《ASTM B835-2014 Standard Specification for Compact Round Stranded Copper Conductors Using Single Input Wire Construction《使用单输入线路结构的致密圆铜绞接导线的标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM B835-2014 Standard Specification for Compact Round Stranded Copper Conductors Using Single Input Wire Construction《使用单输入线路结构的致密圆铜绞接导线的标准规格》.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: B835 04 (Reapproved 2009)B835 14Standard Specification forCompact Round Stranded Copper Conductors Using SingleInput Wire Construction1This standard is issued under the fixed designation B835; the number immediately following the designation indicates the year oforiginal adoption or, in
2、 the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers bare compact round stranded conductors made from uncoated
3、 copper wires of a single input wire(SIW) diameter for general use in covered or insulated electrical wires or cables. These conductors shall be constructed with oneor more layers of helically laid compacted wires (Explanatory Note 1, Note 2, and Note 3).1.2 The values stated in inch-pound units are
4、 to be regarded as standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information only and are not considered standard.1.2.1 For density, resistivity and temperature, the values stated in SI units are to be regarded as standard.1.3 This standard d
5、oes not purport to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatorylimitations prior to use.2. Referenced Documents2.1 The follo
6、wing documents of the issue in effect on date of material purchase form a part of this specification to the extentreferenced herein.2.2 ASTM Standards:2B3 Specification for Soft or Annealed Copper WireB263 Test Method for Determination of Cross-Sectional Area of Stranded ConductorsB354 Terminology R
7、elating to Uninsulated Metallic Electrical Conductors2.3 NIST Document:3NBS Handbook 100 Handbook 100Copper Copper Wire Tables3. Classification3.1 The conductors described in this specification are intended for subsequent insulation or covering. The classification of theseconductors is SIW compact.4
8、. Ordering Information4.1 Orders for material in accordance with this specification shall include the following information:4.1.1 Quantity of each size (Table 1);4.1.2 Conductor size, circular-mil area, or AWG (Section 8);4.1.3 Packaging (Section 1516), if required;4.1.4 Special package marking; and
9、4.1.5 Place of inspection (Section 1415).5. Requirements for Wires5.1 Before stranding and compacting, the copper wire shall meet all of the requirements of Specification B3.1 This specification is under the jurisdiction of ASTM Committee B01 on Electrical Conductors and is the direct responsibility
10、 of Subcommittee B01.04 on Conductorsof Copper and Copper Alloys.Current edition approved Oct. 1, 2009Sept. 1, 2014. Published January 2010September 2014. Originally approved in 1993. Last previous edition approved in 20042009as B835 04.B835 04 (2009). DOI: 10.1520/B0835-04R09.10.1520/B0835-14.2 For
11、 referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standardsstandards Document Summary page on the ASTM website.3 Available from National Institute of Standards and Tech
12、nology (NIST), 100 Bureau Dr., Stop 1070, Gaithersburg, MD 20899-1070, http:/www.nist.gov.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible
13、 to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West C
14、onshohocken, PA 19428-2959. United States16. Joints6.1 Welds and brazes may be made in rods or in wires prior to final drawing.6.2 Welds and brazes may be made in the individual wires for compact conductors, but they shall not be closer together than1 ft (0.3 m) for conductor of 19 wires or less or
15、closer than 1 ft (0.3 m) in a layer for conductor of more than 19 wires.6.3 No joint or splice shall be made in a compact-stranded conductor as a whole.7. Lay7.1 The length of lay shall not be less than 8 or more than 16 times the outside diameter of the completed conductor.7.2 The direction of lay
16、of the outer layer shall be left-hand, and it may be reversed or unidirectional in successive layers.7.3 Other lay requirements may be furnished upon special agreement between the manufacturer and the purchaser.8. Construction8.1 The construction of the compact round SIW stranded conductors shall be
17、 as given in Table 1.8.2 Wires used in the fabrication of the compact round conductor shall be of such dimensions as to produce a finished conductoras prescribed in Table 1.9. Density9.1 For the purpose of calculating mass per unit length, cross sections, and so forth, the density of the copper shal
18、l be takenas 8.89 g/cm3 (0.32117 lb/in.3) at 20C.10. Density Mass and Electrical Resistance9.1 For the purpose of calculating mass per unit length, cross sections, and so forth, the density of the copper shall be takenas 8.89 g/cm3 (0.32117 lb/in.3) at 20C.10.1 The mass and electrical resistance of
19、a unit length of stranded unsealed conductor are a function of the length of lay. Theapproximate mass and electrical resistance may be determined using the standard increments shown inan increment of 2 %. Table2. When greater accuracy is desired, the increment based on the specific lay of the conduc
20、tor may be calculated (Explanatory Note4).10.2 The maximum electrical resistance of a unit length of stranded conductor shall not exceed 102 % of the nominal dcresistance shown in Table 1. When the dc resistance is measured at other than 20C, it is to be corrected by using the multiplyingfactor give
21、n in Table 2.10.3 For conductors to be used in covered or insulated wires or cables, dc resistance measurement may be used instead of themethod outlined in Section 1011, to determine compliance with this specification.TABLE 1 Construction Requirements of Compact Round SIW-Stranded Copper ConductorsC
22、onductor Size MinimumNumber of WiresCompact Conductor Diameter Mass/1000 ft,lb/1000 ftMass/km,kg/kmdc Resistance at 20CCircular, mils AWG mm2 in. mm /1000 ft /km1 000 000 . 507 53 1.060 26.9 3086 4590 0.0106 0.0347900 000 . 456 53 0.999 25.4 2780 4140 0.0118 0.0386800 000 . 405 53 0.938 23.8 2469 36
23、80 0.0132 0.0433750 000 . 380 53 0.908 23.0 2316 3450 0.0141 0.0462700 000 . 355 34 0.877 22.3 2160 3220 0.0151 0.0495650 000 . 329 34 0.845 21.4 2006 2990 0.0163 0.0535600 000 . 304 34 0.813 20.6 1850 2760 0.0176 0.0577550 000 . 279 34 0.775 19.7 1700 2530 0.0192 0.0630500 000 . 253 30 0.736 18.7 1
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMB8352014STANDARDSPECIFICATIONFORCOMPACTROUNDSTRANDEDCOPPERCONDUCTORSUSINGSINGLEINPUTWIRECONSTRUCTION

链接地址:http://www.mydoc123.com/p-462438.html