improved performance under fire conditions compared to the cables specified in BS 6622.Hazard warningsUse of this documentIt has been assumed in the preparation of this British Standard that the execution of its provisions will be entrusted to appropriately qualified and experien
19、ced people, for whose use it has been produced.Presentational conventionsThe provisions of this standard are presented in roman (i.e. upright) type. Its requirements are expressed in sentences in which the principal auxiliary verb is “shall”.Commentary, explanation and general informative material i
20、s presented in smaller italic type and does not constitute a normative element.Contractual and legal considerationsThis publication does not purport to include all necessary provisions of a contract. Users are responsible for its correct application.Compliance with a British Standard cannot confer i
21、mmunity from legal obligations.WARNING. This British Standard calls for the use of substances and/or procedures that can be injurious to health if adequate precautions are not taken. It refers only to technical suitability and does not absolve the user from legal obligations relating to health and s
22、afety at any stage.iv BSI 2008 This page deliberately left blankBS 7835:2007 BSI 2008 1BS 7835:20071 ScopeThis British Standard specifies requirements and test methods for the construction, dimensions and mechanical and electrical properties of armoured cables with thermosetting insulation for rated
23、 voltages from 3.8/6.6 (7.2) kV up to 19/33 (36) kV inclusive which, when assessed by the specified tests, produce lower levels of smoke and corrosive gases on exposure to fire compared to the cables specified in BS 6622. It covers cables designed for a maximum continuous conductor operating tempera
24、ture of 90 C and for a maximum short circuit conductor temperature of 250 C, for use in fixed installations such as networks or industrial installations. This British Standard specifies single-core and three-core cables for voltages in the range 3.8/6.6 (7.2) kV up to 19/33 (36) kV, with: a stranded
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS78352007ELECTRICCABLES NARMOUREDCABLESWITHNTHERMOSETTINGINSULATIONNFORRATEDVOLTAGESFROMN3866KVTO1933KVNHAVINGLOWEMISSIONOFNSMOKEANDCORROSIVEGASESNPDF

链接地址:http://www.mydoc123.com/p-547076.html